    Have a look at the manual American Water Heater Commercial Gas NonDampered Water Heater CG3275T75 CG32100T77 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11
    water pIpInG
    water (potable) heatInG  and space heatInG
    This	water	 heater	 shall	not	be	connected	 to	any	 heating	 systems 	
    or	 component(s)	 used	with	a	non-potable	 water	heating	 appliance.
    All	 piping	 components	 connected	to	this	 unit	 for	space	 heating 	
    applications	shall	be	suitable	for	use	with	potable	water.
    Toxic	 chemicals,	 such	as	those	 used	for	boiler	 treatment 	shall	 not	
    be	introduced	into	this	system.
    When	 the	system	 requires	 water	for	space	 heating	 at	temperatures 	
    higher	 than	required	 for	domestic	 water	purposes,	 a	mixing	 valve	
    must	 be	installed.		 Please	refer	to	Figure	 2	for	 suggested	 piping	
    arrangement. 	
    These	 water	heaters	 cannot	be	used	 in	space	 heating	 applications 	
    only.
    closed w ater sYsteMs
    Water	supply	 systems	 may,	because	 of	code	 requirements	 or	
    such	 conditions	 as	high	 line	pressure,	 among	others,	 have	
    installed	 devices	such	as	pressure	 reducing	valves,	check	
    valves,	 and	back	 flow	preventers.	 Devices	such	as	these	 cause	
    the	water	system	to	be	a	closed	system.
    therMal expansIon
    As	 water	 is	heated,	 it	expands	 (thermal	expansion).	 In	a	closed 	
    system	 the	volume	 of	water	 will	grow	 when	 it	is	 heated.	 As	the	
    volume	 of	water	 grows	 there	will	be	a	corresponding	 increase	in	
    water	 pressure	 due	to	thermal	 expansion.	 Thermal	expansion 	
    can	 cause	 premature	 tank	failure	 (leakage).	 This	type	 of	failure 	
    is	 not	 covered	 under	the	limited	 warranty.	 Thermal	expansion 	
    can	 also	 cause	 intermittent	 Temperature-Pressure	 Relief	Valve	
    operation:	 water	discharged	 from	the	valve	 due	to	excessive 	
    pressure	 build	up.	This	 condition	 is	not	 covered	 under	the	limited 	
    warranty.	 The	Temperature-Pressure	 Relief	Valve	is	not	 intended 	
    for	the	constant	relief	of	thermal	expansion.
    A 	properly	 sized	thermal	 expansion	 tank	must	 be	installed	 on	
    all	 closed	 systems	 to	control	 the	harmful	 effects	of	thermal 	
    expansion.	 Contact	a	local	 plumbing	 service	agency	 to	have	 a	
    thermal	expansion	tank	installed.
    fIGure 7.
    NOTE:	 To	protect	 against	 untimely	 corrosion	of	 hot	 and	cold 	
    water	 fittings,	 it	is	 strongly	 recommended	 that	di-electric	 unions	
    or	 couplings	 be	installed	 on	this	 water	 heater	 when	connected	 to	
    copper	pipe.
    Figure	 7	shows	 the	typical	 attachment	 of	the	 water	 piping	 to	the 	
    water	 heater.	 The	water	 heater	 is	equipped	 with	1”	NPT 	threaded 	
    nipple	 (75	gallon	 models)	 or	1.25”	 NPT	threaded	 nipple	(100	
    gallon	models)	water	connections.
    teMperature-pressure relIef v alve
    Explosion Hazard
    Temperature-Pressure Relief  Valve
    must comply with  ANSI Z21.22-
    CSA 4.4 and  ASME code.
    Properly sized temperature-
    pressure relief valve must be
    installed in opening provided .
    Can result in overheating and
    excessive tank pressure .
    Can cause serious injury or death.
    This	water	 heater	 is	provided 	with 	a	 properly	 rated/sized	 and	
    certified	 combination	 Temperature-Pressure	 Relief	Valve	 (T&P	
    valve)	 by	the	 manufacturer.	 The	valve	 is	certified	 by	a	nationally 	
    recognized	 testing	laboratory	 that	maintains	 periodic	inspection 	
    of	 production	 of	listed	 equipment	 of	materials	 as	meeting	 the	
    requirements	 for	Relief	 Valves	 for	Hot	 Water	 Supply	 Systems, 	
    ANSI	Z21.22	•	CSA 	4.4,	and	the	code	requirements	of	 ASME.
    If	 replaced,	 the	new	 T&P	valve	 must	meet	 the	requirements	 of	
    local	 codes,	 but	not	less	 than	 a	combination	 Temperature-Pressure 	
    Relief	 Valve	rated/sized	 and	certified	 as	indicated	 in	the	 above 	
    paragraph.	 The	new	 valve	 must	be	marked	 with	a	maximum	 set	
    pressure	 not	to	exceed	 the	marked	 hydrostatic	 working	pressure 	
    of	 the	 water	 heater	 (150	psi	=	1,035	 kPa)	and	a	discharge	 capacity	
    not	 less	 than	 the	water	 heater	 Btu/hr	or	kW	 input	 rate	as	shown 	
    on	the	water	heater’s	model	rating	label. 
    						
    							12
    NOTE:	In	addition	 to	the	 factory	 installed	 Temperature-Pressure 	
    Relief	 Valve	on	the	 water	 heater,	 each	remote	 storage	 tank	that	
    may	 be	installed	 and	piped	 to	a	water	 heating	 appliance	 must	also	
    have	 its	own	 properly	 sized,	rated	 and	approved	 Temperature-
    Pressure	 Relief	Valve	installed.	 Call	the	toll	free	 technical	 support	
    phone	 number	 listed	on	the	 back	 cover	 of	this	 manual	 for	technical 	
    assistance	 in	sizing	 a	Temperature-Pressure	 Relief	Valve	 for	remote 	
    storage	tanks.
    For	 safe	 operation	 of	the	 water	 heater,	 the	Temperature-Pressure	
    Relief	 Valve	must	not	be	removed	 from	its	designated	 opening	nor	
    plugged.	 The	Temperature-Pressure	 Relief	Valve	must	be	installed	
    directly	 into	the	fitting	 of	the	 water	 heater	 designed	 for	the	 relief	 valve. 	
