Home > Honeywell > Control panel > Honeywell control panel OMNI 408408EU User Manual

Honeywell control panel OMNI 408408EU User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell control panel OMNI 408408EU User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							 
    – 21 – 
    Miscellaneous Commands (cont’d) 
    The display will show: 
    LCD Keypad: 
    BYPASSED: ZN1 
      
    Fixed-Word Keypad: 
    01 
     BYPASS 
     
    Set Time and Date 
    To set the time and date, press [#], [3].  Enter 2 digits each for hours, 
    minutes, month, day, and year. 
         hours (00-23)          minutes (01-59)   
        month (01-12)         day (01-31)                year (00-99) 
     
    In order to acknowledge your entry, a beep sounds after you set each 
    component of the time and date. 
    Turn Chime On/Off 
    Chime is an optional feature that causes the keypad to chime when 
    selected doors are opened when the burglary protection is off or 
    disarmed. 
    Only your installer can program a zone for the Chime feature, but 
    once it is programmed, you can turn Chime on or off to meet your 
    daily needs.  To turn Chime on or off:       
    Press [#], [6]. 
    The fixed-word keypad displays the current status of the chime 
    feature.  
    						
    							– 22 – 
    Testing the System 
    System Test 
    We recommend that you test your system once a week using the 
    following procedure: 
     
    If your system is monitored, contact your central station before you perform this 
    test. 
    1.  Arm your security system. 
    2.  Wait until your exit time is over and then activate the system by 
    opening a protected zone (for example, a window or door). 
    3.  Confirm that the alarm sounding device (bell or siren) sounds.  If 
    your system is connected to a central station, the keypad sounds 
    the ringback tone to confirm that the signal was received. 
    4.  Disarm the security system. 
    5.  Call the central station to tell them you are finished testing. 
    Battery Test 
    We recommend that you test your battery once a month.  To test your 
    backup/standby battery, follow this procedure. 
    1.  Remove main power from the system. 
    2.  Observe that the AC indicator light on the keypad goes off. 
    3.  Activate your alarm by performing the above SYSTEM TEST.   
    Remember to contact your central station if your system is 
    monitored. 
    4.  Restore main power to the security system. 
    If you have any further questions about the operation of your system, 
    please contact your alarm company.  
    						
    							 
    – 23 – 
    Recommendations on Smoke Detectors 
    With regard to the number and placement of smoke/heat detectors, we 
    subscribe to the recommendations contained in  the National Fire 
    Protection Association’s (NFPA) Standard #72 noted below. 
     
    Early warning fire detection is best achieved by the installation of fire 
    detection equipment in all rooms and areas of the household as 
    follows:  A smoke detector installed outside of each separate sleeping 
    area, in the immediate vicinity of the bedrooms and on each additional 
    story of the family living unit, including basements and excluding 
    crawl spaces and unfinished attics. 
     
    In addition, the NFPA recommends that you install heat or smoke 
    detectors in the living room, dining room, bedroom(s), kitchen, 
    hallway(s), attic, furnace room, utility and storage rooms, basements, 
    and attached garages. 
     
    DININGKITCHENBEDROOM
    BEDROOM
    BEDROOM
    BEDROOM
    LIVING ROOMBEDROOMBDRM
    BDRM DINING 
    LIVING ROOM TV ROOMKITCHEN
    BEDROOM
    BEDROOM TO
    BR
    LVNG RM
    BASEMENTKTCHN.CLOSED
    DOORGARAGE
    Smoke Detectors for Minimum Protection
    Smoke Detectors for Additional Protection
    Heat-Activated Detectors
    floor_plan-V0  
    						
