Home > American Water Heater > Gas Heater > American Water Heater Heavy Duty Commercial Gas BCG3 User Manual

American Water Heater Heavy Duty Commercial Gas BCG3 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater Heavy Duty Commercial Gas BCG3 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							51
    NOTES:
    1 .  Pref erred  piping  diagram.
    2 .  The t emperat ure and  pressure  relief valve  setting  shall not exceed  pressure  rating  of  any  component  in the  syst em.
    3 .  Servic e v alv es  are s hown f or serv icing  unit. However , local  codes  shall govern t heir usage.
    4 .  The  Tank  Temperat ure Cont rol should  be wired t o and  control the pump  between t he wat er heat er(s)  and the storage t ank(s).
    5 .  The  wat er heat er’s  operat ing thermost at  should  be set  5 degrees F higher t han the Tank  Temperat ure Cont rol.MUL TI-FL UE (3 UNITS) WITH HORIZON TAL ST ORAGE TANK
    LEGEND
    TEMPERA TURE & PRESSURE
    RELIEF V ALVEPRESSURE RELIEF V ALVECIRCULA TING PUMPTA NK  TE M PER AT URE CO NTR O LDRAIN
    FULL  POR T BALL  VALV
    E
    TEMPERA TURE GAGEW ATER FLOW SWITCH
    CHECK V
    ALVE
    W ARNING:  THIS DRA WING SHOWS SUGGESTEDPIPING CONFIGURA TION  AND OTHER DEVICES;
    CHECK WITH LOCAL  CODES AND ORDINANCES
    FOR  ADDITIONAL  REQUIREMENTS.
    HOT WATER
    RETURN
    ALTERNATE
    LOCATION
    HOT WATER TO FIXTURES
    AOS
    STORAGE TANK
    HEATER
    HEATER
    HEATER
    FINISHED FLOOR EXPANSION TANK
    COLD WATER
    SUPPLY
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN  
    						
    							52
    NOTES:
    1 .  Pref erred  piping  diagram.
    2 .  The t emperat ure and  pressure  relief valve  setting  shall not exceed  pressure  rating  of  any  component  in the  syst em.
    3 .  Servic e v alv es  are s hown f or serv icing  unit. However , local  codes  shall govern t heir usage.MUL TI FLUE F LUE (4 UNITS)
    LEGEND
    TEMPERA TURE & PRESSURE
    RELIEF V ALVEPRESSURE RELIEF V ALVECIRCULA TING PUMPTA NK  TE M PER AT URE CO NTR O LDRAIN
    FULL  POR T BALL  VALV
    E
    TEMPERA TURE GAGEW ATER FLOW SWITCH
    CHECK V
    ALVE
    W ARNING:  THIS DRA WING SHOWS SUGGESTEDPIPING CONFIGURA TION  AND OTHER DEVICES;
    CHECK WITH LOCAL  CODES AND ORDINANCES
    FOR  ADDITIONAL  REQUIREMENTS.
    EXPANSION
    TANKCOLD WATER
    SUPPLY
    HOT WATERTO FIXTURES
    FINISHED FLOOR
    HOT WATE
    R
    RETURN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN  
    						
    							53
    NOTES:
    1 .  Pref erred  piping  diagram.
    2 .  The t emperat ure and  pressure  relief valve  setting  shall not exceed  pressure  rating  of  any  component  in the  syst em.
    3 .  Servic e v alv es  are s hown f or serv icing  unit. However , local  codes  shall govern t heir usage.
    4 .  The  Tank  Temperat ure Cont rol should  be wired t o and  control the pump  between t he wat er heat er(s)  and the storage t ank(s).
    5 .  The  wat er heat er’s  operat ing thermost at  should  be set  5 degrees F higher t han the Tank  Temperat ure Cont rol.MUL TI-FL UE (4 UNITS) WITH VE RTICAL S TORA GE TANK
    LEGEND
    TEMPERA TURE & PRESSURE
    RELIEF V ALVEPRESSURE RELIEF V ALVECIRCULA TING PUMPTA NK  TE M PER AT URE CO NTR O LDRAIN
    FULL  POR T BALL  VALV
    E
    TEMPERA TURE GAGEW ATER FLOW SWITCH
    CHECK V
    ALVE
    W ARNING:  THIS DRA WING SHOWS SUGGESTEDPIPING CONFIGURA TION  AND OTHER DEVICES;
    CHECK WITH LOCAL  CODES AND ORDINANCES
    FOR  ADDITIONAL  REQUIREMENTS.
    HOT WATERTO FIXTURES
    HOT WATER
    RETURNCOLD WATER
    SUPPLY
    EXPANSION
    TANK
    ALT. COLD
    WATER
    CONNECTION
    AOS
    STORAGE TANK
    HEATER
    HEATER
    HEATER
    HEATER
    FINISHED FLOOR
    PIPE T&P TO
    OPEN DRAIN PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN  
    						
