Home > Panasonic > Ventilation > Panasonic Ventilating Fan Fv08vkml1 Installation Instructions

Panasonic Ventilating Fan Fv08vkml1 Installation Instructions

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Ventilating Fan Fv08vkml1 Installation Instructions online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							READ AND SAVE THESE INSTRUCTIONS.R
    Please
    readthese
    instructionscarefullybeforeattempting
    toinstall,
    operate or service the Panasonic Ventilating Fan. Failure to comply
    with instructions could result in personal injury and/or property
    damage. Please retain this booklet for future reference.
    15-16
    16 8-107
    Table of Contents
    Unpacking
    General Safety Information
    14VInstallation( Wooden Header )
    12
    14
    Installation( In Existing Construction )VI
    IInstallation( Joist Mounting- )I
    III( -Joist Mounting )I Installation
    Maintenance
    Practical Guide to Installation
    16Product Service
    2Please Read Prior To Installing This Fan
    13Installation
    ( Between Joist Mounting )IV
    11-12II( Joist Mounting- )II Installation
    Model No.FV-08VKML1
    FV-08VKSL1
    Ventilating Fan
    FV-08VKML1
    FV-08VKSL1
    Thank you very much for having purchased our Ventilating Fan.
    Description
    Dimensions
    Specifications64 3
    3
    Supplied Accessories
    Wiring Diagram
    Switch Indication
    Operation
    5
    5
    6 3 
    						
    							than the minimum ENERGY STAR requirements.
    5
    efficient
    FV-08VKSL1
    FV-08VKML1 only).
    ventilating 
    						
    							These Panasonic ventilating fans use a sirocco fan with dolphin-shaped blades driven by brushless direct
    current motor powered by an integral transformer. The motor is designed to have long operating life, high
    dynamic response, higher speed ranges with saving energy. The grille can be quickly detached from the main
    unit. A damper for preventing air counterflow is provided. The blower uses a high-capacity sirocco fan developed
    to reduce the noise level.
    SUPPLIED ACCESSORIES UNPACKING
    DESCRIPTION
    The lighting unit is an energy-saving, lighting device which uses two 18W fluorescent lamps and produces
    almost the same illumination as a standard 100W incandescent lamp.
    This Panasonic ventilating fan (FV-08VKML1) is equipped with a motion sensor that runs automatically when
    motion is detected. It is user-adjustable to operate 0.5~60 minutes after motion is no longer detected.
    Quantity Appearance
    Part name
    Screw
    (ST4.2X8)I21
    Grille
    Suspension
    bracketI
    Suspension
    bracketII
    1
    1
    2Screw
    (ST4.2X12)II
    Screw
    (ST4.2X16)III
    1
    Machine screw
    (M4X8)2
    Quantity Appearance
    Part name
    2
    1
    1
    18W
    Fluorescent
    lamp
    4W
    Night lamp
    Lighting unit
    1Suspension
    bracketIII
    6Long screw
    (ST4.2X20)
    FV-08VKML1
    FV-08VKSL1
    1
    Unpack and carefully remove unit from carton.
    Refer to the Supplied Accessories list to verify that all parts are present. 
    						
    							DIMENSIONS
    Unit: ( )inches mm
    (For 16 inches on center joists, only use suspension bracket , for 19.2 inches on center joists, only use
    suspension bracket , If more than 19.2 inches on center, use suspension bracket & .)I
    III II III
    Junction box cover
    Junction box
    Lighting unit
    Fluorescent lamp
    Night lamp
    Part name No.Part name
    No.
    1
    2
    3
    4
    5
    67
    8
    9
    10
    11
    Damper Fan bodyAdaptor
    Grille
    Suspension bracket
    Bracket cover
    12Sensor unit
    FV-08VKSL1 FV-08VKML1
    6
    13 330()
    10 1/4 261()
    3 1/2 (90)
    8
    9
    10
    37/8 98()10 1/4 (261)
    12 1/8 (307)
    6
    13 330()
    10 1/4 261()
    3 1/2 (90)
    8
    9
    10
    37/8 98()10 1/4 (261)
    12 1/8 (307)
    12
    11
    113 1/2 (90)1 (25)
    5 1/8 130()
    7 7/8 200() 126() 23/470()
    3 1/4 (81)
    13 1/4~15 1/2 ( 336~394 )
    16 1/2~18 3/4 ( 419~480 )
    21 1/4~23 1/2 ( 540~597 )
    7
    3 1/2 (90)1 (25)
    5 1/8 130()
    7 7/8 200() 126() 23/470()
    3 1/4 (81)
    13 1/4~15 1/2 ( 336~394 )
    16 1/2~18 3/4 ( 419~480 )
    21 1/4~23 1/2 ( 540~597 )
    7
    4 3/5 (116)
    4 3/5 (116) 
    						
