Home > Data Delivery Devices > Communications receiver > Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual

Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Data Delivery Devices VHF, UHF & ISM Wireless RTU RFScada 8ADI-9DO 4ADI-5DO User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 2 Data Delivery Devices manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 41 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
      
    We have now almost completed the system configuration. We have set up output signal 
    routing for the master unit (0) plus output signal routing for units 1 and 2. By checking the ‘Unit 
    Enabled’ box when units 1 and 2 routing was displayed the configuration program was informed that 
    the master needs to communicate with units 1 & 2; this RFScada network will consist of three units, 
    the master plus units 1 and 2.  
    All that remains is to verify that the master will not try to communicate with other units, and 
    finally we can store all of these configuration settings in the master. Click on the slider again to view 
    the routing for unit 3 (even though we do not wish to use unit 3). Since we do not want to try to 
    communicate with unit 3 the ‘Unit Enabled’ check box should not be checked.  This means the master 
    will not attempt to communicate with it. The master will report a good network status, both via the 
    Configuration Screen showing Unit 2 Relay 
    and Analog Output Signal Sourcing  
    Relay 2 on Unit 2 driven 
    by input 3 on unit 0 Relay 1 on Unit 2 will  
    be driven by digital input 
    2 on unit 0 
    This indicates outputs 
    being configured are 
    for Slave Unit 2. 
    Relays 5 to 8 on the Unit 2 will all be driven 
    by digital input 7 on unit 0, i.e. unused 
    Analog output configuration does 
    not matter for channels 3 to 8  
    Relay 3 on Unit 2 driven 
    by input 1 on unit 1 
    Relay 4 on Unit 2 driven 
    by input 2 on unit 1 
    Analog output 1 on Unit 2 will  be 
    driven by analog input 1 on unit 0 
    Analog output 2 on Unit 2 will  be 
    driven b
    y analog input 1 on unit 1 
    Checked indicates master 
    will communicate with unit 
    Unchecked  
    indicates unit 
    2 outputs will 
    be sourced 
    from discrete 
    inputs   
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 42 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    status LED & relay plus to all other units, when it successfully communicates with all enabled units. 
    So we must ensure that this box is not checked for unit 3 and it is not checked for the remaining 28 
    other possible units (ID’s of 4 to 31). When the ‘Unit Enabled’ box is not checked the relay and analog 
    output routing sections are disabled since they do not serve any purpose on unused units.  
     
    By adjusting the slider all remaining possible configurations for slave ID’s will quickly scroll by, 
    and within a couple of seconds the user can verify that no other slave units are enabled. If they are 
    enabled the corresponding ‘Unit Enabled’ check box may be un-checked.  
      Finally we can write these settings to the master unit. To save the system configuration click 
    on the ‘Write to RFScada’s EEPROM’ button to store these settings in the RFScada master units non-
    volatile memory. If the previously configured slave units are operating nearby several clicks may be 
    heard as all of the units will start to communicate using the new configuration settings. All the analog 
    and digital signals should now be routed to match the example of the tank and two pumps. The whole 
    process took just minutes and all settings are permanently stored in the RFScada units. The settings 
    may also be stored on the local PC in a text file (actually as a list of Modbus registers, see the 
    Example Configuration Screen for an 
    Unused Unit Routin
    g (ID of 3 shown) 
    This indicates configuration 
    for slave Unit 3 
    Analog output routing is disabled 
    since this unit is not enabled  
    Un-checked indicates master will NOT 
    tr
    y to communicate with unit 3 
    Relay output routing is disabled 
    since this unit is not enabled    
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 43 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Modbus section for further details) so they can be easily be copied into another system in the future. 
    To save the configuration select the ‘File - Save‘ menu, a prompt appears for a file name and location 
    to save the settings as. A saved configuration may also be loaded in a similar manner using the ‘File - 
    Load’ menu.  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 44 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 45 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Monitoring and Overriding Real Time Inputs. 
     
      Once the system is configured all units should communicate correctly with each other. By 
    selecting ‘Display Registers’ from the configuration program another screen is displayed, with graphs 
    showing analog levels and 8 indicators for digital inputs. If the Modbus connected unit is a slave, all of 
    the connected units analog 
    and digital inputs may be 
    monitored at once. If the 
    Modbus connected unit is 
    the master then every 
    unit’s analog and digital 
    inputs may be monitored at 
    once. Use the slider to 
    select the unit to display. 
    This is a very quick and 
    easy way to monitor every 
    input – even those miles 
    away!. The DC Voltage 
    measured at every unit is 
    also displayed on the right 
    hand side, very useful to 
    see and monitor on remote 
    solar powered systems. 
    The two larger indicators 
    below the digital input 
    indicators show the real time ‘Modbus State’ between the PC and connected unit, the ‘Network State’ 
    shows the real time condition of the RFScada network, in a similar mode to the ‘Network state’ LED 
    on each unit. Additionally the actual Modbus data transmitted and received from the connected unit 
    may be displayed at the bottom of the screen if required.  
      When displaying information from 4ADI-5DO units analog channel six displays the ambient 
    temperature on the printed circuit board. The temperature is approximately (reading * 0.4902) - 60 in 
    °Celsius, or 32 + (((reading * 0.4902) – 60) * 9) / 5 in °Fahrenheit. When using the ISM high power 
    option analog 
    channel 5 
    corresponds to the 
    received signal 
    strength at that unit, 
    so it is possible to 
    read the signal 
    strength at remote 
    sites. The scale is 
    from 0 (no signal) to 
    approximately 290 
    (full signal). Note 
    that it is normal for 
    the reading to 
    fluctuate.   
     
