Home > Carrier > Air Conditioner > Carrier 42qg24-h Manual

Carrier 42qg24-h Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier 42qg24-h Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							 
     
    38
     
    CONNECTING ELECTRICAL WIRING (Cont.) 
     
    17-3 ELECTRICAL DATA 
    Input Power Main Power 
    Connections 
    Cooling Split 
    System 
    Model Starting 
    Current 
    (Note 1) System 
    Power 
    Supply 35 °C 
    * 46 °C 
    ** 52 °C 
    *** Heating 
    **** Circuit  
    Breaker  Wire 
    Size 
    (Note 2)
     
    Heat Pump Amp V/Ph/Hz Amp Watt Amp Watt Amp Watt Amp Watt Amp mm² 
    Standard mild ambient outdoor unit with rotary compressor 
    53QG18-H 52  9.5 1945 11.5 2425 - - 805 1745 20  4 
    53QG24-H 78 220/1/50 
    11.8 2435 13.9 2880 15.1 3130 11.8 2460  25  4 
    High ambient outdoor unit with rotary compressor 
    53QG18-H 44  8.6 1940 10.2 2270 11.1 2450  7.5  1660  20  4 
    53QG24-H 66 220/1/50 
    12.2 2635 14.2 3090 15.3 3340 11.3 2490  25  4 
    Cool Only Amp V/Ph/Hz Amp Watt Amp Watt Amp Watt Amp Watt Amp mm² 
    High ambient outdoor unit with rotary compressor 
    53QG18-C 44  8.5 1880 9.8 2160 10.5 2320  -  -  20  4 
    53QG24-C 66 220/1/50 
    12.5 2550 14.4 3015 15.5 3270  -  -  25  4  
    Notes: 
    1.  Starting Current duration is usually less than 1 Second. 
    2.  Wire size shown applies to standard applications with line length up to 15 meter and a subsequent 
    voltage drop not to exceed 3%. 
      
      For specific conditions and long lines, the resulting voltage drop must be checked and it may be 
    necessary to use the next larger size. 
     
      When sizing wires consider the amperage at peak conditions with the highest possible ambient 
    temperature expected for the installation area and lowest probable line voltage. 
     
    3. Operating Conditions. 
     
    *  Indoor 27/19 °C  DBT/WBT  Outdoor 35 °C DBT 
    High speed of indoor unit motor 
     
    **  Indoor 27/19 °C  DBT/WBT  Outdoor 46 °C DBT 
    High speed of indoor unit motor 
     
    ***  Indoor 27/19 °C  DBT/WBT  Outdoor  52 °C DBT 
      High speed of indoor unit motor 
     
    ****  Indoor 20 °C    DBT       Outdoor 7/6 °C DBT/WBT 
    High speed of indoor unit motor  
    						
    							 
     
    39
    LEGEND 
       Earth 
    L     Live power supply. 
    N     Neutral power supply. 
    R     Live connection indoor/outdoor unit. 
    C     Neutral connection indoor/outdoor unit. 
    Y   Compressor control. 
    O     Reversing valve control. 
    W2     Outdoor fan motor control. 
     S   Outdoor coil sensor. 
    LEGEND
     
       Earth 
    L     Live power supply. 
    N     Neutral power supply. 
    R     Live connection indoor/outdoor unit. 
    C     Neutral connection indoor/outdoor unit. 
    Y        Compressor control. 
     
    CONNECTING ELECTRICAL WIRING (Cont.)  
    17-4 CONNECTING ELECTRICAL WIRING FOR HEAT PUMP SYSTEM 
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    Sizes of electrical wires  
    R C Y O W2 S L N 
    1 mm2 1 mm2 1 mm2 1 mm2 1 mm2 1 mm2 4 mm2 4 mm2  
     
    17-5 CONNECTING ELECTRICAL WIRING FOR COOL ONLY SYSTEM 
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    Sizes of electrical wires  
    R C Y L N 
    1 mm2 1 mm2 1 mm2 4 mm2 4 mm2   
    Note:  (1) Connect the power supply to the outdoor unit and then get the power required 
         for the indoor unit from the outdoor unit. 
     
          (2) All dotted lines to be fitted by installer. 
               (3) Refer to wiring diagrams and stickers-caution sticked inside the outdoor & indoor units. 
     