    Install	 discharge	 piping	so	that	 any	discharge	 will	exit	 the	pipe	 within	
    6	 inches	 (15.2	cm)	above	 an	adequate	 floor	drain,	 or	external	 to	the	
    building.	 In	cold	 climates	 it	is	 recommended	 that	it	be	 terminated	 at	
    an	 adequate	 drain	inside	 the	building.	 Be	certain	 that	no	contact	 is	
    made	 with	any	live	electrical	 part.	The	discharge	 opening	must	not	
    be	 blocked	 or	reduced	 in	size	 under	 any	circumstances.	 Excessive	
    length,	 over	30	feet	 (9.14	 m),	or	use	 of	more	 than	four	elbows	 can	
    cause	restriction	and	reduce	the	discharge	capacity	of	the	valve.
    No	 valve	 or	other	 obstruction	 is	to	 be	 placed	 between	 the	
    Temperature-Pressure	 Relief	Valve	and	the	tank.	 Do	not	 connect 	
    discharge	 piping	directly	 to	the	 drain	 unless	 a	6”	 (15.2	 cm)	air	gap	 is	
    provided. 	To	 prevent 	bodily	 injury,	hazard	 to	life, 	or	 property	 damage,	
    the	 relief	 valve	 must	be	allowed	 to	discharge	 water	in	adequate 	
    quantities	 should	circumstances	 demand.	If	the	 discharge	 pipe	is	
    not	 connected	 to	a	drain	 or	other	 suitable	 means,	the	water	 flow	
    may	cause	property	damage.
    Wa ter Damage Hazar d
    • Temperature- Pressure Relief  Valve discharge
      pipe must terminate at adequate drain.
    CAUT ION
    t&p valve discharge pipe requirements:
    •	 Shall	not	be	smaller	in	size	than	the	outlet	pipe	size	of	the	valve, 	
    or	have	any	reducing	couplings	or	other	restrictions.
    •	 Shall	not	be	plugged	or	blocked.
    •	 Shall	not	be	exposed	to	freezing	temperatures.
    •	 Shall	be	of	material	listed	for	hot	water	distribution.
    •	 Shall	be	installed	so	as	to	allow	complete	drainage	of	both	the 	
    Temperature-Pressure	Relief	Valve	and	the	discharge	pipe.
    •	 Must	terminate	a	maximum	of	six	inches	above	a	floor	drain	
    or	external	to	building.	In	cold	climates,	it	is	recommended	
    that 	discharge	pipe	be	terminated	at	an	adequate	drain	inside 	
    building.
    •	 Shall	not	have	any	valve	or	other	obstruction	between	the	
    relief	valve	and	the	drain.
    Burn hazard.
    Hot water discharge. Keep clear of  Temperature-
    Pressure Relief V alve
    discharge outlet.
    The	 Temperature-Pressure	 Relief	Valve	must	be	manually	 operated	
    at 	least 	twice	 a	year. 	Caution	 should	be	taken	 to	ensure	 that	(1)	 no	
    one	 is	in	 front	 of	or	 around	 the	outlet	 of	the	 Temperature-Pressure 	
    Relief 	Valve	 discharge	 line,	and	 (2)	the	 water 	manually 	discharged 	
    will 	not	 cause 	any	 bodily	 injury	or	property	 damage	because 	
    the	 water	 may	be	extremely	 hot.	If	after	 manually	 operating	 the	
    valve,	 it	fails	 to	completely	 reset	and	continues	 to	release	 water,	
    immediately	 close	the	cold	 water	 inlet	to	the	 water	 heater,	 follow	the	
    draining	 instructions	 in	this	 manual,	 and	replace	 the	Temperature-
    Pressure	 Relief	Valve	with	a	properly	 rated/sized	 new	one.
    NOTE:	 The	purpose	 of	a	Temperature-Pressure	 Relief	Valve	is	to	
    prevent	 excessive	 temperatures	 and	pressures	 in	the	 storage	 tank.	
    The	 T&P	valve	 is	not 	intended	 for	the	 constant	 relief	of	thermal 	
    expansion.	 A	properly	 sized	thermal	 expansion 	tank	 must	 be	installed 	
    on	 all	closed	 systems	 to	control	 thermal	 expansion, 	see	 Closed 	
    Water	 Systems	 and	Thermal	 Expansion	 on	page	 11.
    If	 you	 do	not	 understand	 these	instructions	 or	have	 any	questions	
    regarding	 the	Temperature-Pressure	 Relief	Valve	 call	the	toll	free	 number 	
    listed	on	the	back	cover	of	this	manual	for	technical	assistance.
    fIllInG the w ater heater
    Never	use	this	water	 heater	 unless	 it	is	 completely	 full	of	water.	 To	
    prevent	 damage	 to	the	 tank,	 the	tank	 must	 be	filled	 with	water.	 Water	
    must	 flow	from	 the	hot	water	 faucet	 before	 turning	 “ON”	gas	to	the	
    water	heater.
    To	fill	the	water	heater	with	water:
    1.		Close	 the	water	 heater	 drain	valve	 by	turning	 the	handle	 to	the	
    right	 (clockwise).	 The	drain	 valve	 is	on	 the	 lower	 front	of	the	 water	
    heater.
    2.	 Open	 the	cold	 water	 supply	 valve	to	the	 water	 heater. 		  
    NOTE:	 The	cold	 water	 supply	 valve	must	be	left	 open	 when	 the	
    water	heater	is	in	use.
    3. 		To	 insure	 complete	 filling	of	the	 tank,	 allow	 air	to	exit	 by	opening	 the	
    nearest	 hot	water	 faucet.	 Allow	water	 to	run	 until	 a	constant	 flow	is	
    obtained.	 This	will	let	air	out	of	the	water	heater	and	the	piping.
    4.	 Check	 all	water	 piping	 and	connections	 for	leaks.	 Repair	 as	
    needed.
    aIr requIreMents
    Breathing Hazard - Carbon Monoxide Ga s
    Install water heater in accordance with
    the Instruction Manual and NFPA 54 or
    CAN/CSA-B149.1.
    To  avoid injur y, combustion and ventilation
    air must be taken from outdoors.
    Do not place chemical vapor  emitting
    products near water heater .
    Breathing carbon monoxide can cause brain damage or
    death. Always read and understand instruction manual.
    For	safe	 operation	 an	adequate	 supply	of	fresh	 uncontaminated	 air	for	
    combustion	and	ventilation	must	be	provided.
