Home > Trane > Air Conditioner > Trane Intellipak 2 Service Manual

Trane Intellipak 2 Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Intellipak 2 Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Unit Startup
    RT-SVX24K-EN111
    internally connected for clockwise rotation with the
    incoming power supply phased as A, B, C.
    Proper electrical supply phasing can be quickly
    determined and corrected before starting the unit by using
    an instrument such as an Associated Research Model 45
    Phase Sequence Indicator and following the steps below:
     [ ] Turn the field supplied disconnect switch that
    provides power to terminal block or to the unit
    mounted disconnect switch to the “Off” position.
     [ ] Connect the phase sequence indicator leads to the terminal
     block or unit mounted disconnect switch as
    follows:
     [ ] Close the disconnect switch or circuit protector switc
     h that provides the supply power to the unit
    terminal block or the unit mounted disconnect switch.
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT
     DISCONNECT SWITCH.
     [ ] Observe the ABC and CBA phase indicator lights on the
     face of the sequencer. The ABC indicator light will
    glow if the phase is ABC. If the CBA indicator light
    glows, open the disconnect switch or circuit protection
    switch and reverse any two power wires.
     [ ] Restore the main electrical power and recheck the phasing.
     If the phasing is correct, open the disconnect
    switch or circuit protection switch and remove the
    phase sequence indicator.
    Voltage Supply and Voltage Imbalance
    Voltage Supply
    Electrical power to the unit must meet stringent
    requirements for the unit to operate properly. Measure
    each leg (phase-to-phase) of the power supply. Each
    reading must fall within the utilization range stamped on
    the unit nameplate. If any of the readings do not fall within
    the proper tolerances, notify the power company to
    correct this situation before operating the unit.
    Voltage Imbalance
    Excessive three phase voltage imbalance between phases
    will cause motors to overheat and eventually fail. The
    maximum allowable voltage imbalance is 2%. Measure
    and record the voltage between phases 1, 2, and 3 and
    calculate the amount of imbalance as follows:
    % Voltage Imbalance = where;
    AV (Average Voltage) =
    V1, V2, V3 = Line Voltage Readings
    VD = Line Voltage reading that deviates the farthest from the average voltage.
    Example: If the voltage readings of the supply power
    measured 221, 230, and 227, the average volts would be:
    VD (reading farthest from average) = 221
    The percentage of Imbalance equals:
    The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much
    imbalance between phases can equal as much as a 20%
    current imbalance with a resulting increase in motor
    winding temperatures that will decrease motor life. If the
    voltage imbalance is over 2%, notify the proper agencies
    to correct the voltage problem before operating this
    equipment.Phase Sequence Leads Unit Power Terminal
    Black (phase A) L1
    Red (phase B) L2
    Yellow (phase C) L3
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    WARNING
    Live Electrical Components!
    During installation, testing, servicing and
    troubleshooting of this product, it may be necessary to
    work with live electrical components. Have a qualified
    licensed electrician or other individual who has been
    properly trained in handling live electrical components
    perform these tasks. Failure to follow all electrical
    safety precautions when exposed to live electrical
    components could result in death or serious injury.
    100xAV VD –
    AV
    ----------------
    -
    Vo
    lt1 Volt2 Volt3
    ++
    3
    -------------------------------------------------
    211 230 227 ++
    3
    -----------------------------------
    - 226 A v g=
    100
    x226 221 –
    226
    --------------------
    - 2.2 pe r c e n t= 
    						
