Home > Carrier > Air Conditioner > Carrier Air 5 Manual

Carrier Air 5 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Air 5 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							T-- 298 3-17 3.11.2 Timeguard Timer
    A 3-- minute timeguard is built into the thermostat
    immediately upon power up, and any time the
    compressor (output “Y”) turns off. The compressor will
    not turn on until the timeguard has expired. Pressing UP
    and FAN buttons simultaneously will override the
    timeguard for 1cycle.
    3.11.3 Cycle Timer
    In normal cooling (and heating) operation the
    thermostat will notallow more than4 equipment cycles
    per hour (or 1 cycle every 15 minutes). Both the “Y”
    (cooling) and “W” (heating) outputs have a 15-- minute
    timer that starts counting down when the output is
    turned on, (e.g., if “Y” output is turned on for 9 minutes
    and then satisfies, it cannout turn back on for another 6minutes regardless of demand). However, pressing UP
    and FAN buttons simultaneously or changing the set
    point will override the timer for 1 cycle.
    3.11.4 Minimum On Timer
    Once the equipment has turned on, it will remain on for a
    minimum of 2 minutes regardless of demand. However,
    the equipment can turn off in less than 2 minutes if a
    change in set point, or a changein mode occurs.
    3.11.5 Error Messages
    E4 will be displayed if the thermostat has an internal
    memory failure. If E4 appears, replace the thermostat.
    -- -- (two dashes) will be displayed if the thermostat
    cannot properly read the room temperature. If -- --
    appears, replace the thermostat.
    POWERBOX
    ASSEMBLY
    UPPER UNIT
    1234 2
    1
    12 34
    1
    2
    3
    4
    5L
    N2
    N1
    W
    Y
    GH
    GL
    C
    Y
    GH
    GL
    R
    CCOOL (Compressor)
    FAN (High)
    FAN (Low)
    12VDC LowVoltage
    Power Supply
    CEILING UNIT
    Motor Comp.
    Factory WiringField Wiring
    THERMOSTAT J
    115V AC High Voltage
    Power Supply
    Figure 3-40 Wall Thermostat Wiring Diagram -- Cool Only Model 
    						
    							T-- 2983-18 POWERBOX
    ASSEMBLY
    UPPER UNIT
    1234 21
    12 34
    1
    2
    3
    4
    5
    1
    2 L
    N2
    N1
    W
    Y
    GH
    GL
    C
    TBY
    GH
    GL
    R
    C
    COOL (Compressor)
    FAN (High)
    FAN (Low)
    12VDC LowVoltage
    Power Supply
    CEILING UNITFURNACE + 12VDC12 VDC (Gnd)
    Motor Comp.
    115V AC High Voltage
    Power Supply
    Factory WiringField Wiring
    THERMOSTAT
    J
    Blue
    Blue
    Figure 3-41 Wall Thermostat Wiring Diagram -- Heat/Cool Model 
    						
    							T-- 298 4-1
    SECTION 4
    WIRING SCHEMATICS
    4.1 INTRODUCTION
    This Section contains wiring schematics for the AirV units.
    Figure 4-- 1 is the schematic for the standard upper unit assembly and it is applicable to all standard units.
    Figure 4-- 2 is the schematic for the Low Profile upper unit assembly.
    Figure 4-- 3 is the schematic for a free blow ceiling unit without heat while Figure 4-- 4 is a free blow unit with heat.
    Figure 4-- 5 is for a ducted unit with microprocessor control.
    Figure 4-- 6 is for an Upper Unit Heat Pump with free blow application and Figure 4-- 7 is the matching free blow ceiling
    unit.
    Figure 4-- 8 is for the Upper Unit Heat Pump ducted application and Figure 4-- 9 is the matching ducted ceiling unit.
    Note that the ducted units have 115 VAC power for the components and 12 VDC power for the microprocessor control
    system.
    Figure 4-- 10 is for the ducted or free blow application that uses a wall-- mounted thermostat, with or without the furnace
    option.
    Where applicable, diagrams that designate 115 Volt, 60 H, 1 Phase, are also available using 220 Volts, 50 H, 1 Phase.
    Most noteably Figure 4-- 1 and Figure 4-- 5.
    4P
    2P
    2P
    CF
    H
    1 11
    22
    3
    4
    2
    BLK
    BLU BLK
    BLU
    WHT
    WHT GRN/YEL
    CONTROL
    BOXEVAP. GRN/YELGRN/YEL
    WHTBRN
    12
    CAPACITOR
    YEL YEL
    RED
    BLU
    COMPRESSOR
    R
    C
    S
    FAN MOTOR
    OVERLOAD PROTECTOR
    RED
    PTCBLU
    PLUG CONNECTS
    TO CEILING UNIT
    SEE FIG> 4-- 3
    OR 4 -- 4
    (If Used)
    Figure 4--1 Upper Unit Schematic -- Standard & HC
    4P
    2P4P
    CF
    H BLK
    BLU BLK
    BLU
    WHT GRN/YELGRN/YEL
    WHT
    WHT
    WHT
    BRNBRN
    1
    (3)2CAPACITOR
    YELRED OLP
    (IF USED)
    BLUBLU RED
    COMPRESSOR
    R
    C
    S 1
    2
    3
    4
    1
    21
    2
    3
    41
    2
    3
    4
    OLP: OVERLOAD PROTECTION
    PTC: START THERMISTER
    JTB: JOINT TERMINAL BLOCK
    FMC: INDOOR FAN MOTOR CAPACITOR
    PLUG CONNECTS TO CEILING UNIT.
    SEE DIAGRAM SUPPLIED WITH
    CEILING UNIT FOR ADDITIONAL
    WIRING.
    INDOOR FAN MOTOR
    YEL
    WHT
    YEL1
    2
    31
    2
    3
    WHT
    3PYEL
    BRN
    FMC
    YEL
    WHT
    BRN
    OUTDOOR FAN MOTOR
    PTC
    (IF USED)LEGEND
    (UNIT -- 99 -- 00468 -- 10)
    Figure 4--2 Upper Unit Schematic -- Low Profile 
    						
