Home > AirComm Corporation > Other > AirComm Corporation Cessna Citation 550 560 Maintenance Manual

AirComm Corporation Cessna Citation 550 560 Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual AirComm Corporation Cessna Citation 550 560 Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 74 AirComm Corporation manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							 Products, Inc. 
                                                              Maintenance Manual 
     
    21-50-00 
    May 15/95 Page 1 
      AIR CONDITIONING SYSTEM - SYSTEM DESCRIPTION 
     
    1. GENERAL 
     
    The air conditioning system for the Cessna 500 series aircraft consists of a refrigerant 
    R134a vapor cycle cooling system.  This system allows the co-pilot to control cooling 
    for a comfortable aircraft cabin.  Figure 1 shows a general arrangement of the air 
    conditioning system. 
     
    The co-pilots control panel contains the cooling system ON/OFF/FAN switch, the 
    FWD fan LOW/HIGH switch, the AFT fan OFF/LOW/HIGH and a blue A/C system ON 
    indicator.  
     
    2. COOLING SYSTEM 
     
    The cooling or air conditioning system, as designed and manufactured by Keith 
    Products for the Cessna 500 Series aircraft, is a vapor cycle type cooling system 
    using refrigerant R134a.  The system is electrically operated using the aircraft 28 VDC 
    electrical system and is operable in all normal flight modes up to 18,000 feet MSL.  Air 
    conditioning may be operated with ground external power or the aircraft electrical 
    system providing 28 vDC to the non-essential buss. 
     
    The major components of the system are the compressor/condenser assembly with 
    blower, and two evaporator/cabin blower units.  Refrigerant plumbing and electrical 
    systems connect the major component to provide a closed loop system.   
     
    The compressor/condenser assembly is mounted either forward of the rear baggage 
    door; or in the baggage compartment. The compressor drive and condenser fan drive 
    are both driven by a common, double shafted motor which turns at approximately 
    4500 RPM.  The compressor is belt driven from the shortest shaft while the condenser 
    fan is attached directly to the longer motor shaft.  Condenser cooling air (ambient air) 
    is drawn in through a cutout in either underside of the engine pylon or the right side of 
    the fuselage of the aircraft by the condenser fan.  The air passes over the compressor 
    and drive motor to provide cooling airflow for those components prior to passing 
    through the condenser coil to remove heat from the system.  After passing through the 
    condenser coil, the air is exhausted to the outside through an exhaust duct located 
    either on the underside of the fuselage; or through a cutout on the left side of the 
    aircraft.  The compressor takes low pressure refrigerant gas and compresses it to a 
    higher pressure and temperature.    
       
    						
    							 Products, Inc. 
                                                                Maintenance Manual 
     
    21-50-00 
    May 15/95 Page 2 
    An evaporator/blower unit is located in the aft cabin at the end of the recessed isle 
    (at floor level) within the aircraft interior.  It provides cooling airflow for the cabin 
    area of the interior.  A forward evaporator is located at the cockpit floor and 
    provides cooling airflow to the flight crew through a floor mounted air outlet or 
    through dedicated ducting at the pilots and co- pilots control stick.  Both 
    evaporators are of a design wherein the cabin air is drawn into the evaporator coil 
    and the fan then delivers the conditioned air to the cabin.  This recirculating system 
    continues to dry and cool the air each time it passes through the evaporator.  
    Moisture removed from the air by the cold coil (condensate) is collected within the 
    evaporator housing and is forced overboard.  Each evaporator is equipped with a 
    thermal expansion valve which regulates the amount of refrigerant entering the coil 
    to provide optimum cooling effect.  The evaporator blowers can be operated in the 
    FAN position to re-irculate cabin air without cooling.  Each blower is operated from 
    an independent fan speed control. 
     
    The plumbing which connects the compressor, condenser and the evaporators, 
    consists of rubber based hoses with a nylon barrier.  The fittings are permanently 
    swaged onto the hoses.  All fittings are o-ring type connections with sealant on the 
    fitting mating surfaces to prevent refrigerant leaks.  Two R134a service valves are 
    located near the compressor/condenser pallet assembly.  They are sized differently 
    to avoid incorrect cross-connecting when gaining access to the plumbing for system 
    recharging. 
     
