Home > Honeywell > Thermostat > Honeywell Thermostat T8112d1005 (1) Manual

Honeywell Thermostat T8112d1005 (1) Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Thermostat T8112d1005 (1) Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							PRODUCT DATA
    ¨ U.S. Registered Trademark
    Copyright © 1998 Honeywell Inc.   ¥   All Rights Reserved
    T8112D
    Programmable Thermostat
    GENERAL
    The T8112D Programmable Thermostat provides energy
    savings for single-stage heating and cooling applications
    while providing reliable, precise temperature control.
    FEATURES
    ¥ HEAT-OFF-COOL System switch.
    ¥ AUTO-ON Fan switch.
    ¥ Separate programs for weekdays and weekends
    (5 day/2 day).
    ¥ Digital LCD display.
    ¥ Easy to program and install.
    ¥ Precise temperature control.
    ¥ Four daily energy saving programs.
    ¥ Compatible with most 24 Vac standing pilot, gas
    electronic ignition, oil or central electric systems.
    ¥ Requires two AA alkaline batteries.
    ¥ LCD flashes 
    bAt Lo indicating low battery power.
    ¥ Isolated heating/cooling circuits.
    Contents
    General ............................................................................... 1
    Features .............................................................................. 1
    Specifications ...................................................................... 2
    Ordering Information ........................................................... 2
    Installation ........................................................................... 3
    Programming the Thermostat ............................................. 6
    Checkout and Settings ........................................................ 7
    Troubleshooting ................................................................... 8
    68-0206 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-02062
    SPECIFICATIONS
    IMPORTANT
    The specifications given in this publication do notinclude normal manufacturing tolerances; therefore,an individual unit might not exactly match the listed
    specifications. Also, this product is tested andcalibrated under closely controlled conditions, andsome minor differences in performance can be
    expected if those conditions are changed.
    Model:
    T8112D Thermostat: Provides electronic programmable
    control for 24 to 30 Vac heating and cooling systems.
    Programming Keys:
    Eight program keys.
    Electrical Rating:
    Battery operated (2 AA alkaline batteries).
    System and Fan Ratings: 1.2A run; 7.5A inrush.
    Total cooling and fan load not to exceed 1.2A.
    Dimensions:
    See Fig. 1. Mounting:
    Mounts on mounting plate directly on wall. Mounting screws
    and wall anchors provided.
    Setpoint Range:
    45
    °F to 88 °F (7 °C to 31 °C).
    Operating Ambient Temperature Range:
    40 °F to 110 °F (4 °C to 43 °C).
    Shipping Temperature  Range:
     -20 °F to 120 °F (-29 °C to -49 °C).
    Temperature Display:
    Fixed or field selectable.
    Operating Relative Humidity:
    5 to 90 percent RH; noncondensing.
    Time Indication:
    12 hour with AM, PM indication.
    Cycles Per Hour Adjustment: Heating: Field adjustable to 3, 6, or 9 cph  ±10 percent.
    Cooling: Factory set at 3 cph  ±10 percent (not field
    adjustable).
    Calibration:
    Thermostat and thermometer self-calibrating to  ±1.25 °F.
    M9349
    1(25)
    1-1/4     
     (32)
    4
    (102) 3/4 (19)
    6-7/8 (175)
    ORDERING INFORMATION
    When purchasing replacement and modernization products from your TRADELINE¨ wholesaler or your distributor, refer to the
    TRADELINE¨ Catalog or price sheets for complete ordering information, or specify:
    1. Model Number.
    2. Accessories, as desired.
    If you have additional questions, need further information, or would like to comment on our products or services, please write  or
    phone: 1. Your local Honeywell Home and Building Control Sales Office (check white pages of phone directory).
    2.Home and Building Control Customer Relations Honeywell, 18
     85 Douglas Drive North
    
    Minneapolis, Minnesota 55422-4386 
    In CanadaÑHoneywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and
    Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexi co,
    Netherlands, Spain, Taiwan, United Kingdom, U.S.A. Fig. 1. T8112 dimensions in in. (mm). 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-0206
    3
    INSTALLATION
    When Installing this ProductÉ
    1. Read these instructions carefully. Failure to follow the
    instructions can damage the product or cause a
    hazardous condition.
    2. Check the ratings given in the instructions and on the
    product and in the compatibility chart (Table 1) to make
    sure the product is suitable for your application.
    3. Installer must be a trained, experienced service
    technician.
    4. After installation is complete, check out product
    operation as provided in these instructions.
    Compatibility
    Check Table 1 to make sure the thermostat is compatible with
    the intended system.