    							– 24 – 
    Emergency Evacuation 
     
    2nd FLOOR
    BACK
    FRONT
    floor_plan2-V0
    BATH CLOSET
    BEDROOM
    BEDROOM
    BEDROOM
    1st FLOOR
    BATH KITCHEN
    BEDROOMBEDROOM
    PORCH
    BACK DOOR
     Establish and regularly practice a plan of escape in the event of 
    fire. The following steps are recommended by the National Fire 
    Protection Association: 
    1.  Position your detector or your interior and/or exterior 
    sounders so that they can be heard by all occupants. 
    2.  Determine two means of escape from each room.  One path o
    f 
    escape should lead to the door that permits normal exit from 
    the building.  The other is an alternative route, such as 
    through a window, should your normal escape path be 
    unpassable.  Station an escape ladder at such windows if 
    there is a long drop to the ground. 
    3.  Sketch a floor plan of the building.  Show windows, doors, 
    stairs, and rooftops that can be used to escape.  Indicate 
    escape routes for each room.  Keep these routes free from 
    obstruction and post copies of the escape routes in every 
    room. 
    4.  Assure that all bedroom doors are shut while you are asleep.  
    This will prevent deadly smoke from entering while you 
    escape. 
    5.  Try the door.  If the door is hot, check your alternate escape 
    route.  If the door is cool, open it cautiously.  Be prepared to 
    slam the door shut if smoke or heat rushes in. 
    6.  When smoke is present, crawl on the ground.  Do not walk 
    upright, since smoke rises and may overcome you. Clearer 
    air is near the floor. 
    7.  Escape quickly; don’t panic. 
    8.  Establish a common meeting place outdoors, away from your 
    house, where everyone can meet and then take steps to 
    contact the authorities and account for those missing.  
    Choose someone to assure that nobody returns to the house 
    — many die going back.  
       
    						
    							 
    – 25 – 
    RADIO FREQUENCY EMISSIONS STATEMENTS 
    FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 
    This device complies with part 15 of the FCC rules.  Operation is subject to the following two conditions:  (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. 
    INDUSTRY CANADA 
    This Class B digital apparatus complies with Canadian ICES-003. 
    Cet Appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. 
     
    TELEPHONE/MODEM INTERFACE STATEMENTS 
    FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 
    This equipment complies with Part 68 of the FCC rules.  On the front cover of this equipment is a label that contains the FCC registration number and Ringer Equivalence Number (REN).  You must provide this information to the telephone company when requested. 
    This equipment uses the following USOC jack: RJ31X 
    This equipment may not be used on telephone-company-provided coin service.  Connection to party lines is subject to state tariffs.  This equipment is hearing-aid compatible. 
    INDUSTRY CANADA 
    NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction. 
    Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. 
    Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment. 
    Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas. 
    Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or electrician, as appropriate. 
    RINGER EQUIVALENCE NUMBER NOTICE 
    The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface.  The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5. 
      
    						
    							– 26 – 
    INDUSTRIE CANADA 
    AVIS: L’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur. Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations. Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par l’utilisateur ou à cause de mauvais fonctionnement. Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales. Avertissement: L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des installations électriques, ou à un électricien, selon le cas. AVIS: L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5. 
    TELEPHONE OPERATIONAL PROBLEMS 
    In the event of telephone operational problems, disconnect the control by removing the plug from the RJ31X wall 
    jack. We recommend that your certified installer demonstrate disconnecting the phones on installation of the 
    system. Do not disconnect the phone connection inside the control/communicator. Doing so will result in the loss 
    of your phone lines. If the regular phone works correctly after the control/communicator has been disconnected 
    from the phone lines, the control/communicator has a problem and should be returned for repair. If upon 
    disconnection of the control/communicator, there is still a problem on the line, notify the telephone company that it 
    has a problem and request prompt repair service. The user may not under any circumstances (in or out of 
    warranty) attempt any service or repairs to the system. It must be returned to the factory or an authorized service 
    agency for all repairs. 
    This control unit was manufactured under rigid quality standards and complies with all UL requirements 
    for its intended use. Maintenance is best performed by your installing company with trained service 
    personnel. 
     O560 DECLARATION OF CONFORMITY 
    Application of Council Directives 98/482/EC, 89/336/EEC, 73/23/EEC 
    Standards to which conformity is declared: 
    ETS 300 001:1997  EN50081-1  EN 50130-4:1995  EN 60950:1998 
    Intended use:  Alarm system, analogue subscriber interface to PSTN 
    Restrictions: None  
    EMC environment:   RESIDENTIAL, COMMERCIAL AND LIGHT INDUSTRY 
    Manufacturer:  Honeywell International Inc. 
    Address:  165 Eileen Way, Syosset NY 11791, USA 
    Customer support:  Contact your local distributor  
    						
