    Have a look at the manual Alpha Tool.Com.HK Limited Moisture Test Kit User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 67 Alpha Tool.Com.HK Limited manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Part No: MTK005 Version 1
    103 Bauer Drive, Oakland, NJ 07436 • 800-648-7229 • Fax: 800-286-01 14
    www.alpha-tools.com
    Alpha® Moisture Test Kit
    Instruction Manual
    MANUAL  
    						
    							2
    Table of CoNTeNTs
     
    Introduction ........................................................................\
    ......... 3
    ASTM F 1869 Protocol Checklist For Conducting   
       The Calcium Chloride Test  ...................................................... 3
    Quantative Test Method for Determining Moisture   
       Vapor Emission Rate (ASTM F 1869)  .....................................4
      Purpose  ........................................................................\
    ..... 4
      Contents ........................................................................\
    .... 4
      Required Tools  .................................................................. 4
      Applicable Standards  ........................................................ 4
      Preparation  ........................................................................\
     5
    Test Instructions ........................................................................\
    .. 6
    Calculations  ........................................................................\
    ........ 8
    Bias & Precision of the Test  ........................................................ 9
    Health and Safety  ....................................................................... 9
    Limited Warranty & Terms of Sale  ..............................................9
    Concrete Moisture Vapor Emission Log Sheet  .........................10  
    						
    							3
    INTroduCTIoN
    Thank you for purchasing the alpha® Moisture Test Kit, a calcium chloride test for 
    determining if the concrete slab is suitable for floor covering or polymer coating 
    installations.
    The test works by absorbing moisture in a vapor form that is exiting the slab’s 
    surface due to natural environmental factors over a period of time. 
    The test measures an approximate 70 square inches area of concrete surface for 
    60 to 72 hours, then a simple calculation is followed that determines the volume 
    of the vapor emission. 
    The Moisture Vapor Emission Rate (MVER) is the equivalent weight of water (if 
    the gas turned into liquid) that emits from 1,000 square feet of concrete surface 
    area in 24 hours time.
     
      CauTIoN!
    To ensure correct use, read this Instruction Manual and the product’s Limited 
    Warranty and Terms of sales prior to use of this product. The use of the product 
    implies that the Buyer and User agrees to Manufacturer’s Limited Warranty and 
    Terms of sale.  Keep this manual in a place where operators can access it easily 
    whenever necessary!
    asTM f 1869 ProT oCol CHeCKlIsT for CoNduCTING 
    THe CalCIuM CHlorIde TesT
    before starting the test, make sure the following conditions are met: 
    1.  Provide the number of test kits required.
    Install 3 test kits for areas up to 1,000 sq. ft or smaller, add 1 test kit for each 
    additional 1,000 sq. ft. area thereafter. 
    2.  Ensure interior environment is conditioned correctly before performing 
    tests. 
    a properly conditioned building interior has a temperature between 65 to \
    85 
    degrees F. with a relative humidity of 40 to 60 % for at least 48 hours before 
    the test begins and remains consistent throughout the testing period of 60 to 
    72 hours. Record values on log sheet.   
    						
    							4
    3.  Clean the concrete surface of any foreign substances. 
     A foreign substance can be floor covering, adhesive residue, epoxy coating, 
    paint, curing and sealing compounds, waxes, dirt or oil stains, or any other 
    material residue on the slab surface. Remove concrete contaminants by shot 
    blasting, abrasive grinding wheel or diamond cup wheel. The use of wire brushes 
    or razor scraping may not be suitable for achieving a clean, open concrete slab 
    surface. 
    4.  Prepare test area and schedule testing. 
      ASTM requires that a minimum of 20 x 20 inches of concrete surface area be 
    cleaned for each test (as described above) and allowed to remain open for at 
    least 24 hours before setting the calcium chloride test. once the test is placed, 
    it must remain undisturbed for a period of 60 to 72 hours. Always plan carefully 
    in advance of testing to ensure open time after preparation and exposure time 
    during the testing period will allow for proper placement and retrieval. 
    QuaNTIT aTIVe TesT MeTHod for deTerMINING MoIsTure 
    V aPor eMIssIoN ra Te (asTM f 1869)
    ►PurPose:
    alpha
    ® Moisture Test Kit is designed to quantitatively measure the rate of moisture 
    vapor emission.
    ►CoNTeNTs:
    Each test kit consists of one cylindrical container filled with anhydrous calcium 
    chloride and one transparent plastic dome with pre-installed sealant aro\
    und the 
    perimeter. 
    ►reQuIred T ools: (NoT INCluded)
    Surface grinder with vacuum mount, safety goggles, dust respirator, protective 
    gloves, cloth rags, utility knife, scale capable of measuring to nearest 0.1 gram 
    and duct tape.
    ►aPPlICable sT aNdards:
    A person using this test kit shall strictly follow the instructions given in the latest 
    asTM f 1869 published by  american society for Testing & Materials. The copies    
    						