    Table 1. Compatibility Chart.
    aCompatible with 2-wire Honeywell zone valves.
    All system types:
    Not compatible with any 120/240 volt circuit.
    Not designed for steam or gravity systems.
    Not compatible with 2-wire White Rodgers no. 1361 zone
    valves.
    Isolating relay required for 3-wire thermostats for zone valves.
    CAUTION
    Damage to Heating Cooling System Possible.
    Be careful when handling wires during installation.
    Disconnect power at furnace or main breaker/fuse box.
    Location
    Locate the thermostat about 5 ft (1.5m) above the floor in
    an area with good air circulation at average temperature.
    Do not mount the thermostat where it can be affected by:
    Ñ drafts or dead spots behind doors and in corners.
    Ñ hot or cold air ducts.
    Ñ concealed pipes and chimneys.
    Ñ unheated (uncooled) areas such as an outside wall
    behind the thermostat.
    Mounting Plate Installation (Fig. 2)
         1.  Hold mounting plate in position and mark the two holes
    for mounting.
         2.  Level for appearance only; thermostat functions
    properly even when not level.
         3.  Tighten the mounting screws.
         4.  Set aside the mounting plate.
         5.  Drill the two holes in the wall as marked.
    Ñ Drill 3/16 in. holes for drywall.
    Ñ Drill 7/32 in. holes for plaster or wood.
         6.  Reposition the mounting plate over the holes and pull
    wires through the wiring opening.
         7.  Loosely insert the two mounting screws into the holes.
    WALLWIRES THROUGH
    WALL OPENINGWALL ANCHORS (2)
    MOUNTING
    PLATE
    MOUNTING
    SCREWS (2)
    M1718
    Fig. 2. Mounting plate installation.
    Wiring Thermostat
    All wiring must comply with local electrical codes and
    ordinances. Refer to Fig. 5 through 8 for typical hookups. A
    letter code is located near each terminal for identification.
         1.  Connect the system wires to the thermostat. See Fig. 3.
    A letter code is located near each terminal for
    identification.
    NOTE: Hold the thermostat as shown in Fig. 4 to
    minimize the need for wire extenders.
         2.  Securely tighten each terminal screw.
         3.  Push excess wire back into the hole.
         4.  Plug the hole with nonflammable insulation to prevent
    drafts from affecting thermostat operation.
         5.  Run the required number of wires to the thermostat
    location. Refer to Fig. 5 through 8 for typical wiring
    diagrams.
         6.  In 5-wire installations only, be sure to remove the factory-
    installed jumper connecting the terminals R and Rc.
    System TypeCompatible
    with T8112D
    Gas—Standing Pilot Yes
    Gas—Electronic Ignition Yes
    Gas-Fired Boilers Yesa
    Gas—Millivolt No
    Oil-Fired Boilers Yesa
    Oil-Fired Furnace Yes
    Electric Furnace Yes
    Electric Air Conditioning Yes
    Baseboard Electric (120/240 Line Volt) No
    Heat pumps/Multistage Equipment No 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-0206
    4
    Fig. 3. Proper wiring technique.
    M1712A
    JUMPER (FACTORY-
    INSTALLED) REMOVE 
    IF 5-WIRE SYSTEMINSERT
    STRAIGHT 
    UNDER 
    SCREW HEAD
    5/16 in. 
    (8 mm)
    STRIP 
    END OF WIRE 
    VISIBLE HERE
    R
    R
    c WY G
    Fig. 4. Holding thermostat while installing.
    M3002A
    Fig. 5. 2-wire heat-only application (jumper intact).
    RRc W      Y      G
    B               D A               C
    2-WIRE HEAT-ONLY (JUMPER INTACT)
    M1709B
    L1
    (HOT)
    L2
    POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
    OVERLOAD PROTECTION AS REQUIRED.
    1
    1
    HEATING
    RELAY OR
    VALVE COIL
    JUMPER
    Fig. 6. 3-wire cool-only application (jumper intact).
    RRc W      Y      G
    B               D A               C
    3-WIRE COOL-ONLY (JUMPER INTACT)
    L1
    (HOT)
    L2
    POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
    OVERLOAD PROTECTION AS REQUIRED.
    1
    JUMPER
    M848A
    COOLING
    CONTACTOR
    COIL
    FAN
    RELAY
    Fig. 7. 4-wire heat/cool application (jumper intact).
    RRc W      Y      G
    B               D A               C
    4-WIRE HEAT/COOL (JUMPER INTACT)
    L1
    (HOT)
    L2
    POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
    OVERLOAD PROTECTION AS REQUIRED.
