Home > Lincoln > Welding System > Lincoln Na5 Service Manual

Lincoln Na5 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Lincoln Na5 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1 Lincoln manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							MECHANICAL
    INSTALLATION
    ELECTRIC SHOCK
    can kill.
    • Turn off input power to the welding power source
    using the disconnect
    switch before working on
    this equipment.
    INTRODUCTION
    This section covers the basic requirements to
    install the control box and welding head
    shown in Figure A.1. This section will give
    you mounting hole alignments, component
    mounting clearances, and any special
    instructions or precautions that must be fol-
    lowed when installing the control box and
    mounting head.
    CONTROL BOX INSTALLATION
    The control box can be mounted either on
    the standard travel carriage or on a separate
    fixture. It is electrically grounded by a lead
    in the input cable assembly.
    To install the control box on the standard
    travel carriage, use mounting kit T14469 and
    perform the following steps. Also refer to
    Figure A.2. 1. Align the mounting holes in adapter
    plate M-13945 to the holes in the
    travel carriage.
    2. Install four hex head screws through the adapter plate and into the travel
    carriage.
    3. Secure the control box to the adapter plate with four lock washers and four
    bolts, two from the bottom and two
    from the back.
    Before mounting the control box onto a
    fixture,  you must  provide mounting holes in
    the fixture per the measurements provided
    in Figure A.3 or dimension print S16717.
    When placing the mounting holes, ensure
    the controls and meters are convenient to
    the operator. 
    INSTALLATIONA-4A-4
    NA-5
    WARNING
    ADAPTER
     PLATE
    TRAVEL
    CARRIAGE
    CONTROL
     BOX
    FIGURE A.2 – CONTROL BOX CARRIAGE MOUNTING.
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							To install the control box on a fixture,
    perform the following steps and refer to
    Figure A.3.1. Align the mounting holes on the back and/or bottom of the control box with
    the holes you put in the fixture
    according to the measurements
    provided in Figure A.3.
    2. Secure the control box to the fixture using lock washers and hex head
    screws at each of the mounting holes.  WELDING HEAD INSTALLATION
    The welding head can be mounted either
    with the standard head mounting hardware
    or with the horizontal head and/or vertical lift
    adjusters.  Design the installation of your
    welding head so it meets the adjustability
    requirements of your welding application.
    Refer to Section C, Accessories, for more
    information regarding the adjustable
    mounting hardware.
    The welding head and electrode are
    electrically “hot” when welding. They must
    be insulated from ground.
    Standard head mounting hardware and
    insulation are shipped with the NA-5
    welding head.  If you are mounting the
    welding head on a separate fixture, provide
    the mounting holes for the standard head
    mount as specified in Figure A.4. For best
    arc striking, use a rigid mounting that
    prevents the head from moving when the
    electrode strikes the work.
    FRONT
    VIEW FROM BOTTOM
    1/4-20 THREAD  HOLES
    3.50
    (88.9)
    VIEW FROM BACK
    1/4-20
    THREAD HOLES
    1.71
    (43.43)
    1.09
    (27.68)
    0.28 (7.11) SLOTS
     4 PLACES 0.41
    (10.41)
    0.43
    (10.92) 13.77
    (349.76)
    12.75
    (323.85)
    0.562 DIA (14.27)
    2 HOLES
    12.00
    (304.8)
    
    12.00
    (304.8)
    NOTE:  DIMENSIONS ARE IN INCHES 
                 WITH MILLIMETERS IN 
    	    PARENTHESES.
    1.34
    (34.04)
    1.71
    (43.43)
    APPROXIMATE
     INSULATOR
     SIZE
      2.62
    (66.55) 
    
    2.88
    (73.15)
      4.265
    (108.33) 0.531 DIA.
       (13.49)
    NOTE:  DIMENSIONS ARE IN INCHES 
                 WITH MILLIMETERS IN 
    	    PARENTHESES.
    