    							5
    of asTM documents can be obtained from  american society for Testing and Ma-
    terials. 100 Barr Harbor Drive, West Conshohocken, PA 19428. Tel: 610-832-9585 
    Fax: 610-832-9555. The documents may also be purchased on the internet from 
    www.astm.org.
    ►PreP araTIoN:
    1.   Survey Job Site Conditions - Verify environmental controls are operational. 
    The building temperature and humidity should be representative of what it 
    would be during normal use. The temperature should be between 65 to 85 
    degree and the relative humidity between 40% and 60% for a minimum of 48 
    hours prior to conducting tests.
    2.  schedule  accordingly - The tests need to remain undisturbed for a minimum of 
    60 hours and a maximum 72 hours. On the first day preparation will take place 
    and on the following day the tests will be set and retrieved in 60 to 72 hours.
    3.  Test Location & Frequency - Place tests throughout the area with some in the 
    middle of the building, at the perimeter, over cracks and joints and especially 
    in areas of potential moisture. The tests should be performed at a rate \
    of three 
    tests for the first 1,000 square feet and one test for each additional 1,000 sq feet.
    You need to keep track of the following for your records:
     
    1.  location of the tests 
    2.  Test number 
    3.  ambient room temperature 
    4.  ambient humidity 
    5.  start date/end date 
    6.  start time/end time 
    7.  Exposure time (15-minute increments) 
    8.  start weight/ending weight 
    9.  Weight gain 
    10.  Note any unusual occurrences or damage to kit 
    11.  results of test 
    12.  Flooring manufacturer’s moisture limits for materials to be installed. 
    13.  Moisture testing can be done with relative accuracy; however, if one is to stray 
    from the test methods, your test could produce faulty results.    
    						
    							6
    TesT INsTruCTIoNs
    The following testing procedure is brief and is not meant to replace the\
     most current 
    ASTM standards. Therefore, the User must get acquainted with the applicable 
    current asTM standard and osHa  safety regulations prior to using this test kit.
    sTeP 1
    Remove any foreign objects such as overspray, curing 
    compound and sealers from the concrete surface using 
    mechanical devices such as a grinder (photo shows 
    alpha
    ® Ecogrinder with dust carriage attached). Remove 
    dust from the concrete surface to insure proper adhesion 
    of the sealant. Strictly follow guidelines given by Occupa-
    tional safety & Health  administration (osHa). 
    sTeP 2
    Weigh the container with the vi-
    nyl tape seal at the test location 
    immediately prior to initiating the 
    test (W1).
    Note:  b e sure the scale is set to grams, ounce scales will  not work for this test. 
    Weigh to the nearest 0.1 gram and note this initial weight on the top of \
    the container 
    label using felt tip pen or permanent marker as well as the time and date the test 
    was started (T1).
    sTeP 3
    Remove  the sealing tape from 
    the plastic container. Make sure 
    the tape does not get dirty or 
    lost since it will be needed to 
    reseal the container at the end 
    of the test. 
    Note:  for best results, stick the tape on the outer wall of 
    the dome unit to keep it safe.     
    						
    							7
    sTeP 4
    Peel off the paper protective backing from the black seal-
    ant that is around the dome and discard. Make sure the 
    sealant material does not contact objects or clothing as it 
    is very sticky and intended to provide a secure, longlasting 
    seal to the concrete throughout the duration of the test.
    sTeP 5
    Carefully remove the lid from the container that holds 
    the calcium chloride crystals.  do not spill the crystals.  
    It is easiest to turn it over and place it under the dish as  
    shown.  It may also be secured to the top of the dome or 
    any other location as long as it is stored safely for reuse.
    sTeP 6 
    Install the test kit on the concrete floor.  First, place the 
    open calcium chloride container on the concrete floor.  
    Make sure the crystals are relatively level.  If any crystals 
    are spilled the test can be invalid.
    STEP 7
    Next, immediately place the dome unit over the center of the dish.  Press firmly 
    along the edges of the sealant material to securely bond 
    the unit to the floor. To test for an airtight seal, press 
    firmly on the center of the cover. The cover should resist 
    pressure, if properly sealed. 
    a llow the test kit to remain undisturbed for a period of 60 
    to 72 hours. Note the ambient temperature and humidity 
    at the test area.    
    						