    220-240V ~ 50Hz  
    Circuit  
    Breake
    r
    Main  
    Switch  
    220-240V ~ 50Hz
    Circuit  
    Breake
    r
    Main  
    Switch  
    Indoor 
    Unit  
    Outdoor
     
    Unit  
    Indoor
     
    Unit  
    Outdoor
     
    Unit  
    R C Y 
    RC Y 
    						
    							 
     
    40
    Piping
    Decorative Tape
    Saddles 
     
    18. FINISHING INSTALLATION  
    18-1  FINISHING STEPS FOR INSTALLATION   
     
    d. Insert grille frame to the top of the 
    indoor unit body.   
     
    a. Tie together refrigerant piping, drain 
      hose, electrical connection cords. 
    Form the refrigerant piping in the required 
    direction and bind the drain hose, electrical 
    connection cord and signal line together with 
    vinyl tape. 
    • The drain hose should be always at the bottom 
    of lump to assure smooth drainage.  
    • The lump must be of circular shape. 
     
     
     
     
     
     
     
     
     
     
    e. Push the triangle marks located at the 
    bottom of the grill frame.
     
     
    f.  Fix the grille frame by the two screws  
      Fix the terminal block cover by the two 
    screws.
     
     
    b. Fill the gap between the outside wall 
    pipe hole and the piping with sealing 
    wall sleeve, wall cap and sealer so that 
    rain and wind cannot enter.
     
     
     
     
     
     
     
     
     
     
    g. Mount insert grille to the top of indoor 
    unit body with both hands and fit it to 
    the latch of the grille frame.
     
     
    c. Adjust the internal deflectors of supply 
    air for correct air diffusion to the right 
    or left direction as per the requirements 
    for the room to be air-conditioned
     
     
    h. Check that the return air sensor is 
    properly fixed and inside its plastic clip-
    on the indoor coil.
     
     
    i.  After completion of electrical wiring to the outdoor unit: 
    • Fasten the electrical cords with the cable clamp. 
    • Install again the service door.  
     
    Electric Cables &  
    Di-frost sensor cable
    Liquid Line 
    Drain Hose  Suction 
    Line 
    Wall Sleeve 
    Wall Cap    
    Sealer Putty  
    Outdoor side 
    Wall
    Indoor Side   
    						
    							 
     
    41
     
    19. TEST RUNNING  
    19.1 Note:  
    - 
    Operate test running after mounting air filters, return grill and cabinet. 
    - Operate testing running after completion of connecting refrigerant piping lines,  
    drain line and  electrical wiring 
     
    19.2  STEPS FOR COOLING TEST RUNNING  
    a.  Move circuit breaker to ON position. 
     
    b.  After system operation becomes stabilized:      
    - Measure high and low pressures to check 
    correct refrigerant charge. (See figure & table) 
    - Measure total Amps consumed by the system. 
    - Measure System working voltage.  
     
     
     
    System Cooling Test Running  
     
    SYSTEM MODEL 53QG18-H 53QG24-H 
    AMBIENT TEMP    ºC 35 40 46 35 40 46 52 
    HIGH PRESSURE     PSI  280 315 350 260 305 345 390 
    LOW PRESSURE      PSI 72 75 79 60 62 64 66 
    TOTAL AMPS             9.5  10.5  11.5  11.8  12.7  13.9  15.1 
    Notes: 
    1-  Readings at 220 volt and 27 ºC return air to indoor unit 
        and high speed of indoor unit motor. 
    2-  System with Standard mild ambient outdoor unit with rotary compressor. 
    SYSTEM MODEL 53QG18-H 53QG24-H 
    AMBIENT TEMP    ºC 35 40 46 52 35 40 46 52 
    HIGH PRESSURE     PSI  280 312 343 392 267 300 334 382 
    LOW PRESSURE      PSI 73 75 77 79 65 67 69 71 
    TOTAL AMPS             8.6  9.3  10.1 11.1 12.2 13.1 14.0 15.3 
    Notes: 
    1-  Readings at 220 volt and 27 ºC return air to indoor unit 
        and high speed of indoor unit motor. 
    2-  System with High ambient outdoor unit with rotary compressor. 
    SYSTEM MODEL 53QG18-C 53QG24-C 
    AMBIENT TEMP    ºC 35 40 46 52 35 40 46 52 
    HIGH PRESSURE     PSI  260 295 330 370 260 297 335 375 
    LOW PRESSURE      PSI 69 71 73 75 62 64 66 68 
    TOTAL AMPS             8.5  9.1  9.8  10.5 12.5 13.4 14.4 15.5 
    Notes: 
    1-  Readings at 220 volt and 27 ºC return air to indoor unit 
        and high speed of indoor unit motor. 
    2-  System with High ambient outdoor unit with rotary compressor. (1)
    1.   High Pressure Measuring. 
    2.  Low Pressure Measuring.  (2)
     
    Outdoor Unit Details  
    						
    							 
     
    42
     
    TEST RUNNING  (Cont.) 
     