    4.5 
    (114.30)
    FIGURE A.4 – WELDING HEAD MOUNTING HOLES.
    INSTALLATIONA-5A-5
    FIGURE A.3 – CONTROL BOXFIXTURE MOUNTING.
    NA-5
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-6A-6
    NA-5
    When mounting the welding head to the
    standard travel carriage, (see 305-B sec.
    T2.2.4) mount it so only a minimum of
    overhang weight exists. Mount the head so
    it stays within the dimension shown in Figure
    A.5.
    ELECTRICAL
    INSTALLATION
    ELECTRIC SHOCK
    can kill.• Do not touch electrically live parts such as output
    terminals or internal
    wiring.
    This section  provides information on proper 
    wiring  procedures  for the NA-5 welding sys-
    tem.  This section  also  provides  basic con- nection diagrams for connecting automatic
    welding systems to various welding power
    sources.
    INPUT POWER REQUIREMENTS
    350 volt-amperes of 115 VAC 50/60 Hz
    power is required for the wire feed motor and
    controls. Another 250 volt-amperes may be
    required depending on the travel circuit.
    CONTROL BOX TO WELDING
    HEAD CONNECTIONS
    All welding heads include a 4 ft (1.2 m)
    motor cable and motor tachometer cable.
    Insert the plugs on these cables into the
    matching receptacles on the side of the
    control box. 
    If the 4 ft (1.2 m) cables are not sufficient,
    install a K335 or K338 control to head
    extension cable of the length ordered [up to
    30 ft (9.1 m)].  The K335, for the NA-5S
    head, includes motor, tachometer and flux
    hopper lead extensions with polarized plugs
    on each end, and electrode cables.  The
    K338 for the NA-5N, NF, and SF heads is
    the same as the K335 without the flux
    hopper lead extension.
    The NA-5N and NA-5S also include two 4 ft
    (1.2 m) lengths of electrode cable. Bolt the
    terminals at one end of the the cable pair to
    the wire contact assembly and the terminals
    at the other end to the electrode leads on the
    power source to control cable assembly.
    Properly insulate the bolted connection.
    When the K335 or K338 extension cables are
    used between the controls and heads, the 4 ft
    (1.2 m) lengths of electrode cable are not
    used.  If currents or duty cycles higher than
    1000 amps at 80% duty cycle will be used,
    add additional electrode cable per Table A.1.
    TABLE A.1
    FIGURE A.5 – MOUNT TO CARRIAGEOVERHANG DIMENSION.
       19 IN.
    (483 MM)
    WARNING
    80% Duty Cycle
    Below 1000 amps Two 4/0
    1000 to 1300 amps Three 4/0
    1300 to 1500 amps Four 4/0
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							The “F” models do not include the 4 ft (1.2
    m) lengths of electrode cable as standard.
    If you are not using a K335 or K338 exten-
    sion cable for the NA-5NF or NA-5SF, order
    an appropriate length of the needed elec-
    trode cable.  Connect it between the wire
    contact assembly and the control cable
    assembly as described above. 
    POWER SUPPLY TO CONTROL
    BOX CONNECTIONS
    At the NA-5 control box, in order to activate
    the NA-5 weld current sensing switch, the
    electrode cables of the control cable
    assembly must be placed under the clamp
    bar on the left-hand side of the control box,
    as shown in Figure A.6.  This is required
    for proper operation of the reed switch.
    The nuts holding the clamp bar in place
    need only to be pulled up snug.  Do not
    overtighten.  If a carriage is used, the
    electrode cables should also be clamped
    to it with the cable clamp supplied on the
    carriage.  Do not clamp the control cable
    under the travel carriage clamp but route it
    over its top.Insert the polarized connector of the K215
    or K597* control cable into the matching
    receptacle on the side of the control box.
    With the power source off, connect the
    control cable assembly to the power
    source as follows:
    1. If   using   the   multi-process power source (SAM, SA-800, SAF-600,
    DC-400, DC-600, DC-1000, or DC-
    1500 types), be sure it is properly set
    for the welding process being used
    per the connection diagram (Figures
    A.8 to A.14). 
    2. Connect the K215 control cable leads to the power source terminal
    strip  exactly as specified on the
    connection diagram.* Include all