    							54
    NOTES:
    1 .  Pref erred  piping  diagram.
    2 .  The t emperat ure and  pressure  relief valve  setting  shall not exceed  pressure  rating  of  any  component  in the  syst em.
    3 .  Servic e v alv es  are s hown f or serv icing  unit. However , local  codes  shall govern t heir usage.
    4 .  The  Tank  Temperat ure Cont rol should  be wired t o and  control the pump  between t he wat er heat er(s)  and the storage t ank(s).
    5 .  The  wat er heat er’s  operat ing thermost at  should  be set  5 degrees F higher t han the Tank  Temperat ure Cont rol.MUL TI-FL UE (4 UNITS) WITH HORIZON TAL ST ORAGE TANK
    LEGEND
    TEMPERA TURE & PRESSURE
    RELIEF V ALVEPRESSURE RELIEF V ALVECIRCULA TING PUMPTA NK  TE M PER AT URE CO NTR O LDRAIN
    FULL  POR T BALL  VALV
    E
    TEMPERA TURE GAGEW ATER FLOW SWITCH
    CHECK V
    ALVE
    W ARNING:  THIS DRA WING SHOWS SUGGESTEDPIPING CONFIGURA TION  AND OTHER DEVICES;
    CHECK WITH LOCAL  CODES AND ORDINANCES
    FOR  ADDITIONAL  REQUIREMENTS.
    HOT WATER
    TO FIXTURES
    HOT WATER
    RETURN
    COLD WATER
    SUPPLY
    ALTERNATE
    LOCATION
    AOS
    STORAGE TANK
    HEATER
    HEATER
    HEATER
    HEATER
    FINISHED FLOOR EXPANSION TANK
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN
    PIPE T&P TO
    OPEN DRAIN  
    						
    							55
    MANIFOLD KITS
    TWO UNIT MANIFOLD KIT
    (9003426205)
    THREE UNIT MANIFOLD KIT
    (9003427205)
    FOUR UNIT MANIFOLD KIT (9003428205)
    MODEL DIMENSIONS "A" INCHES (CM)
    BCG370T120 69.75” (177cm)
    BCG380T15073.00” (185cm)
    BCG380T18067.50” (171cm)
    BCG3100T19975.00 (192cm)
    BCG380T19967.50” (171cm)
    (A)BCG3100T20072.00” (183cm)
    (A)BCG3100T25072.00” (183cm)
    (A)BCG365T25075.00” (191cm)
    (A)BCG3100T27572.00” (183cm)
    (A)BCG365T30075.00” (191cm)
    (A)BCG385T36079.50” (202cm)
    (A)BCG3100T39075.50” (192cm)  
    						