    An	 insufficient	 supply	of	air	 can	 cause	 recirculation	 of	combustion 	
    products	 resulting	in	contamination	 that	may	 be	hazardous	 to	life. 	
    Such	 a	condition	 often	will	result	 in	a	yellow,	 luminous	 burner	flame,	
    causing	 sooting	of	the	 combustion	 chamber,	burners	and	flue	tubes	
    and	creates	a	risk	of	asphyxiation.
    Do	 not	 install	 the	water	 heater	 in	a	confined	 space	unless	 an	adequate 	
    supply	 of	air	 for	 combustion	 and	ventilation	 is	brought	 in	to	 that	 space	
    using	 the	methods	 described	 in	the	 Confined	 Space	section	 that	follows. 	
    Never	 obstruct	 the	flow	 of	ventilation	 air.	If	you	 have	 any	doubts	 or	
    questions	 at	all,	 call	 your	 gas	supplier.	 Failure	to	provide 	the 	proper	 
    						
    							13
    amount	of	combustion	 air	can	 result	 in	a	fire	 or	explosion	 and	cause	 property 	
    damage,	serious	bodily	injury	or	death.
    unconfIned space
    An	 Unconfined	 Space	is	one	 whose	 volume	 is	not	 less	 than	 50	
    cubic	 feet	per	1,000	 Btu/hr	 (4.8	cubic	 meters	 per	kW)	 of	the 	
    total	 input	 rating	 of	all	 appliances	 installed	in	the	 space.	 Rooms	
    communicating	 directly	with	the	space,	 in	which	 the	appliances 	
    are	 installed, 	through	 openings	 not	furnished	 with	doors, 	are 	
    considered	a	part	of	the	unconfined	space.
    Makeup	 air	requirements	 for	the	 operation	 of	exhaust	 fans,	kitchen 	
    ventilation	 systems,	clothes	dryers	and	fireplaces	 shall	also	be	
    considered	 in	determining	 the	adequacy	 of	a	space	 to	provide 	
    combustion,	ventilation	and	dilution	air.
    unusuall Y tIGht constructIon
    In	 unconfined	 spaces	in	buildings,	 infiltration	 may	be	adequate	 to	
    provide	 air	for	 combustion,	 ventilation	and	dilution	 of	flue	 gases. 	
    However,	 in	buildings	 of	unusually	 tight	construction	 (for	example, 	
    weather	 stripping,	 heavily	insulated,	 caulked,	vapor	barrier,	 etc.)	
    additional	 air	must	 be	provided	 using	the	methods	 described	 in	
    the	Confined	Space	section	that	follows.
    confIned space
    A 	Confined	 Space	is	one	 whose	 volume	 is	less	 than	 50	cubic	 feet	per	
    1,000	 Btu/hr	 (4.8	cubic	 meters	 per	kW)	 of	the	 total	 input	 rating	 of	all	
    appliances	installed	in	the	space.
    Openings	 must	be	installed	 to	provide	 fresh	air	for	 combustion,	 ventilation	
    and	 dilution	 in	confined	 spaces.	The	 required	 size	for	the	 openings 	is 	
    dependent	 on	the	 method	 used	to	provide	 fresh	air	to	the	 confined	 space	
    and	the	total	Btu/hr	input	rating	of	all	appliances	installed	in	the	space.
    dIrect  vent applIances
    Appliances	 installed	in	a	Direct 	Vent 	configuration	 that	derive	 all	
    air	 for	combustion	 from	the	outdoor	 atmosphere	 through	sealed	
    intake	 air	piping	 are	not	factored	 in	the	 total	 appliance	 input	Btu/hr	
    calculations	 used	to	determine	 the	size	 of	openings	 providing	fresh	
    air	into	confined	spaces.
    exhaust f ans
    Where	exhaust 	fans 	are 	installed, 	additional 	air 	shall 	be 	provided 	
    to 	replace 	the	exhausted 	air.	When 	an	exhaust 	fan	is	installed 	in	
    the	 same	 space	 with	a	water	 heater, 	sufficient 	openings	 to	provide 	
    fresh	 air	must	 be	provided	 that	accommodate	 the	requirements 	
    for	 all	appliances	 in	the	 room	 and	the	exhaust	 fan.	Undersized 	
    openings	 will	cause	 air	to	be	 drawn	 into	the	room	 through	 the	water 	
    heater’s	 vent	system	 causing	 poor	combustion.	 Sooting,	serious	
    damage 	to 	the 	water 	heater 	and 	the 	risk 	of 	fire 	or 	explosion 	may 	
    result.	It	can	also	create	a	risk	of	asphyxiation.
    louvers and GrIlles
    The	 free	areas	 of	the	 fresh	 air	openings	 in	the	 instructions	 that	follow	 do	not 	
    take	 in	to	 account 	the	 presence	 of	louvers,	 grilles	or	screens	 in	the	 openings.
    The	 required	 size	of	openings	 for	combustion,	 ventilation	and	dilution 	
    air	 shall	 be	based	 on	the	 “net	 free	area”	 of	each	 opening.	 Where	the	
    free	 area	 through	 a	design	 of	louver	 or	grille	 or	screen	 is	known,	 it	shall 	
    be	 used	 in	calculating	 the	size	 of	opening	 required	 to	provide	 the	free 	
    area	 specified.	 Where	the 	louver	 and	grille 	design 	and 	free 	area	 are	not 	
    known,	 it	shall	 be	assumed	 that	wood	 louvers	 will	have	 25%	free	area 	
    and	 metal	 louvers	 and	grilles	 will	have	 75%	free	area.	 Non	motorized 	
    louvers	and	grilles	shall	be	fixed	in	the	open	position.
    fresh  aIr openInGs for confIned spaces
    The	following	 instructions	 shall	be	used	 to	calculate	 the	size, 	
    number	 and	placement	 of	openings	 providing	 fresh	air	for	
    combustion,	 ventilation	and	dilution	 in	confined	 spaces.	The	
    illustrations 	shown	in	this 	section 	of	the 	manual 	are	a	reference 	
    for 	the 	openings 	that 	provide 	fresh 	air 	into 	confined 	spaces 	
    only.	 Do	not	 refer	 to	these	 illustrations	 for	the	 purpose	 of	vent 	
    installation.	 See	Venting	 Installation	 on	page	 18	for	 complete 	
    venting 	installation 	instructions.
    outdoor  aIr throuGh two openInGs
    fIGure 8.