    jumpers on the terminal strips as
    shown on the diagram. Do not put
    on any other jumpers. If currents or
    duty cycles higher than 1000 amps
    at 80% duty cycle will be used, add
    additional electrode cables to the
    K215 assembly per Table A.1.
    3 Depending on the  power source and the process to be used, the jumpers
    on the NA-5 voltage board may have
    to be changed.  As shipped, the
    NA-5 is connected for use with the
    DC-400, DC-600, DC-1000, and
    DC-1500 type power sources.  For
    other power sources, refer to the
    appropriate connection diagram and
    to IM305 Sec. T3.6.
    4. Connect work leads of sufficient size and length per Table A.1. between
    the “To Work” stud on the power
    source and the work.  Be sure the
    connection to the work makes a tight
    and clean metal-to-metal contact.
    *The K597 cable assembly has a 14-pin MS-type
    connector for use with later model Lincoln CV powersources.
    INSTALLATIONA-7A-7
    NA-5
    FROM 
    POWER
    SOURCE
    TO
    WELDING
     HEAD
    CLAMP
    BAR
    FIGURE A.6 – CONTROL BOXELECTRICAL CONNECTIONS. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-8A-8
    NA-5
    ELECTRODE POLARITY
    ELECTRIC SHOCK
    can kill.• Turn off input power to the welding power
    source using the
    disconnect switch
    before working on this
    equipment.
    Polarity is changed at the power source. 
    The polarity of the NA-5 control circuit is
    shipped connected for electrode positive.  If
    electrode negative is required, two leads
    inside the NA-5 control must be reversed.
    Proceed as follows:  1. Turn off the input power to the NA-5 control box by turning off the welding
    power source.
    2. Open the control box door and locate the terminal strips on the back of the
    control box in the lower left-hand
    corner as shown in Figure A.7.
    3. On the right end of the lower terminal strip, interchange the black and white
    leads going to the terminals marked
    (+) and (-).  The  black lead (#67)
    must be connected to the same
    polarity as the electrode welding lead;
    i.e. if the electrode is positive,
    connect the black lead to the (+)
    terminal on the terminal strip. The
    white lead (#21) is connected to the
    opposite polarity terminal.
    POWER SOURCE
    CONNECTION DIAGRAMS
    The following section contains the wiring
    diagrams necessary to connect the
    applicable power source to the control box.
    If there is no diagram, refer to power source
    manual. 
    ELECTRIC SHOCK
    can kill.• Turn off input power to the welding power
    source using the
    disconnect switch
    before working on this
    equipment.
    WARNING
    TERMINAL
    STRIPS
    FIGURE A.7 – TERMINAL STRIP LOCATION. 
    WARNING
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-9A-9
    NA-5
    FIGURE A.8 – CONNECTION OF NA-5 (ALL) TO A DC-600.     
    N.A.	 ON EARLIER DC-600S, #67 TERMINAL WAS ALSO ON THE TERMINAL STRIP.
    N.B.	 WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\
     OF IMMEDIATE AND FUTURE APPLICATIONS.
    N.C.	 EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\
    OR THE INSTALLATION. AN S-16586 - [ ] REMOTE VOLTAGE SENSING WORK 
    	 LEAD IS AVAILABLE FOR THIS  PURPOSE. CONNECT IT DIRECTLY TO THE WORK PIE\
    CE KEEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION
    	 TO THE WORK PIECE. FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TAP\
    ED ALONG THE WELDING WORK CABLE.
    N.D.	 TAPE UP BOLTED CONNECTION.
    N.E.	 CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\
    ED          NEAR THE POWER SOURCE TERMINAL STRIP. THE POWER 
    	 SOURCE MUST BE PROPERLY  GROUNDED.
    N.F.	 IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #75 TO #75 ON TERMIN\
    AL STRIP, CONNECT LEAD #76 TO #76 ON TERMINAL STRIP, CONNECT 
    	 LEAD #77 TO #77 ON TERMINAL STRIP.
    N.G.	 THE JUMPERS ON THE NA-5 VOLTAGE BOARD MUST BE CONNECTED AS FOLLOWS: CONN\
    ECT RED JUMPER TO PIN S. CONNECT WHITE JUMPER TO PIN B.
    N.H.	 CONNECT A JUMPER FROM N TO P. THERE IS NO NPS TERMINAL STRIP ON DC-6\
    00 CODES ABOVE 8200.
    N.J.	 FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER TH\
    E CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX.	 NOTE:	 DIAGRAM SHOWS ELECTRODE CONNECTED POSITIVE. 
    		