    							T-- 2984-2
    2P
    GRN/YELORNWHT
    WHT
    ASM
    PLUG CONNECTS TO UPPER UNIT.
    SEE DIAGRAM SUPPLIED WITH
    UPPER UNIT FOR ADDITIONAL WIRING.
    4P
    2P
    1 1
    2
    3
    4
    2
    {
    ASWO (OFF)
    I(ON)2
    2--1 SWITCH
    POSITIONCONTACTS MADE
    HIGH FAN
    LOW FAN
    OFF
    LOW COOL1--4 . 1--6
    1--2 . 1--6
    NONE
    1--2 . 1--6 . 1--8
    1--4 . 1--6 . 1--8
    HIGH COOL
    ASM : AIR SWEEP MOTOR
    ASW : AIR SWEEP SWITCH
    SW : SWITCH
    IT : INDOOR THERMOSTAT
    LEGEND
    ORNBLU BLK
    ORN
    SWIT
    ASW
    21
    CL
    8
    6 12
    4
    YEL BLK
    WHT
    YEL
    12
    GRN/YEL11 5 VA C
    SUPPLY
    WIRE
    Figure 4--3 Ceiling Unit Schematic -- Cooling Only
    2P
    CEC2P
    PLUG CONNECTS TO UPPER UNIT.
    SEE DIAGRAM SUPPLIED WITH
    UPPER UNIT FOR ADDITIONAL
    WIRING.
    GRN/YEL
    GRN/YEL
    4P
    2P
    2 1
    2
    3
    4
    1{
    ASWO (OFF)
    1(ON)22--1 SWITCH
    POSITION CONTACTS MADE
    OFF
    LOW FAN
    HIGH FAN
    LOW COOLNONE
    L1--L . L1--A
    L1--H . L1--A
    L2--C . L1--L . L1--A . B--3
    L2--C . L1--H . L1--A . B--3
    L2--HT.L1--L.L1--A.B--1 HIGH COOL
    HEAT
    ASM AIR SWEEP MOTOR
    ASW AIR SWEEP SWITCH
    SW SWITCH
    CEC CLOSED END CONNECTOR
    BT BIMETAL IT INDOOR THERMOSTATLEGEND
    ORNBLU BLK
    ORN
    ORNWHT
    WHT
    ASM
    HEATER-- ASSY SW
    IT
    ASW
    21
    11
    32 1
    L2B
    3
    C HT
    A L1L H
    YEL BLK
    BLK REDYEL
    BLU
    BLK BLK
    WHT
    WHT WHT
    WHTHEATER
    BT
    1
    12
    2
    11 5 VA C
    SUPPLY
    WIRE
    Figure 4--4 Ceiling Unit Schematic -- Heat/Cool
    1
    2
    2 21
    3
    1
    1 1Y
    L
    N1 N2 2 34 12
    4 3 2
    (--) (+)
    BLK
    BLKWHT BLU
    BLK
    GRN/YEL GRN/YELWHT
    WHT
    BLU BLUBLK RED
    24
    CN9 CN9
    135786
    CN1
    CN4
    CN4
    CN1
    CN2CN3
    RY1
    RY2
    D1 RY3
    RY4250V 3.15AFUSE
    11
    2
    3
    4
    5
    6
    7 7 65 432 RA Th
    BRNBLKIDC Th
    24 135786
    8
    1
    7 65
    4
    3
    2
    88
    DISPLAY PCB AS
    11
    2
    3
    321
    3 2
    CONTROL
    PCB
    ASS’Y
    LEGEND
    IDC Th : INDOoR COIL THERMISTER
    RA Th : ROOM AIR THERMISTER
    KY : RELAY
    DI:DIODE
    115 VAC POWER
    12 VDC POWER
    Figure 4--5 Ceiling Unit, Standard -- Ducted 
    						