    19.4  STEPS FOR HEATING TEST RUNNING  
     
    a.  Move circuit breaker to ON position. 
     
    b.  After system operation becomes stabilized: 
    - Measure high and low pressures to check 
    correct refrigerant charge. (See figure) 
    - Measure total Amps consumed by the system. 
    - Measure system-working voltage. 
     
     
     
     
     
    System Heating Test Running   
     
    SYSTEM MODEL 53QG18-H 53QG24-H 
    AMBIENT TEMP    ºC  7 7 
    HIGH PRESSURE    PSI   240  260 
    LOW PRESSURE     PSI  52  50 
    TOTAL AMPS     8.5  11.8  
    Notes: 
    1- Readings at 220 volt and 20 ºC return air to indoor unit 
        and high speed of indoor unit motor. 
    2- System with Standard mild ambient outdoor unit with rotary compressor. 
     
    SYSTEM MODEL 53QG18-H 53QG24-H 
    AMBIENT TEMP    ºC  7 7 
    HIGH PRESSURE    PSI   230  250 
    LOW PRESSURE     PSI  60  60 
    TOTAL AMPS     7.5  11.3  
    Notes: 
    1- Readings at 220 volt and 20 ºC return air to indoor unit 
        and high speed of indoor unit motor. 
    2- System with High ambient outdoor unit with rotary compressor. 
     1.  Low Pressure Measuring. 
    2. High Pressure Measuring.  (1)
    (2)
     
    Outdoor Unit 
    Details  
    						
    							 
     
    43
     
    20. AIR CIRCULATION FOR INDOOR UNIT 42QG SERIES  
    Air is supplied into the room through the supply grilles located on the bottom of the cabinet of the indoor unit. 
    Air from the room is drawn into the indoor unit through the return grille and filters at the top of the indoor unit. 
    • Make absolutely sure that the supply and return grilles of the indoor units are not obstructed (even partially). 
     
    The airflow direction can be adjusted to optimize air distribution in the room. 
    Press button SWING repeatedly to choose one of the following louver positions:  
     
    Symbol on display 
     
    Air direction will be set automatically. 
    Louver will be set to the preset position  
    according to the operation mode. 
     
     
    • In Cool or Dry or Fan mode, the louvre will swing in cooling range. 
    • In Heat mode, the louvre will swing in heating range. 
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    6 positions can be chosen. 
    The louvre can be set to one  
    of 6 different airflow directions. 
     
     
     
     
    The louver will continuously swing up and down. 
    “Swing” always assures optimal even air distribution in the room. 
     
     
     
     
     
     
     
    COOL
    HEAT   Swing Range 
       Notes: 
    • Please do not fix the flap at position   6   for a long time, because this position 
    minimizes air circulation resulting in uneven room temperature. 
    • Do not adjust the flap by the hand during SWING operation because it may damage 
    the air swing mechanism. 
    • If you want maximum cooling or heating capacity, please set louvre at position  4  
    						
    							 
     
    44
     
    21. AFTER INSTALLATION CHECK LIST 
     
    21.1 INDOOR UNIT 
    a.   The installation location is adequate.  
    b.  The unit is solidly mounted and leveled.  
    c.   The air filters are installed correctly.  
    d.  The internal deflectors of supply air are adjusted for correct air diffusion.  
    21.2 OUTDOOR UNIT 
    a.   The installation location is adequate.  
    b.  The unit is solidly mounted and leveled.  
    c.   The wall support is fixed properly with the wall.  
    d.  The service door and its fixing screw are replaced.  
    21.3  REFRIGERANT PIPING LINES CONNECTIONS 
    a.   The refrigerant piping lines are adequate with system model.  
    b.  The insulation is wrapped on the coupling connections.  
    c.   The air purge is properly done.  
    d.  The refrigerant piping lines are tested for refrigerant leakage.  
    e.   The service valves for suction and liquid in outdoor unit are open.  
    f.   The cap nuts for flare valves are properly tightened.  
    21.4  CONDENSATE DRAIN LINE CONNECTIONS 
    a.   The Condensate drain line from indoor unit is gradually inclined downwards to the 
     outside. 
     
    b.  The Condensate water flow smoothly.  
    21.5 ELECTRICAL CONNECTIONS 
    a.   The operating voltage electrical power supply is in the voltage range shown on the 
    unit’s nameplates. 
     
    b.  The sizes of electrical connection cords are adequate according to system model.  
    c.  The size and type of unit circuit breaker are adequate according to system model.  
    d.  The electrical wiring connections between power supply, outdoor unit, indoor unit 
    and circuit breaker are adequate. 
     
    e.  All fields electrical wiring connections are tightened and secured.  
    f.  The earth wire is connected to the ground.   
    						