    TO CHANGE POLARITY, TURN POWER OFF, REVERSE THE
    	  	 ELECTRODE AND WORK CABLES  AT THE POWER SOURCE
    		 AND POSITON THE SWITCH ON POWER SOURCE TO PROPER 
    		 POLARITY. REFER TO NA-5 OPERATING MANUAL FOR REQUIRED
    		 NA-5 CONTROL BOX POLARITY CONNECTIONS.
    
    
    ALL CODES:
    TURN OFF INPUT POWER
    ADJUST THE POWER SOURCE: DC-600:
    1.	 CONNECT ELECTRODE CABLES TO TERMINAL OF DESIRED POLARITY.
    2.	 SET TOGGLE SWITCH TO SAME POLARITY AS THE ELECTRODE CABLE
    	 CONNECTION.
    3.	 SET TOGGLE SWITCH TO REMOTE.
    4.	 SET MODE SWITCH TO THE DESIRED POSITION FOR THE PROCESS TO BE USED.
    	
    DC-600 CODES 8000-8045:
    FOR SUB ARC:
    1.	 SET MODE SWITCH TO CV SUB ARC.
    2.	 WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M AND BLUE 
    	 LEAD IS CONNECTED TO W.
    
     FOR ALL OPEN ARC PROCESSES EXCEPT NR-302 AND NR-203 ELECTRODES:
    1.	 SET MODE SWITCH TO CV INNERSHIELD.
    2.	 WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M AND BLUE 
    	 LEAD IS CONNECTED TO W.
    
    
    FOR NR-203 AND NR-302 ELECTRODES:
    1.	 SET MODE SWITCH TO CV INNERSHIELD.
    2.	 WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN I 
    	 AND BLUE LEAD IS CONNECTED TO S.DC-600 CODES 8046-8200:
    FOR SUB ARC:
    1.	 SET MODE SWITCH TO CV SUB ARC.
    2.	 WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M.
    
    FOR ALL OPEN ARC PROCESSES EXCEPT MR-203 ELECTRODES:
    1.	 SET MODE SWITCH TO CV INNERSHIELD.
    2.	 WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN M.
    
    FOR NR-203 ELECTRODES:
    1.	 SET MODE SWITCH TO CV INNERSHIELD.
    2.	 WHITE LEAD ON CONTROL PC BOARD IS CONNECTED TO PIN I.
    DC-600 CODES ABOVE 8200:
    FOR SUB ARC:
    1.	 SET MODE SWITCH TO CV SUB ARC.
    FOR ALL OPEN ARC PROCESSES:
    2.	 SET MODE SWITCH TO CV INNERSHIELD.
    FOR OPTIMUM PERFORMANCE WITH NA-5, DC-600S WITH CODES 8288 AND 
    ABOVE ARE PREFERRED.  FOR ADDITIONAL INSTALLATION INSTRUCTIONS,
    SEE NA-5 OPERATING MANUAL.
    