    							8
    sTeP 8
    After 60 to 72 hours, remove the dome with a razor. Retrieve the dish with the 
    calcium chloride and immediately place the lid back on and reseal using saved 
    vinyl tape.  Re-weigh the container on the same gram scale used at the start of 
    the test.  record weight, date and time (W2) (T2).
    Note the weight as final weight (W2). Do not spill any of the calcium chloride 
    crystals from the container. If any crystals are spilled, the test must be rerun with 
    a new test kit. 
    CalCula TIoNs
    1. Determine the Exposure Time in hours. 
    Exposure time in hours: T = T2 - T1(Time = End Time - Start Time)
    2.  determine the weight gain of calcium chloride. 
    Weight gain in grams; ∆W = W2-W1
    (Weight  Change = End Weight - Start Weight)
     
    Moisture Vapor Emission Rate (pounds/1000 sq. ft/24 hours)
    Moisture Vapor Emission Rate = 120 x ∆W
                  T
    alpha Professional Tools
    ® also provides on-line calculator at www.alpha-tools.
    com/mcalc.aspx.    
    						
    							9
    bIas & PreCIsIoN of THe TesT
    Follow guide lines provided by the latest ASTM. Our experience indicates that 
    the test results may vary with environmental and seasonal changes. The test 
    determines the rate of moisture vapor emission at the time of the test only. It does 
    not predict future moisture vapor emission rate or the performance of the flooring 
    material. The test performed at the same location at a different time ma\
    y produce 
    different results. 
    HealTH aNd  safeTY
    The chemical product included in this kit contains Calcium Chloride  anhydrous 
    (CaCl2).  a Material safety data sheet for Calcium Chloride is enclosed with the 
    test kits. Please read it carefully. dispose of used product in accordance with local, 
    state or federal regulations. Keep children & pets away from the test kit and test 
    area. do not inhale or ingest this product. In case of emergency, contact nearest 
    hospital and nearest Poison Control Center. National Poison Center’s phone 
    number is 1-800-222-1222.
    lIMITed W arraNTY & TerMs of sale
    a lpha Professional Tools
    ® sole responsibility and liability under this warranty shall be 
    to supply replacement test kit for any test kit items warranted hereunde\
    r shown to 
    be defective in manufacturing. Since the use of the test kit is beyond our control we 
    can not accept damage in excess of the purchase price of this product. Store the test 
    kit in a dry place and use it within 1 year from receiving. Alpha Professional Tools
    ® 
    makes no other warranty, expressed or implied, with respect to its products. Defects 
    in materials caused by misuse, mishandling, improper storage, improper a\
    pplication, 
    improper combination with product of others, or any other failure to str\
    ictly follow 
    alpha Professional Tools
    ® guidance and latest  asTM standards are not warranted 
    under any circumstances.  alpha Professional Tools® shall not be responsible for 
    direct, indirect, incidental, punitive or consequential damages arising from the use 
    of the test kit regardless of the cause.  buyer and u ser assume all liabilities for 
    any loss, damage or injury to persons or property arising out of, connected with 
    or resulting form the use of  alpha Professional Tools
    ® products, either alone or 
    in combinations with other products. b y use of this product the buyer and user 
    accept the limited Warranty and Terms of s ale. any dispute against the  alpha 
    Professional Tools
    ® or its Employees or agents or successors shall be resolved 
    by a binding arbitration in accordance with the  american  arbitration  association in 
    Oakland, Bergen County, New Jersey, United States of America.    
    						
    							10
    CoNCreTe MoIsTure VaPor eMIssIoN loG sHeeT
    report date:  _________________  site location:__________________________________________
    Test Conducted by:______________________________Phone: ____________________________
    sTarTING da Te of TesT:_________________  eNdING da Te of TesT __________________
    building Temperature: ______________________  building Temperature:  _____________________ 
      
    Relative Humidity: __________________________  Relative Humidity:________________________
        
      sT arT of TesT  eNd of TesT    Wt Gain Total MVer
    Test #  location  weight time weight  time in grams    hours Pounds
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    ________  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______
    _______  _________________  ______ _____ ______  _____ ________   _____ _______   
    						