    1
    JUMPER
    HEATING
    RELAY OR
    VALVE COIL
    M1710B
    COOLING
    CONTACTOR
    COIL
    FAN
    RELAY 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-0206
    5
    Fig. 8. 5-wire heat/cool application (jumper removed).
    Adjust Fan Operation Switch, as Required
    The thermostat fan operation switch, labeled FUEL SWITCH
    (see Fig. 9) is factory set in the F position. This is the correct
    setting for most systems. If you have an electric heat system,
    set the switch to E. In systems with the G terminal connected,
    the E setting turns on the fan immediately with heating or
    cooling.
    RRc W      Y      G
    B               D A               C
    5-WIRE HEAT/COOL (JUMPER REMOVED)
    L1
    (HOT)
    L2
    POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
    OVERLOAD PROTECTION AS REQUIRED.
    1M1711B
    L1
    (HOT)
    L2
    COOLING
    CONTACTOR
    COILFAN
    RELAY
    HEATING
    RELAY OR
    VALVE COIL
    11
    M3669
    RRc
    W      Y      G
    B              D
    A             C
    THERMOSTAT BACK
    FOR HIGH EFFICIENCY FURNACE (90%+ AFUE)
    SCREW A–OUT 1 TURN
    SCREW B–IN
    FUEL SWITCH – F POSITION
    FE FUEL SWITCH
    WARM AIR
    FURNACEA–IN
    ADJUST SCREWS THROUGH HOLES
    TO SELECT OPERATION DESIRED
    B–IN
    FUEL SWITCH
    POSITION HEATING SYSTEM
    ELECTRIC 
    FURNACE HOT WATER
    BOILER
    A–IN A–OUT
    1 TURNB–IN
    B–OUT
    1 TURNEFF
    ADJUST:
    NOTE: This thermostat does not have a setting for steam/
    gravity air. Cycles would not be long enough for
    accurate temperature control.
    NOTE: For condensing furnaces, follow manufacturer
    instructions.
    IMPORTANT
    When using a high efficiency furnace such as a
    90 percent or greater AFUE (Average Fuel Utilization
    Efficiency) unit, adjust screw A out one turn and
    screw B In one turn.
    If you want a longer on-time, readjust screws A and B as
    follows (refer to Table 1 Compatibility Chart):
    ¥ Warm Air FurnaceÑset at the Hot Water setting (AÑout
    one turn, BÑin).
    ¥ Electric FurnaceÑleave at the Warm Air Furnace setting
    (AÑin, BÑin).
    NOTE: This thermostat does not have a setting for steam/
    gravity air. Cycles would not be long enough for
    accurate temperature control.
    Install Batteries
    IMPORTANT
    Batteries must be installed for programming and
    operating the thermostat and heating/cooling
    system.
         1.  Use two AA alkaline batteries; nonalkaline batteries will
    not last as long.
         2.  Make sure the thermostat is set to the Off position.
         3.  Use a coin to remove the battery door (see Fig. 10).
         4.  Install the new batteries as shown, making sure positive
    and negative terminals are oriented correctly (see Fig. 11).
         5.  Replace the battery door.
    When the batteries are running low, a 
    bAt Lo indicator will
    flash for one to two months before batteries run out
    completely. Replace the batteries as soon as possible after
    the indicator starts flashing. If the batteries are not replaced
    when the 
    bAt Lo indicator is flashing, the indicator eventually
    stops flashing. When the batteries are almost completely
    dead, 
    bAt Lo will stay on without flashing, indicating that the
    thermostat and heating/cooling system have stopped working.
    The thermostat will not function after the batteries are
    completely dead, and the
     bAt Lo indicator disappears, leaving
    a completely blank display.
    To remove the batteries, press down on the left ends. When
    the new batteries are installed within 20 to 30 seconds of
    removing the old ones, the thermostat does not have to be
    reprogrammed. If the display is blank, the batteries are dead
    or incorrectly installed and the thermostat has to be
    reprogrammed. See OwnerÕs Manual for reprogramming
    instructions.
    IMPORTANT
    Although the thermostat has a low battery indicator,
    replace the batteries once a year to prevent the
    thermostat from losing time and programming due to
    lack of battery power.
    Fig. 9. Back view of thermostat.
    Adjust System On-Time as Required
    The thermostat on-time is factory set for a warm air, gas or oil
    heating system. If you are installing it on another type of
    system, the system on-time must be adjusted by changing the
    setting of screws A and B on the back of the thermostat. Use
    the heating system table in Fig. 9 as a guide to minimize room
    temperature swings. The system on-time should be optimized
    according to the type of system. Setting the screw 
    out one
    turn
     means turning the screw approximately 360°, or one
    complete turn. 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-0206
    6
    Fig. 10. Removing battery door.