    							Unit Startup
    11 2RT-SVX24K-EN
    Table 37. Service test guide for component operation — part I of II
    Component 
    Being Tested COMPONENT CONFIGURATION
    Supply Fan Return
    Fan Exhaust
    Fan Condenser
    Fans Heat Stages
    Compressor Stage
    1231234
    COMPRESSOR
    90 - 105 Ton
    1A  OFF    OFF   OFF  ALL OFF  OFF OFF OFF  ON OFF OFF OFF
    1B  OFF    OFF   OFF  ALL OFF  OFF OFF OFF  ON ON OFF OFF
    2A  OFF    OFF   OFF  ALL OFF  OFF OFF OFF  OFF OFF ON OFF
    2B  OFF    OFF   OFF  ALL OFF  OFF OFF OFF  OFF OFF ON ON120 - 162 Ton
    1A  OFF    OFF   OFF 1A-On /1B-Off/1C-Off/1D-Off  
    2A-Off/2B-Off/2C-Off/2D-Off   OFF OFF OFF  ON OFF OFF OFF
    1B  OFF    OFF   OFF  ALL OFF   OFF OFF OFF  ON ON OFF OFF
    2A  OFF    OFF   OFF 1A-Off/1B-Off/1C-Off/1D-Off 
    2A-On/2B-Off/2C-Off/2D-Off   OFF OFF OFF  OFF OFF ON OFF
    2B  OFF    OFF   OFF  ALL OFF   OFF OFF OFF  OFF OFF ON ON  CONDENSER FANS 
     90 - 105 Ton  — Air Cooled
    1A OFF OFF OFF 1A-On /1B-Off/1C-Off                                      
    2A-Off/2B-Off/2C-Off  OFF OFF OFF   OFF OFF OFF   OFF
    1B & 1C OFF OFF OFF 1A-Off/1B-On /1C-On                                    
    2A-Off/2B-Off/2C-Off  OFF OFF OFF   OFF OFF OFF   OFF
    2A OFF OFF OFF 1A-Off/1B-Off/1C-Off                                                                    \
                                                                            
    2A-On /2B-Off/2C-Off  OFF OFF OFF   OFF OFF OFF   OFF
    2B & 2C OFF OFF OFF 1A-On/1B-Off/1C-Off                                                                    \
               
    2A-Off /2B-On /2C-On  OFF OFF OFF   OFF OFF OFF   OFF120 - 150 Ton — Air Cooled
    1A OFF OFF OFF  1A-On /1B-Off/1C-Off/1D-Off                  
    2A-Off/2B-Off/2C-Off/2D-Off  OFF OFF OFF   OFF OFF OFF   OFF
    1B OFF OFF OFF  1A-Off/1B-On/1C-Off/ 1D-Off                  
    2A-Off/2B-Off/2C-Off/ 2D-Off  OFF OFF OFF   OFF OFF OFF   OFF
    1C & 1D OFF OFF OFF  1A-Off/1B-On/1C-On/ 1D-On                
    2A-Off/2B-Off/2C-Off/ 2D-Off  OFF OFF OFF   OFF OFF OFF   OFF
    2A OFF OFF OFF  1A-Off/1B-Off/1C-Off/ 1D-Off                  
    2A-On /2B-Off/2C-Off & 2D-Off  OFF OFF OFF   OFF OFF OFF   OFF
    2B & 2C OFF OFF OFF  1A-Off/1B-On/1C-Off/ 1D-Off                  
    2A-Off/2B-On/2C-On/ 2D-Off  OFF OFF OFF   OFF OFF OFF   OFF
    2D OFF OFF OFF  1A-Off/1B-On/1C-Off 1D-Off                  
    2A-Off/2B-Off/2C-Off/ 2D-On  OFF OFF OFF   OFF OFF OFF   OFF
      100, 118, 128, 140, 162 Ton — Evaporative Condensing
    1A OFF OFF OFF 1A 0 -100 %                                                            
    2A  OFF  OFF OFF OFF   OFF OFF OFF   OFF
    2A OFF OFF OFF 1A   OFF                                                                
    2A 0 - 100%  OFF OFF OFF   OFF OFF OFF   OFF 
    						
