Page 51

 
Power  management  51 
Power management  
Power management software  
HP Power Manager software ensures maximum power reliability of computer systems through 
comprehensive control of UPSs. The easy -to -use browser interface enables novice users to configure and 
manage power protecti on settings. To download the latest version of HP Power Manager software, see 
the  HP website  (http://www.hp.com/go/rackandpower
).    
 
NOTE:  To install and configure the software, see the software user guide.  The...

Page 52

 
Troubleshooting  52 
Troubleshootin g 
LED troubleshooting            
Utility 
LED  On 
Batter
y LED
 On 
Bypas
s LED
 Self 
Test 
LED
  Battery 
Fault 
LED
  Site 
Wiring 
Fault 
LED
  Over 
Temp 
LED
  Overloa
d LED
  Condition
 
On—
Load 
10% On—
Load 
>25%
 On—
Load 
>50%
 On—
Load 
>75%
 Off
 
UPS is in Operate mode  (on 
page  38) 
Flashin
g  Off
  Off  Off  *  *  *  Off 
UPS is in Standby mode  (on 
page  38) 
Off  Off  On 
On—
Load 
>10% On—
Load 
>25%
 On—
L
oad 
>50%  On—
Load 
>75%
 Off...

Page 53

 
Troubleshooting  53 
Off
  On  Off 
On—
Battery 
capacity 
25%
 On—
Batt
ery 
capacity 
>50%  On—
Battery 
capacity 
>75%
 Off
 
UPS is on battery  (on page 
55) —No utility power  
*  *  *  Off  *  *  Flashing * 
Overtemperature condition  
(on page 56)  
Off  Off  On  Flashing  Flashing  Flashing  Flashing  Flashing  
Internal UPS fault condition  
(on page 56)  
Flashin
g  Off
  Off  Flashing  Flashing  Flashing  Flashing  Flashing  
REPO condition  (on page 
56)  
*  Off  *  Off  *  Flashing *  *...

Page 54

 
Troubleshooting  54 
• Overload  
The load is supported, but not protected while in Auto -Bypass mode.  
Action : 
1.  If power management software is b eing used, check the log files to obtain specific error information 
to help identify the problem.  
For more information about the causes of a general fault condition, see the HP Power Manager user 
guide available for download from the HP website  (http://www.hp.com/go/rackandpower
).  
2.  Verify that no blockage of airflow to the front bezel and...

Page 55

 
Troubleshooting  55 
b.
 
If the Battery Fault LED is red, replace the batteries  (" UPS battery replacement procedure " on 
page  46). 
3.  Reduce the load:  
a. Power down the UPS  (" Powering down the UPS " on page 42). 
b.  Remove one or more load devices to reduce the power requirements.  
c. Wait at least 5 seconds and restart the UPS.  
d. If the condition persists, verify that the load devices are not defective.  
4. Allow the UPS to cool:  
a. Power down the UPS  ("...

Page 56

 
Troubleshooting  56 
Input voltage is out of range  
Action: 
1.  Check the input voltage and reconfigure the UPS  (" Configuring the UPS " on page 40). 
2.  Contact a qualified electrician to verify that the utility power is suitable for the UPS.   
Overtemperature condition 
Possible cause: The UPS internal temperature is too high, or a fan has failed.  
Action : 
1.  Power down the UPS  (" Powering down the UPS " on page 42). 
2.  Allow the UPS to cool:  
a. Clear vents and remove...

Page 57

 
Troubleshooting  57 
O verload conditi on 
All the load LEDs are illuminated.  
Action : 
1.  Power down the UPS  (" Powering down the UPS " on page 42). 
2.  Remove one or more load devices to reduce the power requirements.  
3. Wait at least 5 seconds and restart the UPS.  
4. If the condition persists, verify that the load devices are not defective.   
Checksum failure error  
A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM 
map while...

Page 58

 
Troubleshooting  58 
5.
 
During extended power outages, save your work, power down the load devices, and then power 
down the UPS  (" Poweri ng down the UPS " on page 42) to conserve battery power.  
 
UPS frequently switches between utility and battery 
power  
Action: 
1.  Check the input voltage and reconfigure the UPS  (" Configuring the UPS " on page 40). 
2.  Contact a qualified electrician to verify that the utility power is suitable for the UPS.   

Page 59

 
Specifications  59 
Specifications  
UPS physical specifications      
Parameter   Value 
Height   8.9 cm (3.5 in) 
Depth  63.5 cm (25 in) 
Width  44.5 cm (17.5 in) 
Weight  37 kg (82 lb)   
ERM physical specifications       
Parameter   Value 
Height   8.9 cm (3.5 in) 
Depth  63.5 cm (25 in) 
Width  44.5 cm (17.5 in) 
Weight  55 kg (122 lb)   
UPS input specifications         
UPS model  
Utility voltage 
frequency (Hz)  Available settings 
utility voltage (VAC)   Branch circuit 
rating (A)
 Line...

Page 60

 
Specifications  60 
UPS model   Load segment  Output receptacles  
  2
  2 x 5-20T  
R/T3000h NA/JPN  1  3 x IEC-320- C13 
   1 x IEC
-320- C19 
   1 x L6
-20R  
  2
  3 x IEC-320- C13 
   1 x IEC
-320- C19 
R/T3000 INTL  1  3 x IEC-320- C13 
   1 x IEC
-320- C19 
  2
  3 x IEC-320- C13 
   1 x IEC
-320- C19   
Power protection specifications       
UPS model  VA 
Nominal power rating 
(W)  Nominal voltage 
setting
 
R/T3000 
NA/JPN   2880
  2700  100, 110, 120, 127 
R/T3000h 
NA/JPN  3300
  3000...