Home > American Water Heater > Water Heater > American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual

American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							11  Page
    Installation
    Installation Manual
    -Exhaust vent (ABS, PVC, CPVC, or polypropylene vent)-
    The Indoor model can be vented with ABS, PVC, CPVC, or polypropylene (temperature rated up to at 
    least 149 °F)  Vent material certified to ULC S636 standards is recommended in the USA  In Canada, 
    plastic venting must be certified to ULC S636 standards
    ItemMaterialUnited States Canada
    Exhaust pipe and Fittings Schedule 40 PVC
    ANSI/ASTM D1785
       ULC S636 Certified
          Materials Only
    PVC-DWV
    ANSI/ASTM D2665
    Schedule 40 CPVC ANSI/ASTM F441
    Schedule 40 ABS-DWV ANSI/ASTM D2661
    Polypropylene UL-1738
    Pipe Cement/Primer PVC
    ANSI/ASTM D2564
    CPVC ANSI/ASTM F493
    ABS ANSI/ASTM D2235
    Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
    (polyphenylsulfone) in non-metallic venting systems is prohibited
    Covering non-metallic vent pipe and fittings with thermal insulation is prohibited
    •	The maximum length of exhaust vent piping must not exceed 70 ft (213 m) for 3” venting, which 
    depends on the elevation where the water heater is installed, and 100 ft (305 m) for 4” venting 
    (deducting 5 ft (15 m) for each elbow used in the venting system)  Do not use more than 5 
    elbows  See the table below 
    •	When the horizontal vent run exceeds 5 ft (15 m), support the vent run at 3 ft (09 m) intervals 
    with overhead hangers
    *For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.
    For details on the vent connection, refer to p 13 to 16
    No. of 
    Elbow
    2" venting3" venting4" venting
    0 to 3,000 ft0 to 3,000 ft3,001 to 6,000 ft6,001 to 10,100 ft 0 to 10,100 ft
    065 ft (20 m)70 ft (213 m)40 ft (122 m)25 ft (76 m)100 ft (305 m)
    115 ft (05 m)65 ft (198 m)35 ft (107 m)20 ft (61 m)95 ft (290 m)
    2N/A60 ft (183 m)30 ft (91 m)15 ft (46 m)90 ft (274 m)
    3N/A55 ft (168 m)25 ft (76 m)10 ft (30 m)85 ft (259 m)
    4N/A50 ft (152 m)20 ft (61 m)N/A80 ft (244 m)
    5N/A45 ft (137 m)N/AN/A75 ft (229 m)
    Excludes vent terminators, one termination elbow, or rain caps 
    Max. Vertical or Horizontal (Total) Vent Lengh
    General rules for vent terminations:
    •	Avoid locating the water heater vent termination near any air intake devices  These fans can 
    pick up the exhaust flue products from the water heater and return them to the building  This 
    can create a health hazard
    •	Locate the vent termination so that it cannot be blocked by any debris, at any time  Most codes 
    require that the termination be at least 12 inches (305 mm) above grade, but the installer may 
    determine if it should be higher depending on the job site condition and applicable codes
    •	A proper sidewall termination is recommended when the water heater is vented through a 
    sidewall
    •	Regarding the clearances from the exhaust termination to the air inlet or opening, refer to p 17 
    to 19  
    						
    							12  Page
    Installation
    Installation Manual
    -DIPswitch settings for Vent length-
    Vent lengthTwo-pipe and Single pipe
    5 to 50 ft.
    (DEFAULT)No 6 : ON
    No 7 : OFF
    51 to 100 ft.No 6 : OFF
    No 7 : OFF
    OFF
    ON12 34 56 78910
    OFF
    ON1 2 34 56 78910
    Vent lengthTwo-pipe
    5 to 20 ft.
    (DEFAULT)No 6 : ON
    No 7 : OFF
    21 to 40 ft.No 6 : OFF
    No 7 : OFF
    41 to 70 ft.No 6 : ON
    No 7 : ON
    OFF
    ON1 2 34 56 78910
    OFF
    ON1 2 34 56 78910
    OFF
    ON1 2 34 56 78910
    Set DIPswitches shown in the tables below depending on the vent length  Only adjust switches with a black 
    square  Black squares indicate the position of the switch
    Vent lengthSingle pipe
    5 to 45 ft.
    (DEFAULT)No 6 : ON
    No 7 : OFF
    46 to 70 ft.No 6 : OFF
    No 7 : OFF
    OFF
    ON1 2 34 56 78910
    OFF
    ON1 2 34 56 78910
    Vent length Single pipe
    5 to 6.5 ft.No 6 : ON
    No 7 : ON
    OFF
    ON1 2 34 56 78910
    2 inch venting
    3 inch venting
    4 inch venting  
    						