    							Unit Startup
    RT-SVX24K-EN11 3
     SUPPLY FAN  ON    ON    OFF    ALL OFF    OFF OFF OFF   OFF OFF OFF   OFF
     RETURN FAN  ON    ON    N/A    ALL OFF   OFF OFF OFF   OFF OFF OFF   OFF
     EXHAUST FAN  OFF    N/A    ON    ALL OFF   OFF OFF OFF   OFF OFF OFF   OFF
     GAS HEAT 
    (Full Capacity)    ON     ON  OFF
     ALL OFF   ON ON ON  OFF OFF OFF   OFF
    STAGE 1  ON     ON  OFF  ALL OFF   ON OFF ON  OFF OFF OFF   OFF
    STAGE 2  ON     ON  OFF  ALL OFF   OFF  ON N/A  OFF OFF OFF   OFF
    Full Modulating  ON     ON  OFF  ALL OFF  10% - 90% OFF OFF OFF   OFF
     ELECTRIC HEAT  ON   ON   OFF    ALL OFF   ON ON ON  OFF OFF OFF   OFF
    Stage 1 ON  ON   OFF    ALL OFF  ON OFF OFF  OFF OFF OFF   OFF
    Stage 2 ON  ON   OFF    ALL OFF  OFF ON OFF  OFF OFF OFF   OFF
    Stage 3 ON  ON   OFF    ALL OFF  OFF OFF ON  OFF OFF OFF   OFF
     HYDRONIC HEAT  OFF    OFF    OFF    ALL OFF   100% Select   OFF OFF OFF   OFF
    OUTSIDE AIR  DAMPERS  OFF    OFF    OFF  
     ALL OFF   100% Select   OFF OFF OFF   OFF
     EXHAUST  DAMPERS  OFF    OFF    OFF  
     ALL OFF   100% Select   OFF OFF OFF   OFF
    EVAP COND Sump Pump  OFF    OFF    OFF    ALL OFF   100% Select   OFF OFF OFF   OFF
    Sump Heater  OFF    OFF    OFF    ALL OFF   100% Select   OFF OFF OFF   OFF
    Table 37. Service test guide for component operation — part I of II (continued)
    Component 
    Being Tested COMPONENT CONFIGURATION
    Supply Fan Return
    Fan Exhaust
    Fan Condenser
    Fans Heat Stages
    Compressor Stage
    1231234 
    						
    							Unit Startup
    11 4RT-SVX24K-EN
    Table 38. Service test guide for component operation — part II of II
    Component 
    Being Tested Component Configuration
    Occ
    Unocc Relay Sump Pump Sump Heater
    Econo
    Damper Exhaust
    Damper VFD
    Output
    COMPRESSOR
    90 - 105 Ton
    1A Closed Closed 0%Default OFFOFF
    1B Closed Closed 0%Default OFFOFF
    2A Closed Closed 0%Default OFFOFF
    2B Closed Closed 0%Default OFFOFF
    120 - 162 Ton
    1A Closed Closed 0%Default OFFOFF
    1B Closed Closed 0%Default OFFOFF
    2A Closed Closed 0%Default OFFOFF
    2B Closed Closed 0%Default OFFOFF
     CONDENSER FANS 
     90 - 105 Ton  — Air Cooled
    1A Closed Closed 0%Default OFFOFF
    1B & 1C ClosedClosed 0%Default OFFOFF
    2A Closed Closed 0%Default OFFOFF
    2B & 2C ClosedClosed 0%Default OFFOFF
    120 - 150 Ton — Air Cooled
    1A Closed Closed 0%Default OFFOFF
    1B Closed Closed 0%Default OFFOFF
    1C & 1D ClosedClosed 0%Default OFFOFF
    2A Closed Closed 0%Default OFFOFF
    2B & 2C ClosedClosed 0%Default OFFOFF
    2D Closed Closed 0%Default OFFOFF
      100, 118, 128, 140, 162 Ton — Evaporative Cooled
    1A Closed Closed 0%Default OFFOFF
    2A Closed Closed 0%Default OFFOFF
     SUPPLY FAN  ClosedClosed 100%Unocc OFFOFF
     RETURN FAN ClosedClosed 100%Default OFFOFF
     EXHAUST FAN ClosedClosed 100%Default OFFOFF
     GAS HEAT 
    (Full Capacity)   Closed
    Closed 100%Unocc OFFOFF
    Stage 1 ClosedClosed 100%Unocc OFFOFF
    Stage 2 ClosedClosed 100%Unocc OFFOFF
    Full Modulating ClosedClosed 100%Unocc OFFOFF
     ELECTRIC HEAT ClosedClosed 100%Unocc OFFOFF
    Stage 1 ClosedClosed 100%Unocc OFFOFF
    Stage 2 ClosedClosed 100%Unocc OFFOFF
    Stage 3 ClosedClosed 100%Unocc OFFOFF
     HYDRONIC HEAT ClosedClosed 100%Default OFFOFF
    OUTSIDE AIR  DAMPERS Closed
    Closed 100%Default OFFOFF
     EXHAUST DAMPERS ClosedClosed 100%Default OFFOFF
    EVAP COND Sump Pump ClosedClosed 100%Default ONOFF
    Sump Heater ClosedClosed 100%Default OFFON 
    						