    The	confined	 space	shall	be	provided	 with	two	permanent 	
    openings,	 one	commencing	 within	12	inches	 (300	mm)	of	the	 top	
    and	 one	commencing	 within	12	inches	 (300	mm)	of	the	 bottom	 of	
    the	 enclosure.	 The	openings	 shall	communicate	 directly	with	the	
    outdoors.	See	Figure	8.
    Each	 opening	 shall	have	 a	minimum	 free	area	 of	1	square	 inch	per	
    4,000	 Btu/hr	 (550	mm2	 per	kW)	 of	the	 aggregate	 input	rating	 of	all	
    appliances 	installed	 in	the	 enclosure. 	Each	 opening	 shall	not	be	 less 	
    than	100	square	inches	(645	cm2). 	
    outdoor aIr throuGh one openInG
    fIGure 9.
    Alternatively	 a	single	 permanent	 opening,	commencing	 within	12 	
    inches	 (300	mm)	of	the	 top	of	the	 enclosure,	 shall	be	provided.	 See	
    Figure	 9.	The	 water	 heater	 shall	have	 clearances	 of	at	least	 1	inch	
    (25	 mm)	 from	 the	sides	 and	back	 and	6	inches	 (150	mm)	from	 the	
    front	 of	the	 appliance.	 The	opening	 shall	directly	 communicate	 with	
    the	 outdoors	 or	shall	 communicate	 through	a	vertical	 or	horizontal	 duct	
    to	 the	 outdoors	 or	spaces	 that	freely	 communicate	 with	the	outdoors	
    and	shall	have	a	minimum	free	area	of	the	following:
    1.  1	square	 inch	per	3000	 Btu/hr	 (733	mm
    2	per	 kW)	 of	the	 total	
    input	rating	of	all	appliances	located	in	the	enclosure,	and
    2.  Not	less	 than	 the	sum	 of	the	 areas	 of	all	 vent	 connectors	 in	
    the	space. 
    						
    							14
    outdoor aIr throuGh two horIzontal ducts
    fIGure 10.
    The	confined	 space	shall	be	provided	 with	two	permanent	 horizontal	
    ducts,	 one	commencing	 within	12	inches	 (300	mm)	of	the	 top	and	
    one	 commencing	 within	12	inches	 (300	mm)	of	the	 bottom	 of	the	
    enclosure.	 The	horizontal	 ducts	shall	communicate	 directly	with	the	
    outdoors.	See	Figure	10.
    Each	 duct	opening	 shall	have	 a	minimum	 free	area	 of	1	square	 inch	
    per	 2,000	 Btu/hr	 (1100	mm2	per	kW)	 of	the	 aggregate	 input	rating	 of	
    all	appliances	installed	in	the	enclosure.
    When	 ducts	are	used,	 they	shall	 be	of	the	 same	 cross	sectional	 area	
    as	 the	 free	 area	 of	the	 openings	 to	which	 they	connect.	 The	minimum	
    dimension	of	rectangular	air	ducts	shall	be	not	less	than	3	inches.	
    outdoor  aIr throuGh two vertIcal ducts
    The	illustrations 	shown	 in	this	 section	 of	the	 manual	 are	a	
    reference	 for	the	 openings	 that	provide	 fresh	air	into	 confined	
    spaces	only.
    do not	 refer	to	these	 illustrations	 for	the	 purpose	 of	vent	
    installation.	 See	Venting	 Installation	 on	page	 18	for	 complete	
    venting	installation	instructions.
    fIGure 11.
    The	 confined	 space	shall	be	provided	 with	two	permanent	 vertical	
    ducts,	 one	commencing	 within	12	inches	 (300	mm)	of	the	 top	and	
    one	 commencing	 within	12	inches	 (300	mm)	of	the	 bottom	 of	the	
    enclosure.	 The	vertical	 ducts	shall	communicate	 directly	with	the	
    outdoors.	See	Figure	11.
    Each	 duct	opening	 shall	have	 a	minimum	 free	area	 of	1	square	 inch	
    per	 4,000	 Btu/hr	 (550	mm2	 per	kW)	 of	the	 aggregate	 input	rating	 of	
    all	appliances	installed	in	the	enclosure.	
    When	 ducts	are	used,	 they	shall	 be	of	the	 same	 cross	sectional	 area	
    as	 the	 free	 area	 of	the	 openings	 to	which	 they	connect.	 The	minimum	
    dimension	of	rectangular	air	ducts	shall	be	not	less	than	3	inches.
    aIr froM other Indoor spaces
    fIGure 12.
    The	 confined	 space	shall	be	provided	 with	two	permanent	 openings,	
    one	 commencing	 within	12	inches	 (300	mm)	of	the	 top	and	 one	
    commencing 	within 	12 	inches	 (300	mm)	 of	the 	bottom	 of	the 	enclosure. 	
    See	Figure	12.
    Each	 opening	 shall	communicate	 directly	with	an	additional	 room(s)	
    of	 sufficient	 volume	so	that	 the	combined	 volume	of	all	 spaces	 meets	
    the	criteria	for	an	Unconfined	Space.
    Each	 opening	 shall	have	 a	minimum	 free	area	 of	1	square	 inch	per	
    1,000	 Btu/hr	 (2200	mm2	per	kW)	 of	the	 aggregate	 input	rating	 of	all	
    appliances	 installed	in	the	 enclosure.	 Each	opening	 shall	not	be	less	
    than	100	square	inches	(645	cm2).	
    ventInG 
    						
    							15
    If	the	 water	 heater	 is	being	 installed	 as	a	replacement	 for	an	existing	
    heater	 in	pre-existing	 venting,	a	thorough	 inspection	 of	existing	 venting	
    system	must	be	performed	prior	to	any	installation	work.
    VENT 	DAMPERS	 -	Any	 vent	 damper,	 whether	it	is	 operated	 thermally	
    or	 otherwise	 must	be	removed	 if	its	 use	 inhibits	 proper	drafting	 of	the	
    water	heater.
    Thermally	 Operated	Vent	Dampers:	 this	gas-fired	 water	heater	 has	
    a	 thermal	 efficiency	 at	or	 above	 80%	which	 may	produce	 a	relatively 	
    low	 flue	 gas	temperature.	 Such	temperatures	 may	not	be	high	 enough 	
    to	 properly	 open	thermally	 operated	vent	dampers.		 This	would	 cause	
    spillage	 of	the	 flue	 gases	 and	may	 cause	 carbon	 monoxide 	poisoning. 	
