Page 31

 
Installation  31  
4.
 
If the UPS is powered up, you can be sure that the UPS Network Module is seated properly and 
communicating with the UPS by verifying that the UPS Data LED illuminates solid green, and then 
flashes regularly after 2 minutes.  
 
 
Connecting the UPS Network Module  
The UPS Network Module is provided to manage the attached servers. RJ 45 network patch panel cables 
are required to use this card. 
The RJ 45 network patch panel cables are not include d. 
 
 
Installing the UPS as...

Page 32

 
Installation  32  
  WARNING:
  To prevent personal injury from electric shock or damage to the equipment, 
remove the battery lead labels, and verify that the ERM circuit breakers  are in the Off position. 
  
  
Rotating the logo badge  
Gently pull out the logo badge, rotate it 90 degrees, and then replace it in the bezel.  
 
  

Page 33

 
Installation  33  
Attaching the UPS front bezel  
  
Attaching the tower conversion stands    
  WARNING:
  To reduce the risk of personal injury or damage to the equipment, the tower 
conversion stands must be properly attached when the unit is installed as a tower.  
  
Using the preinstalled screws, attach the tower conversion stands to the unit.  
 
 
Continuing  the installation  
To continue the UPS installation, follow the instructions starting with " Connecting the serial 
communications...

Page 34

 
Installation  34  
Installing the ERM as a tower  
Before installing the unit, review and adhere to all  warnings provided in " Precautions (on page  12)." 
The tower stands and associated hardware ship with the UPS.  
 
Rotating the logo badge 
Gently pull out the logo badge, rotate  it 90 degrees, and then replace it in the bezel.  
 
  

Page 35

 
Installation  35  
Attaching the ERM front bezel  
 
 
 
Attaching the tower conversion stands    
  WARNING:
  To reduce the risk of personal injury or damage to the equipment, the tower 
conversion stands must be properly attached when the unit is installed as a tower.  
   

Page 36

 
Installation  36  
1.
 
Using the preinstalled screws, attach the tower conversion stands to the unit.  
 
2.  Remove a screw from the inner -most, rear corner of the UPS and ERM.  
 
3.  To attach the tower brackets:  
o For the front bracket, use the mounting ear screws.   

Page 37

 
Installation  37  
o
 
For the rear bracket, use the screws removed from the chassis.  
 
 
Continuing the ERM installation 
To continue the  ERM installation, follow the instructions starting with " Connecting the ERM to the UPS (on 
page  28)." 
  

Page 38

 
Installation  38  
Installing the extension bars (if included)  
 
 
  

Page 39

 
Installation  39  
Connecting and securing the power cords  
  

Page 40

 
UPS  operations  40  
UPS operations  
Modes of operation 
The UPS h as five modes of operation:  
• Standby mode (on page 40) 
• Operate mode  (on page 40) 
• Configure mode  (on page 41) 
• Battery mode  (on page 41) 
• Auto -Bypass mode  (on page 41)  
Standby mode  
In Standby mode:  
• No power is available at the UPS output receptacles.  
• The UPS charges the batteries as necessary. 
The UPS can be placed in Standby mode when the UPS is in Operate mode  (on page 40). 
To place the UPS in Standby...