    							PRODUCT DATA
    68- 0223-2® U.S. Registered Trademark
    Copyright © 2001 Honeywell   All Rights Reserved 
    TZ-3 TotalZone® Zone Control Panel
    APPLICATION
    The TZ-3 TotalZone Zone Control Panel controls single-stage, 
    multi-sta
    ge, conventional or heat pump heat/cool equipment. 
    It controls 2 or 3 zones, and is expandable up to 30 zones with 
    optional TotalZone® Add-A-Zone™ Zone Control Panel.
    FEATURES
    • Up to three stages heat and two stages cooling can be 
    controlled by thermostat or built-in timer, based on the 
    number of zones calling.
     Controls up to three zones and can be expanded with 
    TotalZone Add-A-Zone zone Control Panel for up to 30 
    zones.
     Uses virtually any Honeywell four-wire, single-stage, 
    multi-stage, or Trol-A-Temp heat pump thermostat.
     Zone-A-Lone central setback feature.
     Purge timer protects equipment between calls for heat 
    or cool with choice of continually on or equipment 
    controlled fan.
     System and zone damper LEDs indicate system and 
    damper status.
     Individual zone fan control.
     Optional Discharge Air Temperature Sensor for 
    capacity control with adjustable high and low limits.
     Thermal circuit breaker protects panel and transformer 
    from damage if miswired.
    For Internet access: www.trolatem
    p.com or 
    www.hone
    ywell.com/yourhome/zoning/zoning_home.htm
    For technical su
    pport, call 1-800-TAT-Temp (1-800-828-8367).
    To download Zonin
    g literature: http://hbctechlit.honeywell.com
    Contents
    Application ......................................................................... 1
    Features ............................................................................ 1
    S
    pecifications .................................................................... 2
    Installation ......................................................................... 4
    Startu
    p and Checkout........................................................ 9
    Operation........................................................................... 10
    Troubleshooting................................................................. 13 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 2
    SPECIFICATIONS
    Electrical:  
    24 Vac, 60 Hz.
    Dimensions:   
    See Fi
    g. 1.
    Mounting:  
    Mounts with three screws 
    (provided) through 
    holes in cabinet back
    Wiring:  
    18-
    gauge wire for all equipment and system 
    connections
    Wiring Connections:
    Thermostat: W2, L, G, Y, R, W
    Dam
    pers: M6 (Closed); M4 (Open); M1 (Common) 
    ZoneMax TL, TL
    Zone-A-Lone: OC,OC.
    Transformer: TR1 
    (hot), TR2 (common).
    E
    quipment: Y2, Y1, O, R, G, B, W1, E, W2, W3.
    Thermostats (See Table 1):
    Conventional 4-wire 
    (R,W,Y,G) thermostats. 
    Manual or automatic changeover switching subbase for 
    each zone thermostat.
    Multi-sta
    ge or select heat pump thermostats can be used.Fig. 1. TZ-3 dimensions in in. (mm).
    Table 1.  Recommended Thermostats.
    aHeat pump thermostat with single Y first-stage terminals. See Heat Pump Thermostats with Single Y Output section and Fig. 3.bMulti-stage and heat pump thermostats are not required to control multi-stage and heat pump systems with TotalZone. They are 
    used only when second stage or emergency heat control from the zone thermostat is needed.
    Dampers (See Table 2):
    Five dam
    pers maximum connected to each panel.
    Use SDCR for additional dam
    pers required on one zone.
    Use isolation relay when CDO-32 Damper or ML6161 
    Motor Actuator is used (see Fig. 10). 
    Dam
    pers are connected to M1, M4, and M6 (see Fig. 6-10 
    for hookups).
    Accessories: 
    For re
    quired accessories, see Table 3.
    1-5/8
    (41) 7-5/8 (195)
    7-13/16
    (198)
    M19062
    HEATCOOL
    PURGE
    FANEM. HT.ZONE 1ZONE 2ZONE 3
       ®
    System Trol-A-Temp Logo Honeywell Logo
    Single StageNon-ProgrammableProgrammableNon-ProgrammableProgrammable
    T87F3715/Q539A1436
    T87F3707Q539A1428T8601D2027
    T8131C1020T87F1859/Q539A1014
    Q87F4010/Q539A4026
    T8400C1016
    T8400C1040T8600D2069
    T8600D2028
    T8601D2019
    T8602D2018
    T8602D2000
    T8000C1002
    T8000C1010
    Heat Pumpa—T8611G2051aY594R1243a
    Y594G1252a
    T8411R1002
    T8411R1028
    T8011R1006
    T8011R1014
    Multi-Stageb——Y594D1347bT8624D2004a
    T8624D2012b
    M1Common
    M4Power Open
    M6Power Close 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    3 68-0223-2
    Table 2.  Recommended Dampers.