    Vent	 dampers	 must	bear	evidence	 of	certification	 as	complying	 with	
    the	 current	 edition	of	the	 American	 National	Standard	 ANSI	Z21.66 	
    CGA 	6.14	 (covering	 electrically	 and	mechanically	 actuated	vent	
    dampers).	 Before	installation	 of	any	 vent	 damper,	 consult	the	local 	
    gas	utility	for	further	information.
    To	 insure	 proper	 venting	 of	this	 gas-fired	 water	heater,	 the	correct 	
    vent	 pipe	 diameter	 must	be	utilized.		 Any	additions	 or	deletions	 of	
    other	 gas	appliances	 on	a	common	 vent	with	this	water	 heater	 may	
    adversely	 affect	the	operation	 of	the	 water	 heater.	 Consult	 your	gas	
    supplier	if	any	such	changes	are	planned.
    For	 proper	 venting	 in	certain	 installations,	 a	larger	 diameter	 vent	
    pipe	 may	be	necessary.	 Consult	your	gas	supplier	 to	aid	 you	 in	
    determining	 the	proper	 venting	 for	your	 water	 heater	 from	the	vent 	
    tables	 in	the	 current	 edition	of	the	 National	 Fuel	Gas	Code	 ANSI	
    Z223.1/NFPA 	54	 or	the	 Natural	 Gas	and	Propane	 Installation	 Code	
    cAN\cSA B 149.1. 
    Periodically 	check	 the	venting	 system	for	signs	 of	obstruction	 or	
    deterioration	and	replace	if	needed.
    The	combustion	and	ventilation	air	flow	must	not	be	obstructed.
    The	 water	 heater	 with	draft	 hood	 installed	 must	be	connected	 to	a	
    chimney	 or	listed	 vent	pipe	system,	 which	terminates	 to	the	 outdoors.		
    Never	 operate	 the	water	 heater	 unless	 it	is	 vented	 to	the	 outdoors	
    and	 has	adequate	 air	supply	 to	avoid	 risks	of	improper	 operation,	
    explosion	or	asphyxiation.
    •	 For	 proper	draft	hood	 attachment,	 the	draft	 hood	 legs	may	 be	
    angled	slightly	inward.
    •	 Place	 the	draft	 hood	 legs	in	the	 receiving	 holes	on	the	 top	of	the	
    water	 heater.	 The	legs	 will	snap	 in	the	 holes	 to	give	 a	tight	 fit.	
    Secure	draft	hood	with	the	supplied	brackets.
    •	 Place	 the	vent	 pipe	 over	 the	draft	 hood.	 With	the	vent	 pipe	 in	position, 	
    drill	 a	small	 hole	through	 both	the	vent	 pipe	and	draft	 hood.	 Secure 	
    them	together	with	a	sheet	metal	screw. 	See	Figure	13.
    Obstructed	 or	deteriorated	 vent	systems	 may	present	 serious	health	
    risk	or	asphyxiation.
    fIGure 13.
    The	 vent	 pipe	 from	 the	water	 heater	 must	be	no	less	 than	 the	
    diameter	 of	the	 draft	 hood	 outlet	 on	the	 water	 heater	 and	must 	
    slope	 upward	 at	least	 1/4	inch	 per	linear	 foot	(21	mm	 per	meter). 	
    See	Figure	14.
    All	 vent	 gases	 must	be	completely	 vented	to	the	 outdoors	 of	the 	
    structure	 (dwelling).	 	 Install	only	the	draft	 hood	 provided	 with	the	
    new	water	heater	and	no	other	draft	hood.
    Vent	pipes	must	be	secured	at	each	joint	with	sheet	metal	screws.
    fIGure 14.  
    There	 must	be	a	minimum	 of	6”	 (153	 mm)	clearance	 between	single	
    wall	 vent	 pipe	and	any	combustible	 material.	 	Fill	and	 seal	 any	
    clearance	 between	single	wall	vent	 pipe	 and	combustible	 material	
    with	 mortar	 mix,	cement,	 or	other	 noncombustible	 substance.	For	
    other	 than	single	 wall,	follow	 vent	pipe	 manufacturer’s	 clearance	
    specifications.		 To	insure	 a	tight	 fit	of	 the	 vent	 pipe	in	a	brick	 chimney, 	
    seal	around	the	vent	pipe	with	mortar	mix	cement.
    Failure	 to	have	 required	 clearances	 between	vent	piping	 and	
    combustible	material	will	result	in	a	fire	hazard.
    Be	 sure	 vent	pipe	 is	properly	 connected	 to	prevent	 escape	of	
    dangerous	flue	gases	which	could	cause	deadly	asphyxiation.
    Chemical	 vapor	corrosion	 of	the	 flue	 and	vent	 system	 may	occur 	
    if 	air	 for	 combustion	 contains	certain	 chemical	 vapors.	Spray	 can	
    propellants,	 cleaning	solvents,	 refrigerator	 and	air	conditioner 	
    refrigerants, 	swimming 	pool 	chemicals, 	calcium 	and 	sodium 	
    chloride, 	waxes, 	bleach 	and 	process 	chemicals 	are 	typical 	
    compounds	which	are	potentially	corrosive. 
    						
    							16
    Gas pIpInG
    Contact	your	 local	 gas	service	 company	 to	ensure	 that	adequate 	
    gas	 service	 is	available	 and	to	review	 applicable	 installation	 codes	
    for	your	area.
    Size	 the	main	 gas	line	in	accordance	 with	Table	 3.	The	 figures	 shown	
    are	 for	straight	 lengths	of	pipe	 at	0.5	 in.	W.C.	 pressure	 drop,	which	 is	
    considered	 normal	for	low	 pressure	 systems.	 Note:	Fittings	 such	as	
    elbows,	 tees	and	line	regulators	 will	add	 to	the	 pipe	 pressure	 drop.	
    Also	 refer	 to	the	 current 	editions	 of	the	 National	 Fuel	Gas	Code	 (NFPA 	
    54)	 or	Natural	 Gas	and	Propane	 Installation	 Code	(CAN/CSA 	B149.1).