    							 
    – 27 – 
    System Limitations 
    While this system is an advanced-design security system, it does not offer guaranteed protection 
    against burglary, fire, or other emergency. Any alarm system, whether commercial or 
    residential, is subject to compromise or failure to warn for a variety of reasons.  For example: 
    • Intruders may gain access through unprotected openings or have the technical sophistication 
    to bypass an alarm sensor or disconnect an alarm warning device. 
    • Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing 
    devices will not work without batteries or if the batteries are not put in properly.  Devices 
    powered solely by a main power supply will not work if their main power supply is cut off for 
    any reason, however briefly. 
    • Signals sent by wireless transmitters may be blocked or reflected by metal before they reach 
    the alarm receiver.  Even if the signal path has been recently checked during a weekly test, 
    blockage can occur if a metal object is moved into the path. 
    • A user may not be able to reach a panic or emergency button quickly enough. 
    • While smoke detectors have played a key role in reducing residential fire deaths, they may 
    not activate or provide early warning for a variety of reasons in as many as 35 percent of all 
    fires.  Some of the reasons smoke detectors used in conjunction with the system may not work 
    are as follows:  Smoke detectors may not sense fires that start where smoke cannot reach the 
    detectors, such as in chimneys, in walls, on roofs, or on the other side of closed doors.  Smoke 
    detectors also may not sense a fire on another level of a residence or building.  A second-floor 
    detector, for example, may not sense a first-floor or basement fire.  Moreover, smoke detectors 
    have sensing limitations. No smoke detector can sense every kind of fire every time.  In 
    general, detectors may not always warn about fires caused by carelessness and safety hazards 
    like smoking in bed, violent explosions, escaping gas, improper storage of flammable 
    materials, overloaded electrical circuits, children playing with matches, or arson.  Depending 
    on the nature of the fire and/or the location of the smoke detectors, the detector, even if it 
    operates as anticipated, may not provide sufficient warning to allow all occupants to escape in 
    time to prevent injury or death. 
    • A passive infrared motion detector can detect intrusion only within the designed ranges as 
    diagrammed in its installation manual.  Passive infrared detectors do not provide volumetric 
    area protection.  They do create multiple beams of protection, and intrusion can be detected 
    only in unobstructed areas covered by the beams.  They cannot detect motion or intrusion that 
    takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or 
    windows.  Mechanical tampering, masking, painting, or spraying of any material on the 
    mirrors, windows, or any part of the optical system can reduce their detection ability.  Passive 
    infrared detectors sense changes in temperature; however, as the ambient temperature of the 
    protected area approaches the temperature range of 90º to 104º Fahrenheit (32º to 40º 
    Celsius), the detection performance can decrease.  
    						
    							– 28 – 
    System Limitations (cont’d) 
    • Alarm warning devices such as sirens, bells, or horns may not alert people or wake up 
    sleepers who are located on the other side of closed or partly open doors.  If warning devices 
    sound on a different level of the residence from the bedrooms, then they are less likely to 
    waken or alert people inside the bedrooms.  Even persons who are awake may not hear the 
    warning if the alarm is muffled by noise from a stereo, radio, air conditioner, other 
    appliances, or by passing traffic.  Finally, alarm warning devices, however loud, may not warn 
    hearing-impaired people or waken deep sleepers. 
    • Telephone lines needed to transmit alarm signals from a premises to a central monitoring 
    station may be out of service.  Telephone lines are also subject to compromise by sophisticated 
    intruders. 
    • However, even if the system responds to the emergency as intended, occupants may have 
    insufficient time to protect themselves from the emergency situation.  In the case of a 
    monitored alarm system, authorities may not respond appropriately. 
    • This equipment, like other electrical devices, is subject to component failure.  Even though 
    this equipment is designed to last as long as 20 years, the electronic components could fail at 
    any time. 
    The most common cause of an alarm system not functioning when an intrusion or fire occurs is 
    inadequate maintenance.  This alarm system should be tested weekly to make sure all sensors 
    are working properly. 
    Installing an alarm system may make one eligible for lower insurance rates, but an alarm 
    system is not a substitute for insurance. Homeowners, property owners, and renters should 
    continue to act prudently in protecting themselves and continue to insure their lives and 
    property. 
    We continue to develop new and improved protection devices.  Users of alarm systems owe it to 
    themselves and their loved ones to learn about these developments.  
    						