    Table 3.  Required Accessories (Not Supplied With Panel). Honeywell Damper Type Round Rectangular
    Power-open/power-closedMARDIOBD
    AOBD
    AOBD-BM
    CDO-51
    Spring-open/power-closedARDZDB
    ZDS
    Accessory DescriptionBypass Rating
    (cfm)
    40 VA transformerAT140D1046 (PMT-40)—
    Capacity protectorZMS, DATS (C7735A1000)—
    Round static pressure regulator 
    dam
    per
    7 SPRD
    8 SPRD
    9 SPRD
    10 SPRD
    12 SPRD
    14 SPRD
    16 SPRD
    18 SPRD300 
    400 
    600 
    750 
    1200 
    1800 
    2400 
    3200
    Rectangular static pressure regulator 
    damper12 x 8 SPRD
    12 x 10 SPRD
    12 x 12 SPRD
    20 x 8 SPRD
    20 x 10 SPRD
    20 x 12 SPRD1000 
    1200 
    1400 
    1600 
    2000 
    3000  
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 4
    INSTALLATION
    Mounting
    CAUTION
    Equipment Damage Hazard.   
    Do not mount TZ-3 inside HVAC equipment
    Mount onl
    y on wall or on cold air return
    1.
    Mount the thermostats in each zone of the livin
    g space 
    usin
    g the installation instructions provided with each 
    thermostat.
    2.
    Mount the dam
    pers in the ductwork using the installa-
    tion instructions 
    provided with each damper.
    3.
    Mount the TZ-3 zone panel near the HVAC equipment; 
    locate it on a wall or on the cold-air return. See Fig. 2.
    4.
    Level the TZ-3 for a
    ppearance only.
    Wiring
    CAUTION
    Voltage Hazard. 
    Can cause electrical shock or equipment damage.
    Disconnect 
    power before continuing installation.
    Wirin
    g must comply with applicable codes, ordinances, and 
    regulations.
    1.
    Connect thermostats as shown in Fi
    g. 3-5. 
    2.
    Connect dampers as shown in Fig. 6-10.
    3.
    Connect the Discharge Air Temperature Sensor (not 
    su
    pplied) to the TL terminals.The wires are not polar-
    ized. See Fig.12.
    4.
    Connect Add-A-Zone panels (if used) to the AZ1 and 
    AZ2 terminals. The AZ1 terminal on the TZ-3 must be 
    wired to the AZ1 terminal on the TAZ 
    panel. Similarly, 
    the AZ2 terminal must be wired on the TZ-3 to the AZ2 
    on the TAZ.  See Fi
    g. 13.
    5.
    Connect the HVAC equipment to the EQUIP terminals 
    on the panel.  See Fig. 14-17.
    6.
    Connect a 40 VA, 24 volt transformer to TR1 
    (hot) and 
    TR2 (common). This must be a dedicated transformer 
    and any additional TAZ boards also each require a 
    transformer. See Fi
    g. 11.Fig. 2. TZ-3 mounting location.
    Wiring Diagrams (Fig. 3-17)
    Conventional Thermostats
    The C (common) terminal is used only on thermostats that 
    require a common (for example:T8601). See Fig. 3. Wire the 
    W2 terminal on a multi-sta
    ge thermostat (for example: T8624) 
    to the W2 on the panel for second stage control from the 
    thermostat. If the thermostat has a Y2 terminal, do not 
    connect it to the 
    panel.
    Fig. 3. Typical single-stage thermostat wiring.
    Heat Pump Thermostats
    Select a heat pump thermostat from Table 1. If the thermostat 
    selected has a se
    parate Y1 and W1, see Fig. 4. When using 
    the thermostat to control the second stage of heat (W2), set 
    DIP switch 5 to On, and DIP switch 1 to Off. Set both DIP 
    switches 6 and 7  to Off. 
    M19063
    WATER 
    HEATERT2-3ELECTRONIC AIR CLEANER
    RETURN
    AIR
    T2-3
    OPTIONAL
    LOCATION
    FURNACE 
    OR BOILER
    HIGH
     EFFICIENCY
    AIR CLEANER
    LW2GYRWM6
    GY R WC
    M4M1THERMOSTAT ZONE CONNECTIONS ON PANEL
    ZONE THERMOSTAT
    M19064
    MOTOR 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    5 68-0223-2
    Fig. 4. Heat pump thermostat with separate Y1 and W1 
    terminals and multi-stage thermostat wiring.