     Furthermore, 
    every input, both 
    analog and digital, 
    may be ‘overridden’ 
    using this display.  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 46 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    Click on the ‘override’ button, which will start to flash. Now each input state display button may be 
    clicked and will toggle between Active and Inactive, this will have the same effect as physically 
    activating that particular digital input, which is being overridden for the selected unit. Similarly, the 
    sliders next to each analog input display may be adjusted, and this will have the effect of overriding 
    each analog input on the selected unit. This makes it very easy to test configurations and different 
    setups, without requiring the actual final connected hardware. From the master units location (or via a 
    serial port, phone/modem etc. connection to the master unit) complete setups can be tested, every 
    remote input may be overridden and monitored, and system integrity can be verified. All signal routing 
    (and special modes of operation) will still occur normally, as this mode effectively overrides the 
    selected units inputs only, all other inputs on other units will still operate normally, and all outputs will 
    operate normally, so it’s very easy to see the effect of input changes on complex systems.  
      It is even possible to override units not configured for operation; so if another configured unit is 
    set with the un-configured units inputs as its signal source it will react to Modbus overridden signals. 
    This allows Modbus control of all outputs without overriding any physical ‘active’ unit. When the 
    override button is clicked again the button will stop flashing, the display will revert to normal operation, 
    and the unit which was being overridden will revert to providing normal data from its standard analog 
    and digital inputs.  
      This change back to normal operation will be delayed until the programmed ‘Modbus Override” 
    time expires, typically several seconds. Allowing the unit to remain in the ‘overridden’ mode for a 
    programmable time has several benefits. Although the RFScada configuration program ‘register 
    override’ mode may be used for testing and configuration purposes it also provides complete 
    monitoring and control capability of the whole system via Modbus.  
      
      Some users will want purchase or design their own control routines to run on a PC or PLC that 
    (via Modbus) controls and/or monitors an RFScada network.  This may be done using products such 
    as DAQFactory®, Visual Basic®, Labview®, Wonderware® etc. or supplied by vendors such as Data 
    Delivery Devices LLC. These programs continually read and write data on the RFScada network and 
    since the data is continuously being written the RFScada network will output signals depending on a 
    combination of the RFScada system configuration, the actual input signals and the Modbus 
    ‘overridden’ signals. Any units that have been configured for ‘Modbus only’ control will only react to 
    Modbus commands from the control system; typically this mode is for systems that rely on a PC to 
    control the whole system. However, if the PC fails or loses power for example, once the ‘Modbus 
    Override’ time expires without the connected RFScada receiving any valid Modbus data the RFScada 
    reverts to the standard mode, which should be configured for a ‘failsafe’ condition. Therefore the 
    complete system could revert to a known, safe condition in the case of a PC hardware or software 
    failure. 
      
     To summarize, the RFScada system may be used in several ways.  
      
    1.  As a standalone system it can route any analog input on any unit to any 
    one (or more) analog outputs on any units. It also routes any digital input 
    on any unit to any one (or more) digital outputs on any units. All units are 
    aware of, and continually indicate, the confirmed operational status of all 
    other units. If any unit fails all units can revert to a known state within a 
    user programmed time. 
    2.  All of (1) plus the built in control routines, for complete, automated pump 
    and tank control using either analog and/or digital inputs. 
    3.  All of (1) and (2) with the addition of monitoring any analog and digital 
    input remotely using an RS-232, RS-485 or phone/modem connection via 
    Modbus.  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 47 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    4.  All of (1), (2) and (3) with the capability of overriding any analog and 
    digital input remotely using an RS-232, RS-485 or phone/modem 
    connection via Modbus. 
    5.  All inputs may be monitored using an RS-232, RS-485 or phone/modem 
    connection via Modbus using a program such as DAQFactory. All outputs 
    may be directly controlled with the same program. 
     
     
    This flexibility allows simple or very complex systems to be assembled, with many options 
    possible. Call Data Delivery Devices LLC for advice on how your specific application may be 
    configured; since units are pre-configured at the factory even complex systems usually require no 
    setup in the field.             
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 48 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 49 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990 
    General System Information. 
     
      Selecting the about menu from the RFScada configuration &  tester program will display 
    current information about the connected unit. An example of a typical display is shown below. 
    Typically these parameters are set at the factory or depend on the units configuration.  
    						
    							RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC Page - 50 – Bartlesville OK Tel 918-335-3318      FAX 918-398-9990  
    						
    All Data Delivery Devices manuals Comments (0)