    Make	 sure	gas	supplied	 is	same	 type	listed	 on	model	 rating	plate.	The	
    inlet	 gas	pressure	 must	not	exceed	 14	inch	 water	 column	 (2.6	kPa)	
    for	 natural	 and	propane	 (L.P.)	gas.	The	minimum	 inlet	gas	pressure	
    shown	on	rating	plate	is	that	which	will	permit	firing	at	rated	input.
    If	 the	 gas	 control	 valve	is	subjected	 to	pressures	 exceeding	 1/2	pound 	
    per	 square	 inch	(3.5	kPa),	 the	damage	 to	the	 gas	 control	 valve	could	
    result	in	a	fire	or	explosion	from	leaking	gas.
    If	 the	 main	 gas	line	shut-off	 serving	all	gas	 appliances	 is	used,	 also	
    turn	 “off”	 the	gas	 at	each	 appliance.	 Leave	all	gas	 appliances	 shut	
    “off”	until	the	water	heater	installation	is	complete.
    A 	gas	 line	of	sufficient	 size	must	 be	run	 to	the	 water	 heater.	 Consult	
    the	 current	 edition	of	 National	 Fuel	Gas	Code	 ANSI	Z223.1/NFPA 	54	
    or	 the	 Natural	 Gas	and	Propane	 Installation	 Code	CAN/CSA 	B149.1	
    and	your	gas	supplier	concerning	pipe	size.
    There	must	be:
    •	 A 	readily	 accessible	 manual	shut	off	valve	 in	the	 gas	 supply	 line	
    serving	the	water	heater,	and
    •	 A 	sediment	 trap	ahead	 of	the	 gas	 control	 valve	to	help	 prevent	 dirt	
    and	foreign	materials	from	entering	the	gas	control	valve.
    •	 A 	flexible	 gas	connector	 or	a	ground	 joint	union	 between	 the	shut 	
    off	valve	and	control	valve	to	permit	servicing	of	the	unit.
    Be	 sure	 to	check	 all	the	 gas	 piping	 for	leaks	 before	 lighting	 the	water	
    heater.	 Use	a	soapy	 water	solution,	 not	a	match	 or	open	 flame.	 Rinse	
    off	soapy	solution	and	wipe	dry.
    The	 minimum	 inlet	gas	pressure	 shown	on	the	 rating	 plate	is	that	
    which	will	permit	firing	at	the	rated	input.
    table 3.  Gas suppl Y lIne sIzes (In Inches)* 
    MaxIMuM capacItY of pIpe In cubIc feet per hour
    lenGth In  
    feetnoMInal  Iron pIpe sIzes (Inches) 
    Input In thousands (btu/hr)
    1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
    10 175360 6801400 21003960 630011000 23000
    20 120250 4659501460 2750 4360770015800
    30 97200 3757701180 2200 3520625012800
    40 82170 320660 9901900 3000530010900
    50 73151 285580 9001680 265047509700
    60 66138 260530 8101520 240043008800
    70 61125 240490 7501400 225039008100
    80 5711 8 220460 6901300 205037007500
    90 5311 0 205430 6501220 195034507200
    100 50103 195400 6201150 185032506700
    125 4493175 360 5501020 165029506000
    150 4084160 325 500950 1500 26505500
    175 3777145 300 460850 1370 24505000
    200 3572135 280 430800 1280 22804600
    table 4.
    lenGth In 
    Meters
    noMInal  Iron pIpe sIzes (Inches) 
    Input In Kw
    1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
    3 51105 199410 6151160 184532216735
    6 3573142 278 428805 1277 22554626
    9 285911 0 225 346644 1031 18303748
    12 2450 94193 290556 8781552 3192
    15 2144 83170 264492 7761391 2840
    18 1940 76155 237445 7031259 2577
    21 1837 70143 220410 6591142 2372
    24 1735 64135 202381 6001083 2196
    27 1632 60126 190357 5711010 2108
    31 1530 5711 7 182337 5429521962
    38 1327 51105 161299 4838641757
    46 1225 4795146 278 4397761610
    53 1123 4288135 249 4017171464
    61 1021 4082126 234 3756881347
    Use	pipe	 joint	compound	 or	teflon	 tape	marked	 as	being	 resistant	 to	
    the	action	of	petroleum	[Propane	(L.P.)]	gases.	
    The	 water	 heater	 and	its	gas	 connection	 must	be	leak	 tested	 before	
    placing	the	water	heater	in	operation.
    The	 water	 heater	 and	its	individual	 shut-off	valve	shall	be	
    disconnected	 from	the	 gas	supply 	piping	 system 	during	 any	pressure 	
    testing	 of	that	 system	 at	test	 pressures	 in	excess	 of	1/2	 pound	 per	
    square	 inch	(3.5	kPa).	 It	shall	 be	isolated	 from	the	gas	 supply	 piping	
    system	 by	closing 	its	 individual	 manual	shut-off	 valve	during	 any	
    pressure	 testing	of	the	 gas	 supply	 piping	system	 at	test	 pressures	
    equal	 to	or	 less	 than	 1/2	pound	 per	square	 inch	(3.5	kPa).
    Connecting	 the	gas	 piping	 to	the	 gas	 control	 valve	of	the	 water	 heater	
    can	 be	accomplished	 by	either	 of	the	 two	 methods	 shown	in	Figures	
    15 and 16.
    fIGure 15.  Gas pIpInG wIth flexIble connector.
    fIGure 16.  Gas pIpInG wIth  all
    blacK Iron pIpe to Gas control. 
    						
    							17
    sedIMent traps
    A	sediment	 trap	shall	 be	installed	 as	close 	to	 the 	inlet	 of	the 	water 	
    heater	 as	practical	 at	the	 time	 of	water	 heater	 installation.	 The	
    sediment	 trap	shall	 be	either	 a	tee	 fitting	 with	a	capped	 nipple	
    in	 the	 bottom	 outlet	or	other	 device	 recognized	 as	an	 effective 	
    sediment 	trap. 	If 	a	 tee	 fitting	 	 is	used, 	it 	shall	 be	installed	 in	
    conformance	 with	one	of	the	 methods	 of	installation	 shown	in	
    the	Figures	15	and	16.