    If the thermostat selected has a sin
    gle Y terminal, see Fig. 5. 
    Select a sin
    gle Y thermostat for each zone. See Table 1. 
    Set DIP switch 6 or 7 
    (not both) to the On position. Set switch 
    6 to On when B on the thermostat is wired to W on the 
    panel. 
    Set switch 7 to On when 0 on the thermostat is wired to W on 
    the 
    panel.
    When usin
    g the zone thermostat to control the second stage 
    of heat (W2), set DIP switch 5 to On, and DIP switch 1 to Off.
    Fig. 5. Heat pump thermostat with single Y thermostat 
    wiring.
    AOBD Dampers
    Wire the  AOBD, AOBD-BM and IOBD Dampers to the panel 
    as shown in Fig. 6. See Fig. 7 when using two dampers on 
    one  zone. When three or more dam
    pers are controlled on 
    one zone, a slave damper control relay (SDCR) is required.Fig. 6. AOBD single damper wiring.
    Fig. 7. AOBD multiple damper wiring.
    ARD or ZD Dampers
    Wire the ARD or ZD Damper to the panel as shown in Fig. 8. 
    Multiple dampers can be wired in parallel. When ARD or ZD 
    damper is used, the zone LEDs switch directly from red to 
    green (never amber). 
    Fig. 8. ARD or ZD Damper wiring.
    MARD or CDO-51 Dampers
    Wire the MARD or CDO-51 Damper to the panel as shown in 
    Fig. 9. These are floating control modulating dampers, but are  
    controlled as two-position dampers on the TZ-3 panel.Two 
    dam
    pers can be wired in parallel.                                       
    LW2GYRWM6
    G L W2 E Y1 R W1 C/X
    M4M1THERMOSTAT ZONE CONNECTIONS ON PANEL
    ZONE THERMOSTAT
    M19065
    MOTOR
    LGYRWM6
    E W2 L G Y R O C/X
    M4M1W2THERMOSTAT ZONE CONNECTIONS ON PANEL
    HEAT PUMP ZONE THERMOSTAT
    M19066
    MOTOR
    4M6 M4 M156
    123Z
    X
    DAMPER MOTOR FIELD JUMPERM19067
    MOTOR TERMINALS
    4M6 M4 M156
    123
    DAMPER MOTORSM19068
    MOTOR TERMINALS
    456
    123Z
    XZ
    X
    FIELD JUMPER
    M6 M4 M1
    M19037A
    DAMPER TERMINALS
    ON PANEL
    POWER CLOSE
    SPRING OPEN
    MODEL ARD, ZDS, ZDB 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 6
    Fig. 9. MARD and CDO-51 Damper wiring.
    ML6161 Motor Actuator
    When the ML6161 Motor Actuator is used, wire as shown in 
    Fig. 10. Wire the R8222 relay to prevent the damper LED from 
    constantl
    y lighting amber. 
    Fig. 10. ML6161 Damper Motor Actuator wiring.
    Transformer
    Wire the transformer to the panel as shown in Fig. 11.
    NOTE: If the installation includes an Add-A-Zone 
    panel, see 
    the TotalZone Add-A-Zone Panels section.
    Fig. 11. Transformer wiring.
    Discharge Air Temperature Sensor
    Wire the C7735A or the ZMS to the panel as shown in Fig. 12.Fig. 12. Discharge Air Temperature Sensor (C7735A or 
    ZMS) wiring.
    Add-A-Zone Panel
    Wire the Add-A-Zone (TA Z) Panel to the TotalZone (TZ-3) 
    Panel as shown in Fi
    g. 13. Up to nine TAZ Panels can be 
    wired to one TZ-3 panel. See Fig. 13.
    Use 18-
    gauge thermostat wire for runs up to a maximum of 
    500 feet. Keep these wires at least 12 in. from line voltage 
    wiring and equipment; otherwise, use shielded cable wiring. 
    IMPORTANT: 
    When multiple panels are used, it is important that 
    the transformers be in-phase. Check the phasing by 
    measuring for 24V across the TR2 transformer termi-
    nals on each panel. There should be 0 Vac. If not, 
    reverse the TR1and TR2 transformer wires on one of 
    the panels and recheck.