    P
    A
    B
    P
    B
    .
    A.
    TO NA-5 INPUT CABLE PLUG
    CONNECT TO CABLES FROM NA-5
     
    WIRE CONTACT ASSEMBLY
    CONNECT TO WORK
    CLEVELAND, OHIO U.S.A. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-10A-10
    NA-5
    FIGURE A.9 – CONNECTION OF NA-5 (ALL) TO A DC-650 PRO 
    NOTE:  ABOVE DIAGRAMS SHOW ELECTRODE CONNECTED POSITIVE.  TO CHANGE POLA\
    RITY, TURN POWER OFF, REVERSE THE ELECTRODE 
    	 AND WORK CABLES AT THE POWER SOURCE AND POSITION THE SWITCH ON THE POWER\
     SOURCE TO PROPER POLARITY.  REFER TO 
    	 NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS\
    .
    DC650 PRO POWER SOURCE SETTINGS
    1.	 TURN OFF INPUT POWER.
    2.	 CONNECT ELECTRODE CABLES TO TERMINALS OF DESIRED POLARITY.
    3.	 SET TOGGLE SWITCH TO SAME POLARITY AS ELECTRODE CABLE CONNECTION.
    4.	 SET TOGGLE SWITCH TO REMOTE.
    5.	 SET MODE SWITCH TO DESIRED POSITION FOR THE PROCESS TO BE USED.
    6.	 CONNECT NEGATIVE OUTPUT CABLES TO MATCH MODE SWITCH SETTING.
    P
    AR
    P
    A
    N.A.	 WELDING CABLES MUST BE SIZED FOR CURRENT AND DUTY CYCLE OF APPLICATION.
    \
    N.B.	 EXTEND LEAD #21A BY REMOVING LEAD #21A FROM THE TERMINAL STRIP AND CONNE\
    CTING IT TO A #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE FOR 
    	 THE INSTALLATION.
    N.C.	 EXTEND LEAD #21 USING A #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE\
     FOR INSTALLATION.
    N.D.	 CONNECT EXTENDED LEAD DIRECTLY TO THE WORK PIECE KEEPING IT SEPARATE FRO\
    M THE WELDING WORK CABLE CONNECTION TO THE WORK PIECE.  FOR 
    	 CONVENIENCE, THIS EXTENDED LEAD SHOULD BE TAPED ALONG THE WELDING WORK C\
    ABLE.
    N.E.	 TAPE UP CONNECTION.
    N.F.	 FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES  MUST BE SNUGGED UNDER T\
    HE CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX.
    N.G.	 CONNECT NEGATIVE OUTPUT CABLES TO STUDS TO MATCH DC650 PRO MODE SWITCH S\
    ETTING.
    N.H.	 THE JUMPERS ON THE NA-5 VOLTAGE BOARD MUST BE CONNECTED AS FOLLOWS: CONN\
    ECT RED JUMPER TO PIN S, CONNECT WHITE JUMPER TO PIN B.
    N.J.	 IF USING AN OLDER K-215 CONTROL CABLE, CONNECT LEAD #75 TO #75 ON TERMIN\
    AL STRIP, CONNECT LEAD #76 TO #76 ON THE TERMINAL STRIP, CONNECT
    	 LEAD #77 TO #77 ON THE TERMINAL STRIP.
    N.K.	 CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\
    ED          NEAR THE POWER SOURCE TERMINAL STRIP.
    
    P6
    CONTROLCABLE
    TO NA-5 INPUT
    CABLE PLUG
    CONNECT TO CABLES FROM  NA-5 WIRE CONTACT ASSEMBLY TO NA-5 INPUT
    CABLE PLUG
    CONNECT TO CABLES FROM NA-5 WIRE CONTACT ASSEMBLY
    CONNECTTO WORK
    CLEVELAND, OHIO U.S.A. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-11A-11
    NA-5
    FIGURE A.10 – CONNECTION OF NA-5 (ALL) TO A R3S-400, -600, OR -800WITH NO LINE VOLTAGE COMPENSATOR (OBSOLETE).
    R3S POWER SOURCE SETTINGS
    TURN POWER SOURCE OFF.
    
    FOR ALL PROCESSES:
    1.	 CONNECT ELECTRODE CABLE TO TERMINAL OF DESIRED POLARITY.
    2.	 SET THE POLARITY SWITCH TO THE SAME POLARITY AS THE ELECTRODE
    	  CABLE CONNECTION.
    3.	 SET TOGGLE SWITCH TO REMOTE.
    4.	 INSTALL VOLTAGE TRIANGLE IN A POSITION AS CLOSE AS POSSIBLE TO 
    	 THE DESIRED ARC VOLTAGE. NA-5 SETTINGS
    FOR SUB ARC:
    1.	 RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN S.
    2.	 WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A.
    FOR ALL OPEN ARC PROCESSES:
    1.	 RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN F.
    2.	 WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A.
    NOTE:	 ABOVE DIAGRAM SHOWS ELECTRODE CONNECTED POSITIVE.  TO CHANGE POLARITY, T\
    URN POWER OFF, REVERSE THE ELECTRODE AND WORK CABLES AT THE 
    	 POWER SOURCE AND POSITION THE SWITCH ON POWER SOURCE TO PROPER POLARITY.\
      REFER TO NA-5 OPERATING MANUAL FOR REQUIRED NA-5 CONTROL 
    	 BOX POLARITY CONNECTIONS.
    N.A.	 ADD JUMPER FROM #75 TO #76, USING INSULATED COPPER WIRE.
    N.B.	 WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\
     OF IMMEDIATE AND FUTURE APPLICATIONS.
    N.C.	 EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\
    OR THE INSTALLATION.  AN  S -16586 [ ]  REMOTE VOLTAGE-SENSING WORK LEAD\
    