    							Unit Startup
    RT-SVX24K-EN11 5
    Service Testing—Evaporative Condenser
    Components
    From the Compressor and Condenser Service Menu
    screens—Head Pressure Control: AUTO or Head Pressure
    Control: MANUAL
    1. Select:
    Head Pressure Control: MANUAL
    Note: All outputs, Sump Control, Fan Stage Control and
    Fan speed Control (per circuit where specified), will
    be available for ON/OFF, OPEN/CLOSED, 0-100%
    manual settings considering the stipulations in
    Table 39 :
    Notes:
     1. Sump Freeze Protection is active during AUTO but is inactive in service 
    test modes (Head Pressure Control set to MANUAL). 
     2. Water Treatment Drain Request will be ignored in Service Test.
    Verifying Proper Fan Rotation
    Note: Fans controlled by VFD will run in the correct
    direction even if phasing is incorrect.
    1. Ensure that the “System” selection switch at the remote panel is in the “Off” position and the “Fan”
    selection switch for constant volume units is in the
    “Auto” position. (VAV and SZVAV units do not utilize a
    “Fan” selection input.)
    2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal
    block 1TB1 or the unit mounted disconnect switch
    1S14.
    3. Turn the 115 volt control circuit switch 1S2 and the 24 v
     olt control circuit switch 1S3 to the “On” position.
    4. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the appropriate programming manual for
    applications for the SERVICE TEST screens and
    programming instructions. 5. Use
    Table37, p.11 2to program the unit Fans for
    operation by scrolling through the displays. All of the
    F
     ans (Supply, Exhaust, and Condenser fans) can be
    programmed to be “On”, if desired.
    Refer to Figure69, p.11 6for the condenser fan
    locations and the Human Interface designator.
    6. Once the configuration for the Fans is complete, press the
     NEXT key until the LCD displays the “Start test in
    __Sec.” screen. Press the + key to designate the delay
    before the test is to start. This service test will begin
    after theTEST START key is pressed and the delay
    designated in this step has elapsed. Press the ENTER
    key to confirm this choice.
    7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before
    the fans will begin to operate.
    8. Check the supply fan and the exhaust fans (if equipped) for
     proper rotation. The direction of rotation is
    indicated by an arrow on the fan housings. Check the
    condenser fans for clockwise rotation when viewed
    from the top.
    Table 39. Service test guide component operation—
    ev
     aporative condenser
    COMPONENT 
    BEING TESTED Requirements (ON) Requirements 
    (OFF)
    Compressors Sump minimum level 
    switch must be closed for 
    a minimum of five minutes No Requirements
    Sump Pump Sump minimum level 
    switch must be closed for 
    a minimum of five minutes No Requirements
    Condenser Fans No Requirements No Requirements
    Fill Valve Solenoid No Requirements No Requirements
    Drain Valve Actuator No Requirements No Requirements Sump Heater No Requirements No Requirements
    WARNING
    Rotating Components!
    During installation, testing, servicing and
    troubleshooting of this product it may be necessary to
    work with live and exposed rotating components. Have
    a qualified or licensed service individual who has been
    properly trained in handling exposed rotating
    components, perform these tasks. Failure to follow all
    safety precautions could result in rotating components
    cutting and slashing technician which could result in
    death or serious injury. 
    						