    Fig. 13. TotalZone Add-A-Zone wiring.
    Conventional Equipment
    Wire the heating and cooling equipment to the equipment 
    terminals on the TZ-3 Panel as shown in Fig. 14.
    Electric Furnaces: Set DIP switch 8 to On to ener
    gize the fan 
    with a call for heat.
    H
    ydro-Air: Wire the zone valve or circulator relay to the W1 
    equipment terminal. (If the circulator relay has powered 
    terminals, use an isolation rela
    y.)  Set DIP switch 8 to On to 
    energize the fan with a call for heat.
    Oil Heat: Wire an isolation rela
    y on the W equipment wire to 
    isolate the oil primary from the panel.
    COM / M1
    CL / M6
    OP / M4MARD OR CDO-51 ZONE CONTROL PANEL
    DAMPER TERMINALS
    M19069
    M6M4M1
    COM / M1
    CL / M6
    OP / M4ML6161
    R8222 RELAY ZONE CONTROL PANEL
    DAMPER TERMINALS
    M19070
    M6M4M1ZONE
    THERMOSTAT
    TERMINAL
    R
    C 24 VOLT
    TRANSFORMER
    R
    TR1 TR2
    24V, 40 VA
    TRANSFORMER
    MODEL AT140D1046
    M19071
    TL TL ZMS
    SENSORM19072
    TO ADDITIONAL
    TAZ PANELSM19073
    AZ2 AZ1
    TA Z AZ2 AZ1
    TA Z AZ2 AZ1
    TZ-3 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    7 68-0223-2
    Multi-Stage: Wire the equipment as shown in Fig. 14 using the 
    W2 terminal for second stage of heat and the W3 terminal for 
    third sta
    ge of heat. Wire the Y2 for second stage of cooling.
    Fig. 14. Heating and cooling equipment.
    Heat Pump Equipment
    Wire the heat pump to the equipment terminals on the panel 
    as shown in Fi
    g. 15. Refer to manufacturer’s instructions for 
    additional wiring instructions and substitute the TZ-3 
    equipment terminals for the thermostat terminals shown.
    IMPORTANT
    Some heat pump manufacturers (such as York and 
    Trane) use the B terminal as the transformer com-
    mon. Do not connect the common from the equip-
    ment to the zone control panel.
    Two - speed Compressor: Wire the second stage compressor 
    to both Y2 and W2. Wire the auxiliary heat to W3. Remove the 
    two-stage emergency heat jumper and install a jumper from 
    W3 to E.
    Fossil Fuel Kits with Heat Pum
    ps: Wire these systems like 
    Fi
    g.15 but use the manufacturer’s fossil fuel kit. Wire the 
    Trane XL 1800 and the TAYPLUS 103 as shown in Fig. 16. 
    The recommended thermostat is theT8611G2051.
    CGY RWZONE 1
    THERMOSTAT
    24V, 40 VA
    TRANSFORMER
    M19074
    W2
    W3 E W1
    B
    G
    R
    O
    Y1
    Y2 TL TL
    2 STAGE
    EM HEAT
    MODEL TZ-3
    CR OC OC
    TR1 TR2
    HEAT
    TO TERMINAL AZ1 ON TAZ (IF USED)
    OUTDOOR CONDENSING UNIT
    HVAC CONTROLS
    ZoneMAX
    Add-A-ZoneTM
    COOLPURGEFA NEM.HTZONE 1ZONE 2ZONE 3
    BOOT
    OVERRIDE
    PURGE
    REMOTE OCCUPIED/
    UNOCCUPIED CONTROL
    (CLOSE IN UNOCCUPIED)
    ON
    OFF
    Emergency Heat
    ON
    1
    L W2 G Y R W M6 M4M1THERMOSTAT MOTOR
    2345678
    OCCUP
    REMOTE
    UNOCCUP
    Zone-A-Lone
    C
    123X 456ZGY RWZONE 3
    THERMOSTAT
    MODEL ARD  OR 
    ZD DAMPERS
    ZONE 2
    L W2 G Y R W M6 M4M1THERMOSTAT MOTORZONE 1
    L W2 G Y R W M6 M4M1THERMOSTAT MOTORZONE 3
    CGY RWZONE 2
    THERMOSTAT
    123X 456Z
    OPPOSED BLADE DAMPER MOTORS
    AZ1 AZ2TO TERMINAL AZ2 ON TAZ (IF USED)
    ZoneMAX   
    TEMPERATURE
    SENSORTM
    15 MINUTES
    10 MINUTES
    5 MINUTES20 MINUTES
    25 MINUTES
    30 MINUTES
    STAGE TIMER
    130  F
    MAXIMUM
    TEMPERATURE
    120  F110  F140  F150  F160  F
    W
    W2 24V TRANSFORMER
    FAN RELAY
    HEAT RELAYR
    Y
    Y2
    C
    G 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 8
    Fig. 15. Heat pump with auxiliary heat wiring.