    Contaminants	 in	the	 gas	 lines	 may	cause	 improper	 operation	 of	
    t h e 	g a s 	c o nt r o l 	va l ve 	t h at 	m ay 	r e su l t 	i n 	f i r e 	o r 	ex p l o s i o n. 		B ef o r e 	
    attaching	 the	gas	 line	be	sure	 that	all	gas	 pipe	 is	clean	 on	the	
    i n s i d e . 		To	t r a p 	a ny	d i r t	o r	f o r e i g n 	m a t e r i a l 	i n	t h e 	g a s 	s u p p l y 	l i n e ,	
    a	 sediment	 trap	must	 be	incorporated	 in	the	 piping.		 The	sediment 	
    trap 	must 	be 	readily 	accessible. 	Install 	in 	accordance 	with 	the 	
    “Gas	 Piping”	 section.	 Refer	to	the	 current	 edition	of	the	 National 	
    Fuel	 Gas	Code,	 ANSI	Z223.1/NFPA	 54	or	the	 Natural	 Gas	and	
    Propane	Installation	Code	CAN/CSA	B149.1. 
    						
    							19
    for Your safetY read before lIGhtInG
    before lIGhtInG: entIre sYsteM Must be fIlled wIth water and aIr purGed  at faucets.
    warnInG: If you do not follow these instructions exactly, a fire or 
    explosion may result causing property damage, personal injury or loss of\
     life.
    1.													STOP!		Read		the		safety	information	above	on	 	
    	 		this	label.
    2.	 Set	 the	thermostat	 to	the	 lowest	 setting	 by	turning 	
    thermostat	dial	fully	clockwise	
     until it stops.
    3.	 Push	 the	gas	 control	 knob	down	 slightly	 and	turn	
    clockwise	
    	to	“OFF”	(Figure	 A).
    	 NOTE:	 Gas	control	 knob	CANNOT 	be	 turned	 from	“PILOT”  
    	 to	“OFF”	unless	it	is	pushed	down	slightly.	Do	not	force.
    4.	 Remove	 the	inner	 and	outer	 doors	 located	 below	and	
     
    behind	the	gas	control	unit.
    5.	 Wait	 five	(5)	minutes	 to	clear	 out	any	 gas.	 If	you	 then	
     
    smell	 gas													 STOP!		Follow	“B”	in	the	 safety	 information  
    above 	on												 this	label.		 If	you	 do	not	 smell		 gas,	go	
    to	the	next	step.
    6.	 Find	 Pilot.	Follow	 metal	tube	from	 the	bottom	 ,	right	 of	
    the	gas	control	to	the	pilot	burner.	(Figure	D).
    7.	 Turn	 gas	control	 knob	counterclockwise	
    	to	 “PILOT”	
    (Figure	B).
    8.		 Push	 gas	control	 knob	down	 all	the	 way	 and	hold	 it	down.  
    	 	 	 	 	 Immediately	 light	the	pilot	 with	a	match.	 Continue	 to	
    hold 		the	 gas	 control	 knob	down	 for	about	 one	(1)	minute	 	
    after	 the	pilot	 is	lit.	 Release	 the	gas	 control	 knob	and	it	will	
    pop	 back	 up.	Pilot	 should	 remain	 lit.	If	it	goes	 out,	repeat	
    Steps	 3	through	 8.	It	may	 take	 several	 minutes	 for	air	to	
    clear	the	lines,	before	the	pilot	will	light.
    		•	 If	 knob	 does	not	pop	 up	when	 released,	 stop	and		
    	 	 	 immediately	call	your	service	technician	or	gas		 	
        supplier. 
    		•	 If	the	pilot	 will	not	 stay	 lit	after	 several	 tries,	turn	the 
    	 	 	 gas	control	knob	to	“OFF”	(Figure	 A)	and	call	your		
    	 	 	 service	technician	or	gas	supplier.	
    		9.	 Replace	inner	and	outer	burner	doors.
    10.	 At	arm’s	length	away,	turn	the	gas	control		knob		 	
    	 counterclockwise	
    	to	“ON”	(Figure	C).
    11.	 Set	thermostat	to	desired	setting	(See	Figure).
       cautIon: hotter water increases the risk of    
      scald injury. consult the instruction manual    
      before changing temperature.
    lIGhtInG InstructIons
    to turn off Gas to  applIance
    1.	 Set	the	thermostat	to	lowest	setting.
    2.	 Push	gas	control	 knob	down	 slightly	 and	turn	clockwise
      
    to	“OFF”.		Do	not	force,	see	Figure	 A.
    top vIew
    fIGure “d”
    Gas control
    A.	 This	 appliance	 has	a	pilot	 which	 must	be	lighted	 by	hand. 		
    When	 lighting	 the	pilot,	 follow	 these	instructions	 exactly.
    B.  before lIGhtInG:		 smell	all	around	 the	appliance	
    area	 for	gas.		 Be	sure	 to	smell	 next	to	the	 floor	 because 	
    some	 gas	is	heavier	 than	air	and	 will	settle	 on	the	 floor.
      what to do If You sMell  Gas
      •	 Do	not	try	to	light	any	appliance.
    	 •	 Do	not	touch	any	electric	switch;	do	not	use		 	 	 any	phone	in	your	building.
    	 •	 Immediately	call	your	gas	supplier	from	a		 	 	 neighbor’s	phone.		Follow	the	gas	supplier’s		 	
    	 instructions.  
    •	 If	you	cannot	reach	your	gas	supplier,	call	the		 	
    	 fire	department.
    C.	 Use	 only	your	 hand	 to	push	 down	 or		turn	 the	gas	 control 	
    knob.		 Never	 use	tools.		 If	the	 knob	 will	not	 push	 down	 or	
    turn	 by	hand,	 don’t	try	to	repair	 it,	call	 a	qualified	 service	
    technician.		 Force	or	attempted	 repair	may	result	 in	a	fire 	
    or explosion.
    D.	 Do	 not	use	 this	appliance	 if	any	 part	 has	been	 under	
    water.	 Immediately	 contact	a	qualified	 installer	or	service 	
    agency	 to	replace	 a	flooded	 water	heater.	 Do	not	 attempt 	
    to	repair	the	unit!	It	must	be	replaced! 