    							Unit Startup
    11 6RT-SVX24K-EN
    If all of the fans are rotating backwards;
    a. Press the STOP key at the Human Interface Module
    in the unit control panel to stop the fan operation.
    b. Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the
    open position while working at the unit.
    c. Interchange any two of the field connected main power wires at the unit terminal block or the factory
    mounted disconnect switch. Note:
    Interchanging “Load” side power wires at the fan
    contactors will only affect the individual fan
    rotation. Ensure that the voltage phase sequence at
    the main terminal block or the factory mounted
    disconnect switch is ABC as outlined in the
    “Electrical Phasing” section.
    If some of the fans are rotating backwards;
    a. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.
    b. Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the
    open position while working at the unit.
    c. Interchange any two of the fan motor leads at the contactor for each fan that is rotating backwards.WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    Figure 69. Air-cooled (90-150 tons)/evaporative (100-162 tons) condenser fan locations with human interface designator
    2B92B11
    2B102B12
    2B14
    2B15
    2B13 2B16
    2B9
    1K9
    01K1
    01B2
    2B11 1K10
    4K1
    21B2
    11K1
    31B2
    21K1
    41B2
    2B15 1K12
    2B16 1K1
    Condenser Fan Motor Designator Condenser Fan contactor 
    Designator
    120 TON
    130 TON 
    150 TON
    2B5 2B6
    2B5 1K4*
    *1K1
    6B2
    Condenser Fan Motor Designator Condenser Fan contactor 
    Designator
    100 TON
    118 TON 
    128 TON
    140 TON
    162 TON
    *Note: 2B5 and 2B6 are initiated with operation of 
    1K4 and 1K1 compressor contactors. 
    						
    							Unit Startup
    RT-SVX24K-EN11 7
    System Airflow Measurements
    Constant Volume Systems
    1. Ensure that the “System” selection switch at the
    remote panel is in the “Off” position and the “Fan”
    selection switch for constant volume units is in the
    “Auto” position.
    2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT
     DISCONNECT SWITCH.
    3. Turn the 115 volt control circuit switch and the 24 volt control
     circuit switch to the “On” position.
    4. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the appropriate programming manual for CV
    applications for the SERVICE TEST screens and
    programming instructions.
    5. Use Table37, p.11 2to program the Supply Fan for
    operation by scrolling through the displays.
    6. Once the configuration for the Fan is complete, press the
     NEXT key until the LCD displays the “Start test in
    __Sec.” screen. Press the +key to designate the delay
    before the test is to start. This service test will begin
    after theTEST START key is pressed and the delay
    designated in this step has elapsed. Press the ENTER
    key to confirm this choice.
    7. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before
    the fans will begin to operate.
    8. With the system in the SERVICE MODE and the supply fan
     rotating in the proper direction, measure the amperage at the supply fan contactors. If the
    amperage exceeds the motor nameplate value, the
    static pressure is less than design and the airflow is too
    high. If the amperage is below the motor nameplate
    value, static pressure may be too high and CFM may be
    too low. To determine the actual CFM (± 5%);
    a. Measure the actual fan RPM
    b.
     Calculate the Theoretical BHP
    Actual Motor Amps X Motor HP Motor Nameplate Amps
    c. Plot this data onto the appropriate Fan Performance Curve beginning with Figure 62, p. 100. Where the
    two points intersect, read straight down to the CFM
    line.
    Use this data to assist in calculating a new fan drive if the
    CFM is not at design specifications.
    An alternate method with less accuracy is to measure the static pressure drop across the evaporator coil.This can be
    accomplished by;
    a. drilling a small hole through the unit casing on eachside of the coil.
    Note: Coil damage can occur if care is not taken when
    drilling holes in this area.
    b. Measure the difference between the pressures at both locations.
    c. Plot this value onto the appropriate pressure drop curve beginning with Figure 71, p. 120. Use the data
    in Table 40, p. 127 (Component Static Pressure
    Drops) to assist in calculating a new fan drive if the
    CFM is not at design specifications.
    d. Plug the holes after the proper CFM has been established.
    9. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the fan operation.
    Variable Air Volume Systems
    1. Ensure that the “System” selection switch at theremote panel is in the “Off” position.
    2. Close the disconnect switch or circuit protector switch that
     provides the supply power to the unit terminal
    block or the unit mounted disconnect switch.
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    WARNING
    Live Electrical Components!
    During installation, testing, servicing and
    troubleshooting of this product, it may be necessary to
    work with live electrical components. Have a qualified
    licensed electrician or other individual who has been
    properly trained in handling live electrical components
    perform these tasks. Failure to follow all electrical
    safety precautions when exposed to live electrical
    components could result in death or serious injury. 
    						