    							13  Page
    Installation
    Installation Manual
    -Intake and Exhaust Venting Illustrations-
    Typical installations using ABS, PVC, CPVC, or polypropylene vent
    2 inch vent installation
    For details of the optional items, refer to the Installation manual for each optional item
    Single pipe with room-air intake
    Termination
    Hanger
    1.	 Connect	a	3"	 elbow	 directly	 on	the
        intake vent collar of the water heater 
    2.	 Connect	a	3"	 x	2"	 reducer	 directly	on
       the exhaust vent collar of the water
       heater 
       Make sure the couplings engage 
       the o-rings installed in the intake 
       and exhaust vent collars
    3.	 Connect	 a	2"	 straight	 pipe	to
          the reducer
    Vent connections for single pipe
    *The water heater came with a metal screen 
    that will fit into a 3 inch elbow 
    * 3" elbow with bird screen
    Intake vent collar(Female)
    3"x2" reducer
    2" straight pipe
    Exhaust vent collar (Female)
    Refer to pages 17 and 19 for clearance information  
    						
    							14  Page
    Installation
    Installation Manual
    3 inch vent installation
    1.	 Connect	a	3"	 elbow	 directly	 on	the
       intake vent collar of the water heater 
    2.	 Connect	a	3"	coupling directly on the
        exhaust vent collar of the water heater 
       Make sure the couplings engage 
       the o-rings installed in the intake 
       and exhaust vent collars
    3.	 Connect	 a	3"	 straight	 pipe	to
          the coupling
    Exhaust vent collar (Female)
    3" straight pipe
    3" coupling(included)
    Intake vent collar(Female)
    3" straight pipe
    1.	 Connect	 3"	couplings	 directly	on	
       the exhaust and intake vent collar 
       of the water heater 
       Make sure the couplings engage 
       the o-rings installed in the intake 
       and exhaust vent collars
    2.	 Connect	 3"	straight	 pipes	to	 the
       couplings
    For details of the optional items, refer to the Installation manual for each optional item
    Vent connections for two-pipeVent connections for single pipe
    3" coupling (included)
    3" straight pipe
    Exhaust vent collar (Female)
    * 3" elbow with bird screen
    Intake vent collar(Female)
    *The water heater came with a metal screen 
    that will fit into a 3 inch elbow 
    For details of the optional items, refer to the Installation manual for each optional item
    1.	 Connect	3"x4"	increasers 
       directly on the exhaust and intake
       vent collar of the water heater 
       Make sure the couplings engage 
       the o-rings installed in the intake 
       and exhaust vent collars
    2.	 Connect	 4"	straight	 pipes	to
          the increasers
    4" straight pipe
    3"x4" increaser
    Exhaust ventcollar(Female)
    Intake vent collar(Female)
    4" straight pipe
    3"x4" increaser
    4" straight pipe
    3"x4" increaser
    Exhaust vent collar (Female)
    * 3" elbow with bird screen
    Intake vent collar(Female)
    1.	 Connect	 a	3"	 elbow	 directly	 on	the
        intake vent collar of the water heater 
    2.	 Connect	a	3"x4"	increaser directly on
        the exhaust vent collar of the water
       heater 
       Make sure the couplings engage 
       the o-rings installed in the intake 
       and exhaust vent collars
    3.	 Connect	 a	4"	 straight	 pipe	to
          the increaser
    Vent connections for two-pipeVent connections for single pipe
    *The water heater came with a metal screen 
    that will fit into a 3 inch elbow 
    4 inch vent installation
    3" coupling(included)  
    						
    							15  Page
    Installation
    Installation Manual
    Two-pipe, direct-ventSingle pipe with room-air intake
    Terminations
    WallHanger
    Hanger
    Roof
    Roof flashing
    Fire stop
    Termination
    WallHanger
    Roof flashing
    Fire stop
    Roof
    Refer to pages 17 and 19 for clearance information
    Examples of installation of 3 inch & 4 inch vent  
    						