    M5781
    Fig. 11. Installing batteries.
    Mounting Thermostat
         1.  Engage the tabs at the top of the thermostat and
    mounting plate. See Fig. 12.
         2.  Press the lower edge of the case to latch.
    NOTE: To remove the thermostat from the wall, first pull out
    the bottom of the thermostat and then remove the
    top portion.
    Fig. 12. Mounting thermostat on mounting plate.
    INSTALL TWO AA ALKALINE 
    BATTERIES AS SHOWN
    M5782
    Auto   OnFan  Cool   Off   HeatSystem  
    FAN SWITCH
    SYSTEM 
    SWITCH
    TUAMLEAVE 
    M5780
    B.  PRESS LOWER EDGE 
          OF CASE TO LATCH.A.  ENGAGE TABS AT TOP OF 
          THERMOSTAT AND MOUNTING PLATE.
    TUAMLEAVE 
    PROGRAMMING THE THERMOSTAT
    Set the Current Time/Day
    To set the time:
         1.  Press and release the Clock/Day key once.
         2.  Press the Time keys s or t until the current time
    displays.
    To set the day:
         1.  Press and release the Clock/Day key again.
         2.  Press the Time keys s or t until the current day
    displays.
         3.  Press the Run Program key.
    Heating Program
    To set the system switch to HEAT:
         1.  Press and release the Schedule key once. WAKE,
    Mon-Fri , and SET appear on the display.
         2.  Press the Time keys s or t to program WAKE time,
    and Temp keys s or t to program WAKE temperature
    for Mon-Fri.
         3.  Repeat this sequence for LEAVE, RETURN, and
    SLEEP.
         4.  Press the Schedule key until SAT, SUN, WAKE and
    SET appear on the display.
         5.  Press the Time keys s or t to program WAKE time,
    and Temp s or t to program WAKE temperature for
    Sat-Sun.
         6.  Repeat this sequence for SLEEP.
    Cooling Program
         1.  Set the system switch to COOL and follow the same
    procedure as for the Heating Program.
         2.  After programming, adjust the fan and system switches
    as desired.
         3.  Press and release the Run Program key to start the
    program.
    A Quick Guide for Operating or Making
    Changes
    NOTE: The system switch must be set to Heat or Cool to
    perform the following.
    To temporarily change the temperature for the
    current period only:
         1.  Press the Temp keys s or t.
    Ñ The temporary indicator shows on the display and
    cancels itself at the next scheduled change.
         2.  To cancel sooner, press the Run Program key.
    To hold a temperature indefinitely:
         1.  Press the Hold Temp key.
         2.  Press the Temp keys s or t.
         3.  To cancel, press the Run Program key. 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-0206
    7
    To check the current temperature setting:
    Press the Run Program key. (When using TEMPORARILY
    CHANGE or HOLD, pressing this key will cancel the change
    or hold.)
    To check the programs:
         1.  Press the Schedule key repeatedly to see each time
    and temperature.
         2.  Press the Run Program key.
    To cancel a program:
         1.  Press the Schedule key until the program to cancel
    appears
         2.  Press both the Time keys s and t together.
    To permanently change a program:
    Repeat the steps in the Heating Program or Cooling Program
    section as applicable.
    To return to the normal program:
    Press the Run Program key.
    Heat Cool Off
    M1703
    Auto On
    M1705
    Heat Cool Off
    M1704
    Auto On
    M1705
    Auto On
    M1705
    Heat Cool Off
    M1707
    Temp
    Temp
    Temp
    Temp
    CHECKOUT AND SETTINGS
    After the thermostat is mounted on the mounting plate, check operation as follows:
    Fan Switch
    FAN AUTO: Normal setting for most homes. A
    single-speed fan turns on automatically with
    the air conditioner or furnace. A two-speed fan
    usually runs on high with the air conditioner
    and on low with the furnace.
    FAN ON: The fan runs continuously. Use for
    improved air circulation during special
    occasions or for more efficient electronic air
    cleaning.
    System Switch
    COOL: The thermostat controls the air
    conditioning system.
    OFF: Both the heating and air conditioning
    systems are off.
    HEAT: The thermostat controls the heating
    system.