    							SWITCH INDICATION
    30
    40 50 60 70 80
    Delay Time
    [min]
    WI ING DIAG AMRRWI ING DIAG AMRR
    Low speed air-volume preset switch positions
    Air Volume
    [cfm]
    High/Low delay time preset switch positions
    0.5
    1235
    10 2030
    60
    Factory setting : 20 minutes
    Position 0 : Use for factory test only.
    0
    Factory setting : 50 cfm
    Switch indications
    on blower unit
    Low speed air vol-
    ume preset switch High / Low delay time
    preset switch
    FV-08VKML1
    FV-08VKSL1
    White
    White
    Position   use for factory test only.
    CFM 
    						
    							Duct
    diameter
    (inches)
    416.5 7.5()
    (cfm)(rpm)
    FV-08VKML1
    FV-08VKSL1
    9.5
    7.7
    6.5
    5.8
    5.0
    70
    60
    50
    40
    30
    700
    666
    647
    628
    620 
    						
    							CAUTION:
    1. For general ventilating use only. Do not use to exhaust
    hazardous or explosive materials and vapors.
    2. Not for use in cooking area. (Fig. B)
    3. This product must be properly grounded.
    45o45o
    Floor
    Do not install above or(Cooking area)
    inside this area
    equipmentCooking
    Fig. B
    3. Follow all local electrical and safety codes, as well as the National Electrical Codethe Occupation Safety and Health Act (OSHA). (NEC) and
    4. Always disconnect the power source before working on or near the fan, motor or
    light fixture.
    5. Protect the power cord from sharp edges, oil, grease, hot surfaces, chemicals or
    other objects.
    6. Do not kink the power cord.
    7. Do not install the unit where ducts are configured as shown in Fig. A.
    8. Provide suction parts with proper ventilation.
    GENE AL SAFETY INFO MATIONRRGENE AL SAFETY INFO MATIONRR
    1. Do not install this ventilating fan where air temperature may exceed 40 C (104 F).oo
    2. Make certain that the electric service supply voltage is AC 120V, 60 Hz.
    Fig. AAdaptor Prohibited
    9. This unit is UL listed for use over a bathtub or shower when installed in a GFCI
    protected branch circuit.
    10. This product has a fluorescent lamp that contains mercury. Disposal may be regulated
    in your community due to environmental considerations. For disposal or recycling
    information, please contact your local authorities or the Electronics Industries
    Alliance: http://www.eiae.org
    Prohibited
    Prohibited
    Prohibited
    WARNING:
    To reduce the risk of fire, electric shock or injury to persons, observe the following;
    A. Use this unit only in the manner intended by the manufacturer. If you have any questions, contact to
    the manufacturer.
    B. Installation work and electrical wiring must be done by qualified person(s) in accordance with all
    applicable codes and standards, including fire-rated construction.
    C. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney)
    of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturers
    guideline and safety standards such as those published by the National Fire Protection Association
    (NFPA), and the American Society for Heating Refrigeration and Air Conditioning Engineers
    (ASHRAE) and the local code authorities.
    D. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
    E. Ducted fans must always be vented to the outdoors.
    F. Do not use this unit with any solid-state control device. Solid state controls may cause harmonic distortion
    which can cause motor humming noise.
    G. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting
    means to prevent power from being switched on accidentally. When the service disconnecting means
    cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
    H. Not to be installed in a ceiling thermally insulated to a value greater than R40. (This is required for
    installation in Canada only.) 
    						