    	 IS AVAILABLE FOR THIS PURPOSE.  CONNECT IT DIRECTLY TO THE WORK PIECE, K\
    EEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION TO THE
    	 WORK PIECE.  FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TAPED ALO\
    NG THE WELDING WORK CABLE.
    N.D.	 TAPE UP BOLTED CONNECTION.
    N.E.	 CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\
    ED         , NEAR THE POWER SOURCE TERMINAL STRIP.  THE POWER SOURCE
    	 MUST BE PROPERLY GROUNDED.
    N.F.	 IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #75 TO #75 ON TERMIN\
    AL STRIP, CONNECT LEAD #76 TO #77 ON TERMINAL STRIP, CONNECT 
    	 LEAD #77 TO #76 ON TERMINAL STRIP, AND ADD JUMPER PER N.A.
    N.G.	 ON EARLIER R3S MACHINES, #67 AND #1 TERMINALS WERE ALSO ON THE TERMINAL \
    STRIP.
    N.H.	 THE UPPER TERMINAL STRIP (#75, #76, #77) WAS NOT PRESENT ON EARLY R3S \
    MACHINES.  THOSE MACHINES ARE NOT COMPATIBLE WITH THE NA-5 SINCE THERE
    \
    	 CAN BE NO ADJUSTMENT OF VOLTAGE BY THE NA-5.
    N.J.	 FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST  BE SNUGGED UNDER T\
    HE CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX.
    FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL.
    
    B
    B
    B
    POSITIVE
    CLEVELAND, OHIO U.S.A. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-12A-12
    NA-5
    FIGURE A.11 – CONNECTION OF NA-5 (ALL) TO A SAM-400 MOTORGENERATOR OR ENGINE WELDER. 
    NOTE:	 TO CHANGE POLARITY, TURN POWER OFF, AND POSITION THE SWITCH ON POWER SOU\
    RCE TO PROPER POLARITY.  REFER TO NA-5 OPERATING MANUAL FOR
    	  REQUIRED NA-5 CONTROL BOX POLARITY CONNECTIONS.
    
    N.A.	 REMOVE SAM PORTABLE FIELD CONTROL AND CONNECT NA-5 CONTROL CABLE.
    N.B.	 WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\
     OF IMMEDIATE AND FUTURE APPLICATIONS.
    N.C.	 EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\
    OR THE INSTALLATION.  AN S-16586-[ ] REMOTE VOLTAGE-SENSING WORK LEAD
    	 IS AVAILABLE FOR THIS PURPOSE.  CONNECT IT DIRECTLY TO THE WORK PIECE, K\
    EEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION TO 
    	 WORK PIECE.  FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TAPED ALO\
    NG THE WELDING WORK CABLE.
    N.D.	 TAPE UP BOLTED CONNECTION.
    N.E.	 CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\
    ED         , NEAR THE POWER SOURCE TERMINAL STRIP.  THE POWER SOURCE 
    	 MUST BE PROPERLY GROUNDED.
    N.F.	 IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #76 TO #75 ON TERMIN\
    AL STRIP, CONNECT LEADS #75 AND #77 TO #76 ON TERMINAL STRIP.
    N.G.	 ON EARLIER SAM MACHINES, #1 TERMINAL WAS ALSO ON THE TERMINAL STRIP.
    N.H.	 FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER TH\
    E CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL.
    NA-5 SETTINGS
    FOR SUB ARC:
    1.	 RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN S.
    2.	 WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A.
    FOR ALL OPEN ARC PROCESSES:
    1.	
     RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN F.
    2.	 WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A.
    SAM  POWER SOURCE SETTINGS
    
    FOR SUB ARC:
    1.	 SET THE ELECTRODE POLARITY SWITCH TO THE VARIABLE VOLTAGE 
    	 POSITION OF THE POLARITY DESIRED FOR THE PROCESS BEING USED.
    2.	 SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE.
    3.	 SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 7 AND THE
    	  CURRENT CONTROL TO 500.
    