    							T-- 298 4-3
    CONTROL
    BOXEVAP.
    RVC 2P 4P
    2P2P4P
    CF
    H BLK
    BLU BLK
    BLU
    WHT WHT BRN
    BLK BLK
    BLK(BLU) GRN/YEL GRN/YELGRN/YEL
    WHT
    WHT WHT
    BRN BRN
    1
    (3)2
    CAPACITOR
    YEL REDRED OLP
    (IF USED)
    BLUBLU RED
    PTC
    COMPRESSOR
    R
    C
    S
    FREEZE
    SWITCHFA N M O TO R
    1
    2
    3
    4
    1
    2
    1
    21
    2
    3
    41
    2
    3
    4
    1
    21
    2
    OLP: OVERLOAD PROTECTION
    PTC: START THERMISTER
    RVC: REVERSING VALVE COIL
    PLUG CONNECTS TO CEILING UNIT.
    SEE DIAGRAM SUPPLIED WITH
    CEILING UNIT FOR ADDITIONAL
    WIRING.
    Figure 4--6 Heat Pump -- Upper Unit -- Free Blow
    PLUG CONNECTS TO UPPER UNIT.
    SEE DIAGRAM SUPPLIED WITH
    UPPER UNIT FOR ADDITIONALWIRING.
    HEATER AS
    HEATER BTGRN/YEL
    GRN/YEL4P
    2P 2P 2P2P
    {
    ORN
    WHT
    BRN BLK
    WHT REDYELBLUBLK
    ORN
    ORNWHT
    WHT BLK
    ASM SW
    ITASW 21
    1
    C
    L H
    2 B L2
    3 3 C
    1 HTA L1L H
    YEL BLKBLK
    BLK
    CEC WHT
    WHTSWITCH
    POSITIONCONTACTS MADE
    OFF
    LOW FAN
    HIGH FAN
    LOW COOL
    HIGH COOL
    HEATINGNONE
    L1--L . L1--A
    L2--HT.L1--L.L1--A.B--1L2--C . L1--H . L1--A . B--3 L2--C . L1--L . L1--A . B--3 L1--H . L1--A
    ASWO (OFF)
    1(ON)2
    2--1
    LEGEND 1
    2
    3
    4
    1
    2
    1
    2 1
    12
    2
    112 2
    ASM: AIR SWEEP MOTOR
    ASW: AIR SWEEP SWITCH
    SW: SWITCH
    IT: INDOOR THERMOSTAT
    CEC: CLOSED END CONNECTOR
    BT: BIMETAL
    11 5 VA C
    SUPPLY
    WIRE
    Figure 4--7 Heat Pump -- Ceiling Unit -- Free Blow 
    						
    							T-- 2984-4
    LEGEND
    RVCPLUG CONNECTS TO CEILING UNIT.
    SEE DIAGRAM SUPPLIED WITH
    CEILING UNIT FOR ADDITIONAL
    WIRING.
    CN
    CN
    CF
    H
    OLP :OVERLOAD PROTECTORPTC :START THERMISTOR
    RVC :REVERSING VALVE COILCN :HOUSING CONNECTOR
    ODA Th :OUTDOOR AIR THERMISTOR
    ODC Th :OUTDOOR COIL THERMISTORBLK BLK
    BLK(BLU)
    CONTROL
    BOXEVAP.
    BLU
    RED
    RED BRN
    BLU
    WHT GRN/YELGRN/YEL
    WHT WHT BLK
    BRN
    BRN
    1
    (3)2
    CAPACITOR
    YEL YEL
    RED OLP
    (IF USED)
    BLUBLU RED
    PTC
    COMPRESSOR
    R
    C
    S
    FAN MOTOR
    ODC Th
    ODA Th 1
    2
    3
    1
    2
    3
    4
    1
    2
    1
    21
    2
    3
    5
    6
    Figure 4--8 Heat Pump -- Upper Unit -- Ducted
    ODC ODA
    RVC MOTORCOMPRESSOR
    FUSED1
    250V 3.15A
    3 3
    332
    1 7 6
    5 4 3
    2
    1 11
    22
    33
    44
    55
    66
    7
    8 8 87
    1 1
    1
    2 2
    2 1
    2
    3
    4
    FURNACE SIGNAL
    12VDC POWER(--) (+)
    115VAC POWER
    BLK WHT
    BLK
    BLK GRN/YEL
    RED BLU
    BLK RED
    BRN
    GRN/YEL WHT
    BLK
    WHT
    BLUBLU BLUBLK RED
    PLUG CONNECTS TO UPPER UNIT.
    SEE DIAGRAM SUPPLIED WITH UPPER UNIT
    FOR ADDITIONAL WIRING.
    ODA Th :OUTDOOR AIR THERMISTOR
    *
    * *FACTORY WIRING
    (12VDC LOW VOLT.) (115VACHIGHVOLT.)
    FIELD WIRING FIELD WIRING
    LEGEND
    NOTE
    CONTROL PCB
    POWER PCB ASS’Y ASS’Y
    2
    24
    4 CN9
    DISPLAY PCB AS
    CN91
    13
    3576
    5788
    6 CN1
    CN6 CN5
    CN6 CN4 CN4
    CN1
    CN2CN3 CN5
    K1
    K4 K3 K7
    K2
    K61 1
    1 1
    2 2 2
    2 2
    1 3 3
    3441 22 1
    Y
    L
    N2
    N1
    12 RA Th
    BRN BLK
    IDC Th
    IDC Th: INDOOR COIL THERMISTER
    RA Th: ROOM AIR THERMISTER
    ODC Th: OUTDOOR COIL THERMISTER
    RVC: REVERSING VALVE COIL
    D1: DIODE
    K: RELAY
    Figure 4--9 Heat Pump -- Ceiling Unit -- Ducted 
    						