    							16  Page
    Installation
    Installation Manual
    Vent connections for two-pipe
    4" stainless steel vent straight pipe
    Exhaust vent collar (Female)Intake vent collar(Female)
    4" stainless steel vent straight pipe
    Exhaust vent collar (Female)
    4" stainless steel vent straight pipe
    Intake vent collar(Female)
    4" elbow with bird screen
    1.	 Connect	a	4"	 stainless	 steel	vent
          straight pipes directly on the
          exhaust vent collar of the
          water heater 
    2.	 Connect	a	4"	 elbow	 directly
          on the intake vent collar of the
          water heater 
    1.	 Connect	4"	stainless	 steel	vent
          straight pipes directly on the
          exhaust/intake vent collar of the
          water heater 
    For details of the optional items, refer to the Installation manual for each Optional item
    -Exhaust vent (Stainless steel vent)-
    This is a Category IV appliance and must be vented accordingly   The vent system must be sealed airtight  
    All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed 
    aluminum adhesive tape having a minimum temperature rating of 160 °F   For best results, a vent system 
    should be as short and straight as possible
    •	The Indoor model is a Category IV appliance and must be vented accordingly with any 4 inch vent 
    approved for use with Category III/IV or Special BH type gas vent
    •	The manufacturer recommends the NovaVent (Z-Vent) line  However, the following are also UL 
    listed manufacturers: ProTech Systems Inc (FasNSeal), Metal-Fab Inc, and Heat-Fab Inc (Saf-T 
    Vent)
    •	Follow the vent pipe manufacturer’s instructions when installing the vent pipe.
    •	The maximum length of exhaust vent piping must not exceed 100 ft (305 m) (deducting 5 ft (15 
    m) for each elbow used in the venting system)  Do not use more than 5 elbows
    •	When the horizontal vent run exceeds 5 ft (15 m), support the vent run at 3 ft (09 m) intervals 
    with overhead hangers
    DiameterMax. No. of ElbowsMax. Vertical and Horizontal (Total) Vent Length
    4 in (102 mm)5100 ft (305 m )
    *For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.
    No. of ElbowsMax. Vertical or Horizontal Vent Length
    0100 ft (305 m)
    195 ft (290 m)
    290 ft (274 m)
    385 ft (259 m)
    480 ft (244 m)
    575 ft (229 m)
    Excludes vent terminators, termination elbows, or rain caps 
    Vent connections for single pipe  
    						
    							17  Page
    Installation
    Installation Manual
    -Vent termination clearances-
    CanadaUS A
    Direct-vent and other 
    than Direct-vent
    Direct- 
    vent
    Other than  
    Direct-vent
    AClearance above grade, veranda, porch, deck, or 
    balcony1 foot1 foot1 foot
    B Clearance to window or door that may be opened3 feet1 foot 
    4 feet from below or 
    side opening 1 foot 
    from above opening
    CClearance to permanently closed window***
    D
    Vertical clearance to ventilated soffit located above 
    the vent terminator within a horizontal distance 
    of 2 feet (61cm) from the center line of the 
    terminator
    ***
    EClearance to unventilated soffit***
    FClearance to outside corner***
    GClearance to inside corner***
    HClearance to each side of center line extended 
    above meter/regulator assembly 3 feet**
    IClearance to service regulator vent outlet3 feet**
    J
    Clearance to non-mechanical air supply inlet to 
    building or the combustion air inlet to any other 
    application
    3 feet1 foot
    4 feet from below or 
    side opening 1 foot 
    from above opening
    KClearance to mechanical air supply inlet6 feet3 feet3 feet
    LClearance above paved sidewalk or paved driveway  
    located on public property7 feet*7 feet
    MClearance under veranda, porch deck, or balcony1 foot**
    *For clearances not specified in ANSI Z2231 / NFPA 54 (US) or B1491 (Canada), please use clearances in accor-
    dance with local installation codes and the requirements of the gas supplier 
    INSIDE CORNER DETAIL
    V
    Gas meter / regulator
    V
    V
    V
    V
    V
    V
    V
    V
    V
    X
    X
    X
    Vent terminal
    Air supply inlet
    Area where is not permittedG
    A
    E
    D
    B
    L
    C
    F
    B
    B
    B
    BA
    J
    OPERABLEFIXEDCLOSED
    B
    H
    M
    K
    OPERABLE
    FIXEDCLOSED
    I  
    						