    							Unit Startup
    11 8RT-SVX24K-EN
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT DISCONNECT SWITCH.
    3. Turn the 115 volt control circuit switch and the 24 volt
    control circuit switch to the “On” position.
    4. Open the Human Interface access door, located in the unit
     control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the appropriate Programming Manual for
    VAV applications for the SERVICE TEST screens and programming instructions.
    Use T
    able 37, p. 112 to program the following system
    components for operation by scrolling through the
    displays:
    Supply Fan,
    Variable Frequency Drive (100% Output, if applicable), RTM Occ/Unocc Output (Unoccupied)
    5. Once the configuration for the components is complete,
     press the NEXT key until the LCD displays
    the “Start test in __Sec.” screen. Press the +key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START key
    is pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    6. Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before
    the fan will begin to operate.
    7. With the VFD at 100% and the supply fan operating at full
     airflow capability, measure the amperage at the
    supply fan contactors. If the amperage exceeds the
    motor nameplate value, the static pressure is less than
    design and the airflow is too high. If the amperage is
    below the motor nameplate value, static pressure may be too high and CFM may be too low.To determine the
    actual CFM (± 5%);
    a. Measure the actual fan RPM
    b.
     Calculate the Theoretical BHP
    Actual Motor Amps X Motor HP Motor Nameplate Amps
    c. Plot this data onto the appropriate Fan Performance Curve beginning with Figure 62, p. 100. Where the
    two points intersect, read straight down to the CFM
    line.
    Use this data to assist in calculating a new fan drive if the
    CFM is not at design specifications.
    An alternate method with less accuracy is to measure the static pressure drop across the evaporator coil.This can be
    accomplished by:
    a. drilling a small hole through the unit casing on eachside of the coil.
    Note: Coil damage can occur if care is not taken when
    drilling holes in this area.
    b. Measure the difference between the pressures at both locations.
    c. Plot this value onto the appropriate pressure drop curve beginning with Figure 71, p. 120. Use the data
    in Table 40, p. 127 (Component Static Pressure
    Drops) to assist in calculating a new fan drive if the
    CFM is not at design specifications.
    d. Plug the holes after the proper CFM has been established. Press the STOP key at the Human
    Interface Module in the unit control panel to stop
    the fan operation.
    8. Press the STOP key at the Human Interface Module in
     the unit control panel to stop the fan operation.
    Exhaust Airflow Measurement (Optional)
    1. Close the disconnect switch or circuit protectorswitch that provides the supply power to the units
    terminal block or the unit mounted disconnect
    switch.
    HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
    UNIT DISCONNECT SWITCH.
    2. Turn the 115 volt control circuit switch and the 24 volt control
     circuit switch to the “On” position.
    3. Open the Human Interface access door, located in the
     unit control panel, and press the SERVICE MODE
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury.
    WARNING
    Live Electrical Components!
    During installation, testing, servicing and
    troubleshooting of this product, it may be necessary to
    work with live electrical components. Have a qualified
    licensed electrician or other individual who has been
    properly trained in handling live electrical components
    perform these tasks. Failure to follow all electrical
    safety precautions when exposed to live electrical
    components could result in death or serious injury.
    WARNING
    Hazardous Voltage!
    Disconnect all electric power, including remote
    disconnects before servicing. Follow proper lockout/
    tagout procedures to ensure the power can not be
    inadvertently energized. Failure to disconnect power
    before servicing could result in death or serious injury. 
    						