    							NOTES
    57 
    						
    							 EFFECTIVE
    For 3 Years, in the event of a tank leak, we will repair or, at our 
    discretion, replace the defective water heater.
    For 1 Year, in the event of part failure, we will repair or, at our 
    discretion, replace the defective part.
    We  warrant  this  product  against  defects  in  materials  or 
    workmanship  as  described  in  this  document  if  installed  within 
    the United States or Canada and provided the product remains 
    at its original place of installation.
    Warranty coverage begins the date of installation OR the date of 
    manufacture if installation cannot be verified.
     WHAT'S COVERED
    Subject  to  these  terms,  in  the  event  of  defect  in  materials  and/
    or  workmanship  resulting  in  a  tank leak  during  the first  three 
    years, we will:
    •  Replace the water heater should the tank leak.
    Subject to these terms, in the event of a defect in materials and/or 
    workmanship appearing during the first year, we will:
    •  Repair  or,  at  our  discretion,  replace  any  part  of  the  water 
    heater  covered  under  this  limited  warranty  excluding  parts 
    subject  to  normal  maintenance  (Example:  non-electronic 
    anode rod, filter, etc)
    Service/labor, shipping, delivery, installation, handling or any 
    other costs are not covered at any time under this warranty.
    Any  replacement  part  or  product  will  be  warranted  only  for 
    the  unexpired  portion  of  the  original  water  heater’s  limited 
    warranty period.
    If an identical model is no longer available due to a change in law, 
    regulation, or standard, we will replace the product with one having 
    comparable  capacity  and  input.  In  these  instances,  the  owner  will 
    have the option of paying the difference between what was paid for 
    the original model and the new model with the additional features, 
    or  receiving  a  refund  of  the  portion  of  the  purchase  price,  on  a 
    pro-rata basis allocable to the unexpired portion of the warranty.
     WHAT'S NOT COVERED
    •  Problems caused by improper: gas supply line sizing, gas type, 
    venting, connections, combustion air, voltage, wiring, or fusing   
    •   Failure to follow applicable codes   
    •   Failure to follow printed instructions   
    •   Abuse, misuse, accident, fire, flood, Acts of God   
    •   Improper installation,  sizing, delivery, or maintenance   
    •   Claims related to rust, noise, smell, or taste of water   
    •   Failure to conduct authorized factory start up if required   
    •   Alterations to the water heater   
    •   Non-outdoor heaters installed outdoors   
    •   Damages due to a failure to allow for thermal expansion   
    •  Heat exchanger failure due to lack of adequate / proper supply 
    of water   
    •   Heaters moved from their original location   
    •   Service trips to explain proper installation, use, or maintenance  of  the  product/unit  or  to  describe  compliance  requirements 
    under applicable codes and regulations   
    •    Charges  related  to  accessing  your  heater  including  but  not  limited to door/wall removal, equipment rental, etc.   
    •   Replacement parts after expiration of this warranty   
     LIMITATIONS
    NOTWITHSTANDING  ANYTHING  ELSE  TO  THE  CONTRARY, 
    THIS  IS  YOUR  SOLE  AND  EXCLUSIVE  WARRANTY.  
    ALL  OTHER  WARRANTIES  INCLUDING  A  WARRANTY 
    OF  MERCHANTABILITY  OR  FITNESS  FOR  PARTICULAR 
     
    PURPOSE  ARE  EXPRESSLY  DISCLAIMED.  SELLER  SHALL 
    NOT  BE  LIABLE  FOR  ANY  CONSEQUENTIAL,  INCIDENTAL, 
    SPECIAL, PUNITIVE OR OTHER INDIRECT DAMAGES.  TOTAL 
    LIABILITY  ARISING  AT  ANY  TIME  SHALL  NOT  EXCEED  THE 
    PURCHASE  PRICE  PAID  WHETHER  BASED  ON  CONTRACT, 
    TORT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY.
    SERVICE INQUIRIES:
    For service inquiries call the telephone number listed below.  Be prepared to provide the following information: 
    name, address, and telephone number; the model and serial number of the water heater; proof of installation; and a clear description 
    of the problem.  
    For your records, fill in the product:
    Serial: ___________________
    Model: ___________________
      U.S. Customers:
      American Water Heaters
      500 Princeton Road
      Johnson City, TN 37605
     800-999-9515
     www.americanwaterheaters.com
    COMMERCIAL
    WATER HEATER 
    LIMITED WARRANTY
    59 
    						
    							P.O. Box 1597, Johnson City, TN 37605
    Phone: 800-456-9805 • Fax: 800-999-5210 www.americanwaterheater.com
    Copyright © 2015 American Water Heater Company. All rights reserved.www. americanwaterheate r.co m
    American Wa ter Heater
    Johnson Cit y, TN 37605 
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater Heavy Duty Commercial Gas BCG3 User Manual