Page 61
1-55 1. Specifications 1-8 Noise Criterion Curves Outdoor Units REMARKS:1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an nechoic room. NOTE To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER...
Page 62
1-56 1. Specifications 1-9 Increasing the Fan Speed Jumper cable Jumper cable Electrical component box (At shipment) (Jumper cable installed) 2159_M_I Fan motor socket Fan motor 900 Air Flow (CFM) External Static Pressure 0 50 0 0.1 0.2 0.3 0.4 0.5 150 700 500 300 Limit line L 100 1982_U_I HHH (Pa) (inAq) Limit lineHT Air Flow (CFM) External Static Pressure 0 50 0 0.1 0.2 0.3 0.4 0.5 0.6 0.8 150 200 500 1000 Limit line LHHHHT 100 1983_U_I (inAq)(Pa) Limit line NOTE HT : Using the booster cable H : At...
Page 63
1-57 1. Specifications 1-10 Air throw distance chart 4-Way Cassette Type 03 7 10131720 0 3 7 10 13HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) AXIS AIR VELOCITY 2111_X_I Model: 26 Type Model: 36, 42 Type : LOUVER ANGLE 20 in Cooling mode : LOUVER ANGLE 60 in Heating mode Condition Fan Speed : Hi Room air temp. : 80F DB in cooling mode 68F DB in heating mode 03 7 10131720 0 3 7 10 13HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) AXIS AIR...
Page 64
1-58 1. Specifications 1-10 Air throw distance chart Wall Mounted Type COOLING - - - - - HEATING FAN SPEED HIGH HIGH ROOM AIR TEMP. 80°F70°F FLAP ANGLE 0°, 22.5°, 45°45°, 67.5° Axis air velocity (ft./sec.) Vertical distance (ft.) Horizontal distance (ft.) 10 135 0 Model: 26 Type 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
Page 65
1-59 1. Specifications 1-10 Air throw distance chart Ceiling Type Model: 26 Type 0371013172023262933 0 3 7 10 13 17HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.)2115_T_I AXIS AIR VELOCITY Model: 36 Type 2116_T_I AXIS AIR VELOCITY 0371013172023262933 0 3 7 10 13 17HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) Model: 42 Type 2117_T_I AXIS AIR VELOCITY FAN SPEEDHEATING COOLING ROOM AIR TEMP. LOUVER ANGLEHIGH HIGH 68 ° F 80°F 54 °– 7° : COOLING...
Page 66
1-60 1. Specifications 1-11. ELECTRICAL WIRING General Precautions on Wiring (1) as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2)Before wiring, confirm the rated voltage of the unit Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. (3) unit must be grounded. (4) with the wiring system diagram. Wrong wiring may cause the unit...
Page 67
1-61 1. Specifications Inter-unit power wiringPower wiring Inter-unit control wiring 8P terminal board Outdoor Unit Indoor Unit U1 U2 1 2 G L1 L2 Wiring System Diagrams Basic wiring diagram for standard control NOTE Disconnect switch may be needed by the National/Local code. ALWAYS COMPLY WITH NATIONAL AND LOCAL CODE REQUIREMENTS. NOTE (1) (2) (B), (C) have no polarity. But for other wiring, respect polarity. Be sure to connect as shown in the Wiring System Diagram. (3)Refer to Recommended Wire Length...
Page 68
1-62 1. Specifications WARNINGLoose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. How to Connect Wiring to the Terminal For stranded wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the stranded wiring about 3/8 in. (Fig. 1-1) (2) Using a Phillips head screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using a ring...
Page 69
1-63 1. Specifications 1-12. Installation Instructions 1. Tubing SizeOutdoor Unit Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2. Table 1-1 Indoor unit type 26, 36 types 42 type...
Page 70
1-64 1. Specifications CAUTION 1. This unit requires no additional refrigerant charge up to 100 ft. tubing length. In case of more than 100 ft., additional refrigerant charge is required. Refer to Table 1-3. 2. In case of multi type installation, indoor units should be installed within the same room. If multi type indoor units are installed in different rooms, temperature control may develop problems because thermostat operation must follow the thermostat condition of 1 indoor unit only (the main...