    Auto On
    M1705
    Auto On
    M1706
    Heat Cool Off
    M1704
    Heat Cool Off
    M1707
    Heat Cool Off
    M1703
    Heating
    Do not check the heating system operation by jumpering the thermostat terminals at the primary control
    such as the gas valve, zone valve, or oil burner control. This will damage the thermostat.
    Move the system switch to HEAT and the fan switch to AUTO.
    Press the TEMP key until the setting is about 10°F (6°C) above the room temperature. After a short
    delay, the heating should start and the fan should run (immediately if fan operation switch is set in  
    E position).
    Press the TEMP key until the setting is about 10°F (6°C) below the room temperature. The heating
    equipment should shut off.
    Cooling
    To avoid possible compressor damage, do not operate the cooling system when the outside temperature
    is below 50°F (10°C). See the compressor manufacturer instructions for further information.   
    NOTE: When the cooling setting is changed, the thermostat can delay up to five minutes before turning
    on the air conditioner to protect the compressor.  
    Move the system switch to COOL and the fan switch to AUTO.
    Press the TEMP key until the setting is about 10°F (6°C) below room temperature. The cooling
    equipment and fan should start.
    Press the TEMP key until the setting is about 10°F (6°C) above the room temperature. The cooling
    equipment and fan should stop.
    Move the system switch to OFF with the fan switch remaining at AUTO. The system and fan should be
    off. 
    						
    							T8112D PROGRAMMABLE THERMOSTAT
    68-02068
    Home and Building Control
    Honeywell Limited-Honeywell LimitŽe
    155 Gordon Baker Road
    North York, Ontario
    M2H 3N7
    68-0206  L.C. 2-98     Printed in U.S.A.
    Home and Building Control
    Honeywell Inc.
    1985 Douglas Drive North
    Golden Valley, MN 55422
    Printed on recycled paper containing at 
    least 10% post-consumer paper fibers.
    Minimum Off-Timer
    A minimum off-timer for the T8112D assures that the cooling
    compressor does not come on again for at least five minutes
    after it turns off.  The minimum-off timer is triggered when the
    compressor turns off and when the system switch is changed.If the compressor turns off when the setpoint is changed, then
    the minimum-off timer is triggered, which operates only during
    the cooling cycle of the T8112D.
    TROUBLESHOOTING
    www.honeywell.com/yourhome
    IF… THEN…
    Display will not come on. • Set the system switch to OFF; remove batteries; insert backward for at l\
    east  
    five seconds to reset thermostat; replace batteries correctly. Display s\
    hould come
    on.
    • Make sure batteries are fresh and installed correctly.
    Temperature display will not go lower
    than 45°F (7 °C) or higher than 88 °F
    (31 °C) during programming. • The temperature setting limit has been reached. The setting range is 45
    °F to 88 °F
    (7 °C to 31 °C).
    Heating will not come on. • If the display is blank or displays bAt Lo, install fresh batteries.
    • Check that the switch on the thermostat is set to HEAT.
    • Check the system fuse or circuit breaker and replace or reset if necessa\
    ry.
    • If the temperature setting is higher than the current temperature, and S\
    YSTEM ON
    indicator is lit, see the furnace manufacturer instructions.
    Cooling will not come on. • If the display is blank or displays bAt Lo, install fresh batteries.
    • In 2- or 4-wire installations, verify that the R-Rc jumper is installed.\
    • Check that the switch on the thermostat is set to COOL.
    • Check the system fuse or circuit breaker and replace or reset if necessa\
    ry.
    • The thermostat has a built-in time delay on cooling. Allow five to ten m\
    inutes afterchanging the setting before the air conditioner starts.
    • If the temperature setting is lower than the current temperature, and th\
    e SYSTEMON indicator is lit,  see the air conditioner manufacturer instructions.\
    SYSTEM ON indicator is lit, but no
    heat is coming from the registers. • Allow time for the furnace to heat up and the fan to come on before chec\
    king for
    heat at the register. Check to make sure system on-time is set correctly\
     according
    to the instructions in the Installation section.
    Furnace or air conditioner cycles too
    frequently.   • Readjust according to the instructions in the Installation Section.
    The system on-time is too short or too
    long.• Readjust according to the instructions in the Installation Section.
    The thermostat current setting does
    not match the display temperature.• Check that the wiring hole in the wall behind the wallplate was plugged \
    with
    insulation to prevent drafts that could adversely affect thermostat oper\
    ation.
    • It is normal for the current setting and display temperature to differ o\
    ccasionally.
    bAt Lo remains on the display after
    fresh batteries have been installed. • Remove batteries. Wait one hour. Install fresh alkaline batteries. 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Thermostat T8112d1005 (1) Manual