    .
    Fig. 16. Trane XL 1800 with TAYPLUS 103 in restricted mode wiring.
    Water Source Heat Pumps
    Wire the equipment, as applicable, to the TZ-3 as shown in Fi
    g. 17. Turn DIP switch number 8 to On for fan on in heat. 
    Remove the two-sta
    ge emergency heat jumper.
    W2
    W3
    M19075
    E W1
    W2E
    B G
    R
    24V TRANSFORMER
    FAN RELAYREVERSING 
    VALVE (COOL)
    EMERGENCY
    HEATING RELAY
    2 STAGE
    HEATING RELAY
    HEAT PUMP CONTROLSTZ-3
    PA N E L
    EQUIP RCO
    GO Y1
    Y2
    COMPRESSOR
    RELAY
    Y
    OUTDOOR CONDENSING UNIT
    YER W2 W3
    T
    L
    12
    31
    4
    K2 ODT
    5 3G O/B C
    T8611G2051 TRANE XL1800
    CONDENSING
    UNIT VARIABLE
    SPEED
    GAS
    FURNACE TAYPLUS 103
    NOTES:
    M19076
    W2
    W3 E W1
    B
    G
    R
    O
    Y1
    Y2 TL TL
    2 STAGE
    EM HEAT
    MODEL TZ-3
    HEAT
    ZoneMAX
    Add-A-ZoneTM
    COOLPURGEFA NEM.HTZONE 1
    OVERRIDE
    PURGE
    ON
    1
    L W2 G Y R W M6 M4M1THERMOSTAT MOTOR
    2345678
    ZONE 2
    L W2 G Y R W M6 M4M1THERMOSTAT MOTOR
    ZONE 1
    AZ1 AZ215 MINUTES
    10 MINUTES
    5 MINUTES20 MINUTES
    25 MINUTES
    30 MINUTES
    STAGE TIMER
    130  F
    MAXIMUM
    TEMPERATURE
    120  F110  F140  F150  F160  F
    1. DIP SWITCHES 6 OFF AND 7 ON.
    2. DIP SWITCHES 1 OFF AND 5 ON.
    3. T8011R OR T8411R MAY ALSO BE USED.
    4. REMOVE THE 2 STAGE EM HEAT JUMPER.
    F
    Y2
    R
    B
    Y1
    O
    X2
    G
    W2
    W1
    B
    O
    Y
    YLO
    BK
    R
    Y3X3G3
    Y2G1
    X2Y1BW1 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    9 68-0223-2
    Waterfurnace: Wire this system to the panel as shown in Fig. 
    17 except use two isolation relays on compressor wires W1, 
    Y1 and  W2, Y2.
    Fig. 17. Water source heat pump wiring.
    STARTUP AND CHECKOUT
    After the installation is complete, verify correct operation as 
    follows:
    1.
    Place the Em Heat switch in the Off 
    (down) position.
    2.
    Place the Zone-A-Lone switch in the Occup/Remote (up) position.
    3.
    Ver i f
    y that the DIP switches are set correctly. See 
    Sequence of Operation section and Table 6 for correct 
    confi
    guration. 
    4.
    Power up the TZ-3 and set the thermostats so no zones 
    are calling. The board then enters the Purge mode 
    where all dam
    pers open and the fan operates for two or 
    three and one-half minutes (configurable). (If  there is 
    no Discharge Air Temperature Sensor connected to the 
    panel, the Idle LED flashes seven times before entering 
    the Purge mode.) Then the Idle LED turns red and each 
    damper LED turns green.
    5.
    Set  zone one thermostat to heat and raise the set
    point 
    to call for heat. Verify that the heat LED is red and zone 
    one damper remains green while the other damper LED 
    turns red.
    6.
    Raise zone two set
    point to call for heat. Lower zone one 
    set
    point to stop the call for heat to that zone. Verify that 
    zone one LED turns red (it may be amber while moving) 
    and zone two LED turns green.
    7.
    Re
    peat for zone three.
