Page 31

31 • Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the “Room Temperature Setting
button”.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as
shown in below table by pressing on the temperature up or temperature down button at remote control.
• The operation mode judging temperature...

Page 32

32
11.5.3. 7 Minutes Time Save Control
•The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the compres-
sor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
11.5.4. 60 Seconds Forced Operation
•Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached...

Page 33

33
11.5.7. Dew Prevention control
• To prevent dew formation at indoor unit discharge area.
• This control will be activated if:-
- Cooling mode or Quiet mode.
- Remote Control setting temperature is less than 25°C.
- Fan speed is at Low or QLo.
- Room temperature is constant (±1°C) for 30 minutes.
- Compressor is continuously running.
• Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in...

Page 34

34
11.5.8. 30 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 30 minutes and the intake air temperature falls between the compres-
sor OFF temperature (A) and compressor ON temperature (B) during the period.
• This is to maintain the room temperature as set. Despite of this, it is to prevent a wrong judgement of intake air temperature due
to poor installation near the sensor area.
11.5.9. Compressor Overload Protection Control
Outdoor Fan Control
• If the...

Page 35

35
11.5.13. Anti Cold Draft Control
• This operation is to prevent the Cold Draft during Heating mode operation.
• The operation will start when compressor OFF (Thermo OFF) during Heating operation.
• For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
• After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
• Anti Cold Draft Control will stop when:
- Intake temperature...

Page 36

36
11.5.14. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
• Normal Deicing 
Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice opera-
tion. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for 50 sec.
continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating...

Page 37

37 Normal Deicing Time Diagram
Overload Deicing Time Diagram 

Page 38

38
11.6. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
11.6.1. Fan Speed Rotation Chart
11.6.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
- Fan speed rotates in the range of Hi, Me and Lo-.
- Deodorizing Control will be activated.
Fan Speed (rpm) CS-A9EKH CS-A12EKH
S Hi 1300 1320
Hi 1210 1300
Me 1000 1120
H Lo 890 860
C Lo 830 800
Lo- 780 750
S Lo 750 700
SS Lo 300 300
Q S...

Page 39

39 • Auto Fan Speed during cooling operation:
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop,...

Page 40

40 • Auto Fan Speed during Heating operation.
1. Indoor fan will rotate in the range of SLo → Me according to the heat exchanger temperature.
11.6.3. Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
• There are 3 types of fan speed settings: Lo, Me, Hi.
11.7. Outdoor Fan Speed Control
•There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressor and the outdoor fan will...