    FOR ALL OPEN ARC PROCESSES:
     1.	 SET THE ELECTRODE POLARITY SWITCH TO THE CONSTANT VOLTAGE
    	  POSITION OF THE POLARITY DESIRED FOR THE PROCESS BEING USED.
     2.	 SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE.
     3.	 SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 5.  TURN POWER SOURCE OFF.
    P
    
    BOLT TO CABLES
    FROM NA-5
    WIRE CONTACTASSEMBLY
    N.B.
    N.B.
    CLEVELAND, OHIO U.S.A. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    							INSTALLATIONA-13A-13
    NA-5
    FIGURE A.12 – CONNECTION OF NA-5 (ALL) TO A SAM-650 ENGINE WELDER. 
    NOTE:	 TO CHANGE POLARITY, TURN POWER OFF, AND
    	 POSITION THE SWITCH ON POWER SOURCE TO 
    	 PROPER POLARITY.  REFER TO NA-5 
    	 OPERATING MANUAL FOR REQUIRED 
    	 NA-5 CONTROL BOX  POLARITY CONNECTIONS.
    
    FOR ADDITIONAL INSTALLATION INSTRUCTIONS, SEE NA-5 OPERATING MANUAL.
    SAM  POWER SOURCE SETTINGS
    
    FOR SUB ARC:
    1.	 SET THE ELECTRODE POLARITY SWITCH TO THE POLARITY DESIRED FOR THE
    	  PROCESS BEING USED.
    2.	 SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE.
    3.	 SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 7. 
    4.	 CONNECT THE TAP CABLE TO THE 300-575, MAX, SLOPE STUD.
    FOR ALL OPEN ARC PROCESSES:
    1.	 SET THE ELECTRODE POLARITY SWITCH TO THE POLARITY DESIRED FOR THE
    	 PROCESS BEING USED.
    2.	 SET THE TOGGLE SWITCH TO CONSTANT VOLTAGE.
    3.	 SET THE CONSTANT VOLTAGE CONTROL TO NUMBER 5.
    4.	 CONNECT THE TAP CABLE TO THE 450-MAX, MED SLOPE STUD. NA-5 SETTINGS
    FOR SUB ARC:
    1.	 RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN S.
    2.	 WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A.
    FOR ALL OPEN ARC PROCESSES:
    1.	 RED LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN F.
    2.	 WHITE LEAD ON VOLTAGE PC BOARD IS CONNECTED TO PIN A.
     TURN POWER SOURCE OFF.
    
    N.A.	 REMOVE SAM PORTABLE FIELD CONTROL AND CONNECT NA-5 CONTROL CABLE.
    N.B.	 WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DUTY CYCLE\
     OF IMMEDIATE AND FUTURE APPLICATIONS.
    N.C.	 EXTEND LEAD #21 USING #14 OR LARGER INSULATED WIRE PHYSICALLY SUITABLE F\
    OR THE INSTALLATION.  AN S-16586- [ ] REMOTE VOLTAGE-SENSING WORK
    	 LEAD IS AVAILABLE FOR THIS PURPOSE.  CONNECT IT DIRECTLY TO THE WORK PIE\
    CE, KEEPING IT SEPARATE FROM THE WELDING WORK CABLE CONNECTION 
    	 TO THE WORK PIECE.  FOR CONVENIENCE, THIS EXTENDED #21 LEAD SHOULD BE TA\
    PED ALONG THE WELDING WORK CABLE.
    N.D.	 TAPE UP BOLTED CONNECTION.
    N.E.	 CONNECT THE NA-5 CONTROL CABLE GROUNDING LEAD TO THE FRAME TERMINAL MARK\
    ED          NEAR THE POWER SOURCE TERMINAL STRIP.  THE POWER
    	  SOURCE MUST BE PROPERLY GROUNDED.
    N.F.	 IF USING AN OLDER K-215 CONTROL CABLE: CONNECT LEAD #76 TO #75 ON TERMIN\
    AL STRIP, CONNECT LEADS #75 AND #77 TO #76 ON TERMINAL STRIP.
    N.G.	 ON EARLIER SAM MACHINES, #1 TERMINAL WAS ALSO ON THE TERMINAL STRIP.
    N.H.	 FOR PROPER NA-5 OPERATION, THE ELECTRODE CABLES MUST BE SNUGGED UNDER TH\
    E CLAMP BAR ON THE LEFT SIDE OF THE NA-5 CONTROL BOX.
    PP
    P
    .
    .
    TAP POWER SOURCE
    TO NA-5 INPUTCABLE PLUG
    BOLT TO CABLES
    FROM NA-5 WIRE CONTACT
    ASSEMBLY
    CLEVELAND, OHIO U.S.A. 
    Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOCReturn to Master TOCReturn to Master TOCReturn to Master TOC Return to Master TOC 
    						
    All Lincoln manuals Comments (0)