    8.
    Alternately, lower the setpoint to call for cooling.Verify 
    that the green cool LED illuminates.
    W2
    W3
    M19077
    E W1
    O
    GW
    B G
    R2ND STAGE COMPRESSOR1ST STAGE COMPRESSOR
    AUXILIARY HEATY1 C
    Y2
    O Y1
    Y2
    R
    2 STAGE
    EM. HT. 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 10
    OPERATION
    Sequence of Operation
    On a call for heating or cooling, the zone damper stays open 
    to the calling zone, and the dampers close to the zones that 
    are not callin
    g. The TZ-3 panel brings on the heating or 
    cooling and conditioned air is delivered to the calling zone 
    until that zone is satisfied. When the call is satisfied, the 
    s
    ystem enters the Purge mode. This holds open the damper 
    of the last zone calling and purges into that zone. The purge 
    time can be set to three and one-half or two minutes. After 
    purge, all dampers return to the Open position.
    An
    y zone thermostat can call for heating or cooling. If there 
    are co-existin
    g calls for heat and cool, the panel first accepts 
    the first call. Once that call is satisfied, or a maximum of 20 
    minutes has ela
    psed, the panel switches to allow the opposite 
    call.
    On a call for heatin
    g or cooling, the heat LED illuminates red 
    or the cool LED illuminates 
    green. The zone damper LED 
    turns green for the zone calling, and the dampers in the zones 
    not calling close and turn red.  As AOBD dampers move, the 
    LEDs turn amber.
    Purge Mode
    At the end of every call for heat or cool, the panel enters a 
    Purge mode that holds open the calling zone damper for three 
    and one-half or two minutes. During this time, the panel or  the 
    HVAC e
    quipment can operate the fan. Purge also serves as a 
    time delay to prevent short cycling of the heating and cooling 
    equipment after each call. Purge LED lights to signal that the 
    s
    ystem is in the Purge mode. Pressing the purge override 
    button for two seconds overrides the Purge mode. Unless 
    there is a new call for heat or cool during the Purge mode, all 
    dam
    pers are moved to the Open position at the end of  purge.
    Individual Zone Fan Control
    When all zones are satisfied, the Fan switch of each 
    thermostat controls the fan operation for that zone. When the 
    Fan switch is in the On 
    position, the fan is energized, and the 
    dampers close to zones where the Fan switch is in the Auto position.  If there is a call for heat or cool during this time, the 
    circulation mode ceases, and the heat or cool call is honored.  
    When the zone callin
    g is satisfied, the circulation call 
    resumes.
    Single and Multi-Stage Operation
    The panel can control up to three stages of heating and two 
    stages of cooling. The first stage is energized by the 
    thermostat. The second sta
    ge of heating is brought on by the 
    thermostat, timer, or number of zones calling. The third stage 
    of heating is brought on by the timer or number of zones 
    callin
    g. The second stage of cooling is brought on by the timer 
    or number of zones calling.
    The followin
    g instructions show how to configure the panel for 
    stage control.
    If the e
    quipment is single stage, set the DIP switches as 
    follows:
    1st Stage by Thermostat, 2nd and 3rd Stages by 
    Timer (Fig. 18)
    The thermostat controls the first stage of heat or cool. If the 
    call is not satisfied b
    y the first stage within the time set on the 
    timer, the panel energizes the second stage. If the call for heat 
    is not satisfied by the second stage within the time set on the 
    timer, the 
    panel brings on the third stage. 
    Set the DIP switches as follows:
    Fig. 18. Stage timer.
    1st Stage by Thermostat, 2nd Stage Heat by 
    Thermostat
    The thermostat controls the first stage of heat or cool and the 
    second stage of heat. The timer controls the second stage of 
    cool and third sta
    ge of heat. If the first and second stages 
    combined do not satisfy the heat call within the time specified 
    on the timer, the panel brings on the third stage of heat. 
    Set the DIP switches as follows:
    DIP Switch 
    Number
    StatusPurge Time
    3Off3.5 minutes
    3On2 minutes
    DIP Switch 
    NumberStatusFan Control
    4OffPanel control of fan 
    in purge
    4OnHVAC control of fan 
    in 
    purge
    DIP Switch NumberStatus
    1Off
    5Off
    DIP Switch NumberStatus
    1Off
    5Off
    15 MINUTES
    10 MINUTES
    5 MINUTES20 MINUTES
    25 MINUTES
    30 MINUTES
    STAGE TIMER
    M19078 
    						