    						
    							20
    start up condItIons
    draft hood operatIon
    Check	draft	hood	 operation	 by	performing	 a	worst	 case	
    depressurization	 of	the	 building.	 With	all	doors	 and	windows 	
    closed, 	and 	with 	all 	air 	handling 	equipment 	and 	exhaust 	fans 	
    operating	 such	as	furnaces,	 clothes	dryers,	range	hoods	 and	
    bathroom	 fans,	a	match	 flame	should	 still	be	drawn	 into	the	draft 	
    hood 	of 	the 	water 	heater 	with 	its 	burner 	firing. 		If	the 	flame 	is 	not 	
    drawn	 toward	 the	draft	 hood,	 shut	off	water	 heater	 and	make 	
    necessary	air	supply	changes	to	correct.
    condensat Ion
    Whenever	 the	water	 heater	 is	filled	 with	cold	 water,	 some	
    condensate	 will	form	 while	 the	burner	 is	on.		 A	water	 heater	 may	
    Short	 repeated	 heating	cycles	caused	 by	small	 hot	water	 uses	can	
    cause	 temperatures	 at	the	 point	 of	use	 to	exceed	 the	thermostat 	
    setting	 by	up	 to	30°F	 (16.7°C).	 If	you	 experience	 this	type	 of	use 	
    you	 should 	consider	 using	lower	temperature 	settings	 to	reduce 	
    scald	hazards. 	
    Any 	water 	heater’s 	intended 	purpose 	is 	to 	heat 	water. 		Hot 	water 	
    is 	needed 	for 	cleansing, 	cleaning, 	and 	sanitizing 	(bodies, 	dishes, 	
    clothing). 	Untempered	 hot	water	 can	present 	a	 scald	 hazard. 		
    Depending	 on	the	 time	 element,	 and	the	people	 involved	 (adults,	
    children, 	elderly,	 infirm,	etc.)	scalding	 may	occur	 at	different 	
    temperatures.
    HOTTER 	WATER 	CAN 	SCALD:	 Water	heaters	 are	intended 	to	 produce 	
    hot	 water.	 	 Water	heated	 to	a	temperature	 which	will	satisfy	 space	
    heating,	 clothes	washing,	 dish	washing,	 and	other	 sanitizing	 needs	
    can	 scald	 and	permanently	 injure	you	upon	 contact.	 	 Some	people	
    are	 more	 likely	to	be	 permanently	 injured	by	hot	 water	 than	others.		
    These	 include	 the	elderly,	 children,	 the	infirm,	 or	physically/mentally	
    handicapped.		 If	anyone	 using	hot	water	 in	your	 home	 fits	into	 one	 of	
    these	 groups	 or	if	there	 is	a	local	 code	 or	state	 law	requiring	 a	certain	
    temperature	 water	at	the	 hot	water	 tap,	then	 you	must	 take	special	
    precautions.	 In	addition	 to	using	 the	lowest	 possible	 temperature 	
    setting	 that	satisfies	 your	hot	water	 needs,	 a	means	 such	as	a	mixing	
    valve	 should	 be	used	 at	the	 hot	water	 taps	used	 by	these	 people	 or	
    at	 the	 water	 heater.	 Mixing	valves	are	available	 at	plumbing	 supply	or	
    hardware	 stores,	see	Figure	 2.		Follow	 manufacturer’s	 instructions	for	
    installation	 of	the	 valves.	 Before	changing	 the	factory	 setting	on	the	
    thermostat,	 read	the	“Temperature	 Regulation”	section	in	this	 manual, 	
    see	Figures	17	and	18.
    teMperature reGulatIon
    for Your InforMatIon
    appear 	to 	be 	leak ing 	when 	in 	fac t 	the 	water 	is 	c ondensation. 	This 	
    usually 	happens 	when:
    a.		A	new	water	heater	is	filled	with	cold	water	for	the	first	time.
    b . 		B u r n i n g 	g a s 	p r o d u c e s 	w a t e r 	v a p o r 	i n 	w a t e r 	h e a t e r s , 	p a r t i c u l a r l y 	
    high	efficiency	models	where	flue	temperatures	are	lower.
    c.		Large	 amounts	of	hot	 water	 are	used	 in	a	short	 time	and	the	
    refill	water	in	the	tank	is	very	cold.
    Moisture	 from	the	products	 of	combustion	 condense	on	the	 cooler 	
    tank	 surfaces	 and	form	 drops	 of	water	 which	 may	fall	onto	 the	
    burner	 or	other	 hot	surfaces	 to	produce	 a	“sizzling”	 or	“frying”	 noise.
    Excessive	 condensation	 can	cause	 pilot	outage	 due	to	water 	
    running	 down	the	flue	 tube	 onto	the	main	 burner	 and	putting	 out	
    the	pilot.
    Never	 allow	small	 children	 to	use	 a	hot	 water	 tap,	or	to	draw	 their	own	
    bath	 water.	 Never	leave	a	child	 or	handicapped	 person	unattended	
    in	a	bathtub	or	shower.		
    NOTE:	 	 A	water	 temperature	 range	of	120°F-140°F	 (49°C-60°C)	is	
    recommended	by	most	dishwasher	manufacturers.
    The	 thermostat	 of	this	 water	 heater	 has	been	 factory	 set	at	its	 lowest	
    position	 (PIlOT lIGHTING).	 It	is	 adjustable	 and	must	 be	reset	 to	
    the 	desired 	temperature 	setting	 to	reduce	 the	risk	 of	scald 	injury. 		
    The	 mark	 (
    	)	 indicative	 of	approximately	 120°F	(49°C)	 is	preferred	
    starting	point.		Some	States	have	a	requirement	for	a	lower	setting.	
    Turn	 the	water	 temperature	 dial	clockwise	 (	
    	)	 to	 decrease	 the	
    temperature,	 or	counterclockwise	 (			)	 to	 increase	 the	temperature.
    Should	 overheating	 occur	or	the	 gas	 supply	 fail	to	shut	 off,	turn	 off	the	
    manual	gas	control	valve	to	the	water	heater.
    fIGure 17.
    Water 
    Temperature	°F 	
    Time	for	
    1st	Degree	Burn
    (Less	Severe	Burns) Time	for	Permanent	Burns
    2nd	&	3rd	Degree
    (Most	Severe	Burns)
    11 0
    (normal	shower	temp.)
    11 6 (pain	threshold)
    11 6 35	minutes 45	minutes
    122 1	minute 5	minutes
    131 5	seconds 25	seconds
    140 2	seconds 5	seconds
    149 1	second 2	seconds
    154 instantaneous 1	second
    (U.S.	Government	Memorandum,	C.P.S.C.,	Peter	L.	 Armstrong,	Sept.	15,1978)
    fIGure 18. 
    						