    							18  Page
    Installation
    Installation Manual
    For multiple sidewall exhaust terminations, an exhaust 
    termination must be at least 1 ft (305mm) away from 
    another exhaust termination  An exhaust termination 
    must also be at least 2 ft (610 mm) away from an inside 
    corner (If the adjacent wall is less than 2 ft (610 mm) of 
    length, the minimum required distance away from the 
    inside corner will be equal to the length of that adjacent 
    wall)Exhaust terminationInsidecorner
     1 ft(305 mm) min
     2 ft(610 mm) min1 ft (305 mm)min
    For multiple, direct-vent sidewall terminations that 
    combine the intake and exhaust into a single penetration, 
    space each direct-vent termination at least 1 ft (305 mm) 
    away from each other, no matter the orientation  A direct-
    vent termination must also be at least 2 ft (610 mm) away 
    from an inside corner  (If the adjacent wall is less than 2 ft 
    (610 mm) of length, the minimum required distance away 
    from the inside corner will be equal to the length of that 
    adjacent wall)
    Combinedintake andexhausttermination
    Insidecorner
     1 ft (305 mm) min
     2 ft(610 mm)  min1 ft (305 mm)       min
    For direct-vent sidewall 
    terminations that use two 
    separate penetrations for 
    the intake and exhaust, 
    keep the termination 
    clearances shown in the 
    diagrams on the right 
    Exhaust
    Intake
    1 ft.
    (305 mm)
    min. Exhaust
    Intake
    A
    A
    Exhaust
    Intake
    1ft. (305 mm)min. Exhaust
    IntakeA
    
    A
    A: 0.5 ft. (159mm) 
    The clearance of A is recommended on the basis of the structure of the water heater
    * 3inch and 4 inch vent installations only   
    						
    							19  Page
    Installation
    Installation Manual
    
    Exhaust and/or direct-vent sidewall terminations should 
    be at least 2 ft (610 mm) away from an opposite surface/
    wall  Do not place the termination directly in front of an 
    opening into a building
    Intake airExhaust gas
    3  ft (914 mm) min.
    BA
    2 ft (610 mm) min.
    Intake air
    BB
    A
    Exhaust
    Gas
    A:Exhaust terminations must be at least 1 ft (305 mm) away from any obstructions
    B:Intake terminations must be at least 1 ft (305 mm) away from any obstructions
    Exhausttermination2 ft (610 mm)  min
    Please follow all local and national codes in regards to proper termination 
    clearances  In the absence of such codes, the clearances above can be used as 
    guidelines  Local codes supersede these guidelinesCAUTION  
    						
    							20  Page
    Installation
    Installation Manual
    GAS SUPPLY AND GAS PIPE SIZING
    -General-
    •	The minimum and maximum inlet gas pressures are:
    •	Inlet gas pressures that fall outside the range of values listed above may adversely affect the 
    performance of the water heater  These pressures are measured when the water heater is in full 
    operation
    •	Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range 
    will cause dangerous operating conditions and damage to the water heater 
    •	Until testing of the main gas line supply pressure is completed, ensure the gas line to the water heater 
    is disconnected to avoid any damage to the water heater
    -Gas connections-
    1 Install a manual gas shutoff valve between the water heater and the gas supply line  The gas supply 
    line shall be checked for leaks using code approved methods
    2 When the gas connections are completed, it is necessary to perform a gas leak test either by applying 
    soapy water to all gas fittings and observing for bubbles or by using a gas leak detection device
    •	The water heater and its individual shutoff valve must be disconnected from the gas supply 
    piping system during any pressure testing of that system at test pressures in excess of 1/2 psi 
    (35 kPa)
    •	The water heater must be isolated from the gas supply piping system by closing its individual 
    manual shutoff valve during any pressure testing of the gas supply piping system at test 
    pressures equal to or less than 1/2 psi (35 kPa)
    3 Always purge the gas line of any debris and/or water before connecting to the gas inlet
    Size the gas pipe appropriately to supply the necessary volume of gas required for 
    the water heater using ANSI Z2231/NFPA 54 in the USA or B1491 in Canada or 
    local codes  Otherwise, flow capabilities and output temperatures will be limited
    NOTICE
    Gas typeInlet gas pressure
    Natural GasMin 40” W C  (100 kPa) – Max 105” W C (261 kPa)
    PropaneMin 80” W C  (199 kPa)  – Max 140” W C (348 kPa)
    •	Check that the type of gas matches the rating plate first.
    •	Ensure that any and all gas regulators used are operating properly and 
    providing gas pressures within the specified range shown below.  Excess gas 
    inlet pressure may cause serious accidents.
    •	Conversion of this water heater from natural gas to propane or vice versa will 
    void all warranty   Contact your local distributor to get the correct unit for your 
    gas type  The manufacturer is not liable for any property and/or personal 
    damage resulting from gas conversions
    CAUTION  
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater Condensing UltraLow NOx Indoor 120000 BTU Liquid Propane GT140PIH User Manual