    							Unit Startup
    RT-SVX24K-EN11 9
    key to display the first service screen. Refer to the
    latest edition of the appropriate programming
    manual for applications for the SERVICE TEST
    screens and programming instructions.
    4. Use Table37, p.11 2to program the following system
    components for operation by scrolling through the
    displays:
    Exhaust Fan,
    Exhaust Dampers (100% Open, if applicable),
    Outside air dampers (100% Open),
    Variable Frequency Drive (100%, if applicable), RTM Occ/Unocc Output (Default)
    5. Once the configuration for the components is complete,
     press the NEXT key until the LCD displays
    the “Start test in __Sec.” screen. Press the +key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START
    key is pressed and the delay designated in this step
    has elapsed. Press the ENTER key to confirm this
    choice.
    6. Press the TEST START key to start the test. Remember
    that the delay designated in step 5 must elapse before
    the fans will begin to operate.
    7. With the exhaust dampers open and the exhaust fan operating
     at full airflow capability, measure the
    amperage at the exhaust fan contactor. If the
    amperage exceeds the motor nameplate value, the
    static pressure is less than design and airflow is too
    high. If the amperage is below the motor nameplate
    value, static pressure may be too high and CFM may be
    too low. To determine the actual CFM (± 5%);
    a. Measure the actual fan RPM
    b.
     Calculate the Theoretical BHP
    Actual Motor Amps X Motor HP Motor Nameplate Amps
    Use appropriate figures beginning with Figure 71, p. 120
    to calculate a new fan drive if the CFM is not at design
    specifications.
    8. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the fan operation.
    TRAQ™ Sensor Airflow Measurement
    (Optional with all units equipped with an
    economizer)
    1. Open the Human Interface access door, located in theunit control panel, and press the SERVICE MODE key to
    display the first service screen. Refer to the latest
    edition of the appropriate programming manual for
    applications for the SERVICE TEST screens and
    programming instructions.
    2. Use Table37, p.11 2to program the following system
    components for Economizer operation by scrolling
    through
     the displays;
    Supply Fan (On)
    Outside
     air dampers (Selected % Open)
    Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)
    Outside Air CFM Setpoint
    Outside Air Pre-Heater Operation (if applicable)
    3. Once the configuration for the components is complete,
     press the NEXT key until the LCD displays
    the “Start test in __Sec.” screen. Press the +key to
    designate the delay before the test is to start. This
    service test will begin after the TEST START key
    is pressed and the delay designated in this step has
    elapsed. Press the ENTER key to confirm this choice.
    4. Press the TEST START key to start the test. Remember that
     the delay designated in step 3 must elapse before
    the fans will begin to operate.
    5. With the unit operating in the “TEST MODE”,
     the
    amount of outside air flowing through the TRAQ
    sensor can be viewed by switching to the “STATUS
    MENU” screen “OA CFM.
    6. Scroll to the “ECONOMIZER ENABLE/ECONOMIZER POSITION”
     screen by pressing the “NEXT” key and
    read the corresponding damper opening percentage
    (%).
    7. Press the STOP key at the Human Interface Module in the
     unit control panel to stop the unit operation.
    WARNING
    Live Electrical Components!
    During installation, testing, servicing and
    troubleshooting of this product, it may be necessary to
    work with live electrical components. Have a qualified
    licensed electrician or other individual who has been
    properly trained in handling live electrical components
    perform these tasks. Failure to follow all electrical
    safety precautions when exposed to live electrical
    components could result in death or serious injury. 
    						
    							Unit Startup
    120RT-SVX24K-EN
    Performance Data
    Supply Fan with or without Variable
    Frequency Drive
    Figure 70. Supply fan performance LOW CFM — 90/100 tons, 25” supply fan
    Figure 71. Supply fan performance STANDARD CFM — 90/100 and 105/118 tons, 36” supply fan 
    						
    All Trane manuals Comments (0)