    							T-- 298 4-5
    Figure 4--10 Ceiling Unit -- Wall Thermostat -- Ducted & Free Blow
    4.2 WALL MOUNTED THERMOSTATS
    For proper wiring of Wall Mounted Thermostats as an accessory, refer to Figure 3-40 (Wall Thermostat Wiring
    Diagram -- Cool Only Model) or Figure 3-41 (Wall Thermostat Wiring Diagram -- Heat/Cool Model). 
    						
    							Index -1T-- 298
    INDEX
    A
    Air Handling System , 3-8
    Air Sweep Removal, 3-3
    Air Sweep Switch , 3-2
    C
    Capacitor Testing, 3-9
    Capacitor Testing and Replacement, 3-9
    Ceiling Grill -- Ducted, 3-4
    Ceiling Grill -- Free Blow, 3-1
    Ceiling Panel -- Free Blow, 3-2
    CEILING UNIT -- DUCTED SYSTEMS, 3-4
    CEILING UNIT -- FREE BLOW , 3-1
    Cleaning, 3-1
    Compressor , 3-6, 3-13
    Condenser Fan, 3-7
    Control Box -- Ducted, 3-4
    Control Box -- Upper Unit, 3-6
    Controls, 3-1
    Cool Only Thermostat, 3-15
    D
    Design Change, 1-1
    E
    Evaporator Blower Wheel, 3-8
    Exterior Cover, 3-5, 3-10, 3-15
    F
    Filter Removal -- Free Blow, 3-1
    Filter Removal -- Ducted, 3-4
    Fuse Removal -- Ducted, 3-5
    H
    Heat Strip, 3-3
    Heat/Cool Thermostat, 3-15
    I
    Indoor Thermostat , 3-3
    INTRODUCTION, 1-1, 4-1
    L
    LCD DISPLAY, 3-15, 3-16
    Leaks, 3-1
    M
    Main Pcb Board, 3-5
    Master Control Switch, 3-2
    Motor , 3-7
    Mounting, 3-1
    P
    Painting, 3-1
    PCB Display , 3-5
    PREVENTATIVE MAINTENANCE, 3-1
    R
    REFRIGERANT CYCLE, 1-9, 1-10
    S
    Serial Number, 1-1
    SERVICE -- GENERAL, 3-1
    SERVICE -- UPPER UNIT -- LOW PROFILE, 3-10
    SERVICE AND MAINTENANCE, 3-1
    START--UP, 1-9
    T
    THERMOSTAT INSTALLATION AND START--UP IN-
    STRUCTIONS (WALL MOUNTED), 3-15
    TROUBLESHOOTING, 2-1, 2-3
    U
    Upper Scroll Assembly, 3-7, 3-10, 3-11, 3-12, 3-13
    W
    WIRING SCHEMATICS, 4-1 
    						
    							©2006 Carrier CorporationDPrinted in U. S. A. 0606
    Carrier Transport Air Conditioning
    50 Grumbacher Road
    York PA 17402 USA
    Tel: 1 --800 --673 --2431
    Fax: 1 --717 --764 --0401
    A member of the United Technologies Corporation family. Stock symbol UTX
    Carrier Transicold Division,
    Carrier Corporation
    Transport Air Conditioning Group
    P.O. Box 4805
    Syracuse, N.Y. 13221 U.S A
    www.carrier.transicold.com 
    						
    All Carrier manuals Comments (0)