    							 
    – 29 – 
    Glossary 
    AC/LB LED:  Yellow LED that, when lit, indicates the system is running on 
    electricity; when not lit, indicates the system is running on the backup 
    battery. 
    ALARM:  Sound from keypad or other horn/siren indicates a burglar alarm, 
    fire alarm, or other condition you should be alerted to. 
    ARM LED:  Red LED in the upper portion of the keypad.  When lit, some 
    part of the burglar alarm system is armed; when not lit, the burglary portion 
    of the system is disarmed. 
    ARM-STAY:  A system setting that arm the perimeter protection of the 
    building but allows movement throughout the inside.  
    ARMED/DISARMED:  These terms refer to the burglary portion of your 
    security system. There are several operation levels that allow you to protect 
    part of your premises while you remain inside.  Fire and other emergency and 
    environmental sensors are always active and ready, and are not affected in 
    any way by arming or disarming the burglary portion of your security system. 
    AWAY:  A system setting that protects the premises while it is unoccupied. 
    All burglary sensors are active. 
    BURGLARY/FIRE:  The two major functions of a security system.  Fire 
    protection is always armed and cannot be disarmed.  The burglary sensors 
    protect against unauthorized entry into your premises.  The burglary 
    protection can be armed and disarmed and programmed for special levels of 
    access and notification. 
    BYPASS FEATURE:  The Bypass feature allows you to exclude a selected 
    zone or zones from the burglar alarm protection.  
    BYPASS KEY:  Keypad key used to activate the Bypass feature. 
    CENTRAL STATION:  Signal monitoring center contacted by your security 
    system over the telephone and/or other communication channels when 
    alarms are activated if your system is programmed to communicate alarms 
    off site.  The central station will follow their procedures and your instructions 
    for contacting the proper authorities when a signal is received.   
    						
    							– 30 – 
    Glossary (cont’d) 
    CHIME FEATURE:  An optional feature that causes the keypad to chime for 
    1 second when selected doors are opened when the burglary protection is off 
    or disarmed.  Once programmed by your installer, you can turn Chime on and 
    off by pressing [#], [6]. 
    DURESS:  Duress is a system feature that you may have programmed into 
    your system.  If someone should force you to disarm your system, you would 
    use the special Duress User Code.  This code disarms the system and sends a 
    silent duress emergency signal to the central station so personnel can 
    respond appropriately.  
    ENTRY DELAY:  The period of time allowed between opening a designated 
    entry/exit door and disarming the alarm system before the system registers 
    an alarm condition.  This time is determined at the time of installation.  Your 
    system supports two entry times, allowing you to have a different length of 
    time for different doors. 
    EXIT DELAY:  The period of time allowed between arming the system and 
    leaving through a designated exit/entry door.  This is determined at the time 
    of installation. 
    INTERIOR ZONE:  A group of points that protects the interior of your 
    premises.  You may want to arm the perimeter portion of your system while 
    leaving the interior zones disarmed, allowing you to move freely inside, 
    opening interior doors and passing by motion detectors without causing an 
    alarm. 
    KEYPAD:  A keypad is your link to your system.  It displays alarm and 
    trouble messages, shows faulted zones, and allows you to arm and disarm the 
    system by using the keys.  Your system has one or more keypads. 
    ON/OFF:  See ARMED/DISARMED 
    PANIC BUTTON:  A pushbutton that allows you to signal the central 
    station that you need immediate assistance.  Your system has programmable 
    Keypad Send Help Alerts that can also serve as Panic buttons. 
    PERIMETER ZONE:  A group of points that protects the exterior of your 
    premises such as your outside doors and windows.   
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell control panel OMNI 408408EU User Manual