    							8
    2-Screw (ST4.2X8)I
    Suspension bracketIIISuspension bracketII
    INSTALLATION JOIST MOUNTING-II()INSTALLATION JOIST MOUNTING-II()
    1. Insert the suspension bracket into the fan body and
    adaptor. (select the suspension bracket as shown below)
    Spacing A on center joists
    Insert Suspension bracket
    12 inches
    16 inches
    19.2 inches vertical joists
    24 inchesRefer to Fig. 1-1
    Refer to Fig. 1-2
    Refer to Fig. 1-3
    Refer to Fig. 1-4
    If spacing A on center joists is 24 inches, connect
    suspension bracket and (C4 mark to C4 mark)
    as shown below :II III
    Joists
    A
    Suspension
    bracketIII
    Suspension
    bracketI
    Fig.1-1
    Fig.1-2
    Fig.1-3
    Fig.1-4
    Fan body
    Fan body
    Suspension
    bracketI
    Suspension
    bracketIII
    Suspension
    bracketII
    Suspension
    bracketI
    Fan body
    Suspension
    bracketISuspension
    bracketIII
    Fan body
    Tape Damper
    Adaptor
    IMPORTANT :Remove the tape from damper and adaptor
    before installation. As shown below: 
    						
    							Fan body
    4 Long screws (ST4.2X20)
    Joist
    9
    Fig.2-2
    INSTALLATION JOIST MOUNTING-II( ) CONTINUEDINSTALLATION JOIST MOUNTING-II( ) CONTINUED
    3. Install the suspension bracket to joists by using long
    screws (ST4.2X20) and secure it to the fan body by
    using screw (ST4.2X12) (Fig.3)II
    Junction box cover
    Fig.4
    ConduitCircular duct
    4. Remove junction box cover and secure conduit or
    stress relief to junction box knock-out hole. (Fig.4)
    CAUTION:Mount junction box cover carefully so that lead
    wires are not pinched.
    6. Install a circular duct and secure it with duct tape or
    clamps.
    Fig.2-1
    2. Install the suspension bracket and the flange of fan body
    to joists by using long screws (ST4.2X20) ( If spacing A
    between joists is 12 inches, install the flange of fan body
    according to Fig.2-1, others according to Fig.2-2 to install
    the product)
    Duct tape
    Fig.3
    2 Long screws
    (ST4.2X20)
    Screw (ST4.2X12)II
    Joist
    Joist
    5. Refer to wiring diagram of page 5.
    Follow all the local electrical safety codes. As well as
    the National Electrical Code (NEC).
    Using UL approved wire nuts, connect house power
    wires to ventilating fan wires:
    black to black; white to white; green to green;
    Connect the two red wires to the switch for the speed
    control. Replace the junction box cover. (Fig.4)
    Joist
    Wire nutGreen wires
    Lead wiresRed wires
    ConduitJunction box
    2 Long screws
    (ST4.2X20)Fan body
    Junction box
    Wire nut Lead wires
    Conduit
    Green wires 
    						
    							10 7/8(275)
    10 7/8(275)
    Ceiling
    Sensor unitGrille
    Ceiling
    Fig.6-2
    Gloves
    INSTALLATION JOIST MOUNTING-II( ) CONTINUEDINSTALLATION JOIST MOUNTING-II( ) CONTINUED
    8. Insert the plug connector into the receptacle ,
    and secure the lighting unit to the fan
    body with 1 screw (ST4.2X16) and 2 machine
    screws (M4X8). (Fig.5)II II
    III
    9. Insert the fluorescent lamps and s cure the night
    lamp into the lighting unit. (Fig.5)e
    12. Insert mounting springs into the slots as shown and
    mount grille to fan body. (FV-08VKSL1) (Fig.7)Lighting unit
    7. Finish ceiling work. Ceiling hole should be aligned
    with the edge of the flange. (Fig.5)
    10
    Slot
    Grille Mounting spring
    Lighting unit
    Ceiling
    Fig.7
    10. Insert mounting spring into the slot as shown and
    adjust high /low delay time preset switch and low
    speed air volume preset switch. Refer to switch
    indication of page 5 (FV-08VKML1) (Fig.6-1)
    11. Insert the sensor unit into the housing of the grille
    and insert other mounting spring into the slot as
    shown and mount grille to fan body (FV-08VKML1)
    (Fig.6-2, Fig.6-3)
    Grille
    Mounting springCeiling
    Fig.6-3
    Gloves
    Gloves
    Fig.5
    Screw (ST4.2X16)III Machine screw
    (M4X8)
    4 W Night lamp
    Fluorescent lamps
    inches (mm)
    Fig.6-1
    Sensor unit
    Ceiling
    GrilleLighting unit
    Plug connectorII
    Machine screw
    (M4X8)
    CAUTION:
    Mount grille carefully so that lead wires are not
    pinched. 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Ventilating Fan Fv08vkml1 Installation Instructions