    							 
     
    45
     
    INSTALLATION CHECK LIST (Cont.) 
     
    21.6 FINISHING INSTALLATION 
    a.   The refrigerant piping lines, electrical cables and drain hose are lumped together. 
      The drain hose is at the bottom of lump. 
     
    b.  The wall passage hole is properly sealed.  
    21.7 TESTING RUNNING 
    a.   The cooling and heating cycles are tested 
      At least one complete cooling cycle of unit operation is observed. 
      At least one complete heating cycle of unit operation is observed. 
     
    b.  There is no any abnormal noise or vibration from the outdoor unit during operation.  
    c.   There is no any abnormal noise or vibration from the indoor unit during operation.  
    d.  The wireless remote control operate Correctly.  
    e.   Each lamp on the indoor unit lights normally.  
    21.8 CUSTOMER GUIDANCE 
    a.   The correct operation of the air conditioner has been explained to the customer 
      including the following points:   
    • Starting and stopping method  
    • Operation switching  
    • Temperature adjustment  
    • Timer Function  
    • Air Flow switching  
    • Other remote control operations  
    • How to use the air louvers  
    • Filter removal and cleaning  
    b.  The operation and installation manuals have been given to the customer.  
      
    						
    							 
     
    46
     
    22.  INSTALLATION OF OPTIONAL AIR FILTERS 
     
    22.1 NOTE: 
      Optional set of air filters can be added and field installed as shown below. 
     
     
    22.2 TYPE OF AIR FILTERS:  
    Standard anti – bacteria air filters for dust & bacteria removal 
     
    Optional carbon filter for odor removal 
     
    Optional photo-catalytic filter for cigarette smoke removal 
     
     
     
    22.3 INSTALLATION STEPS OF OPTIONAL AIR FILTERS:  
    Step (1): After lifting return air grill up to the top of the unit, pull the standard air filters downward. 
     
    Step (2): Install optional air filters inside the top guides of the unit (specified for optional air filters), 
    then install standard air filters. 
     
    Step (3): Install return air grille and close it. 
     
      
    						
    							 
     
    47
     
    23.  SELF DIAGNOSTIC FUNCTION FOR MALFUNCTIONS DETECTION 
     
    EXPLAINATION OF SELF-DIAGNOSTIC FUNCTION 
     
    -  Self-diagnostic function is the key for success of air conditioner operation.  
    -  The printed circuit boards existing inside the indoor unit are equipped with self-diagnostic function 
    to detect malfunction and automatically stops the operation at the air conditioner. 
     
    -  Once a malfunction is detected, the diagnostic control section will force the system mode to OFF 
    for 3 minutes. After the OFF delay, system mode releases and allowed returning to its normal state. 
    The system will be allowed to restart on its own.  
    The diagnostic control section will allow the system to fail 5 consecutive times before shutting 
    down the system.  
    If the system is performing an active defrost, both the compressor drive and reversing valve 
    malfunction test will be cancelled and reinitiated after the following compressor OFF-ON cycle.  
     
    - The unit on lamp is scanned every half-second and the error codes are displayed by the flashing 
    frequency of unit on lamp. The error codes are displayed during SHUT-OFF  (3 minutes off and after 
    the 5th retry failure). 
     
     
      
     
     
     
     
     
     
     
     
     
     
     
     
    Malfunction 
    Reason 
    Flashing 
    Frequency 
    Allowed 
    Modes 
    Return Air Sensor  3  Fan Only 
    Indoor Coil Sensor  4  Fan Only 
    Compressor Drive  9  Fan Only 
    Electronic Control PCB (EEPROM)  10  Fan Only 
     
    Notes : 
     
    1-  Prior to the malfunction repair, disconnect the electrical mains supply by moving the circuit 
    breaker to OFF position. 
     
    2-  After repairing the malfunction:  
         2-1 Press Reset button (3)  
         2-2  connect the electrical main supply by moving the circuit breaker to ON position  
         2-3 operate the air conditioner by using the wireless remote control. 
     
    1 : Green led flashes 
         if there is a malfunction 
    3 : Reset  Button 
    1
    3 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier 42qg24-h Manual