    On the ground, the electrical system allows operation of the air conditioning system 
    from either aircraft power or from an active GPU prior to engine start. System safety 
    features include electrical interlocking and load shedding.  In flight, the air 
    conditioning system can be operated from the aircraft electrical system only with 
    both generators on line.  Loss of either generator will automatically shed the air 
    conditioning system electrical loads except for the minimal loads of the evaporator 
    fans.  
     
    The entire air conditioning refrigerant loop is protected against over pressure 
    conditions by two separate safety devices.  The first device is a binary high/low 
    pressure switch that activates in the event of an overpressure and is on the 
    compressor discharge port.  This switch will open at approximately 350 PSIG and 
    will interrupt power to the compressor control circuit.  This in turn will de-energize 
    the compressor motor relay and remove power to the compressor motor.  The 
    refrigerant system pressures will then drop. The switch will also interrupt power to 
    the compressor control circuit under low pressure conditions.   The second 
    overpressure safety device is a fuse plug which will vent the system refrigerant 
    safely overboard in the event of a system pressure in excess of 425 PSIG.  It is 
    located on the receiver/drier.   
      
    						
    							 Products, Inc. 
                                                              Maintenance Manual 
     
    21-50-00 
    May 15/95 Page 3 
     
     
     
     
     
    Figure 1. Air Conditioning System General Arrangement 
      
    						
    							 Products, Inc. 
                                                               Maintenance Manual 
     
               21-50-01 
    May 15/95 
    Page 1 
      
     ELECTRICAL
     
     
    DESCRIPTION AND OPERATION 
     
    1. GENERAL 
     
    The air conditioning system consists of one high energy compressor/condenser 
    drive motor and two centrifugal evaporator blowers (Fwd) and (Aft).  The system is 
    controlled by a mode switch with Air Conditioning Off and Fan Only position.  Each 
    evaporator has a high and low position switch.  A blue indicator light will illuminate 
    whenever the compressor/condenser is selected.  The system incorporates a binary 
    pressure switch to sense an over pressure or under pressure condition in the 
    system.   
     
    The air conditioning system in controlled by a Logic Card which monitors generator, 
    GPU and battery inputs to ensure operation or shedding of the system if a fault 
    exists.  
     
    The system is protected by a 15 amp control and blower breaker and a 100 amp 
    breaker for the compressor/condenser drive motor. 
     
    This section of the maintenance manual describes the electrical system and 
    presents electrical troubleshooting procedures.  An Illustrated Parts List is included 
    in Figure 1.   
     
    2. LOAD/SHED DESCRIPTION 
     
    The system incorporates a logic control PC card that enables the system to operate 
    or be shed under various conditions.  The table below shows operation under 
    various conditions. 
     
    CONDITIONS
         EVAP FANS   COMP/COND 
    Gnd Power Cart/On    On      On 
    Gnd Power Cart Connected/Off    On      Off      
    Battery Only     On   Off 
    One Generator on Ground    On      On 
    Both Generators on Ground    On      On 
    Refrigerant Over/Under Pressure    On      Off 
    One Generator in Flight    On      Off 
    Both Generators in Flight    On      On  
    						
    							 Products, Inc. 
                                                                Maintenance Manual 
     
    21-50-01 
    May 15-95 
    Page 101 
     
      
    TROUBLESHOOTING 
     
    1. GENERAL 
     
    The following procedures are used for troubleshooting the electrical system and the 
    electrical interfaces with the other assemblies of the air conditioning system. 
     
    2.  TOOLS AND EQUIPMENT 
     
     
    Designation  
    Ref. No.  
    Qty  
    Remarks 
     
     
    Service Pressure Gauge  
    Comm. Avail.  
    1  
    None 
     
    Multi-meter  
    Comm. Avail.  
    1  
    None 
     
    28vdc Source  
      
    A/R  
    None 
     
    3. ELECTRICAL TROUBLESHOOTING PROCEDURES (REF. IPL Fig. 1) 
     
    NOTE:   Always attach a service gauge set to system prior to beginning trouble 
    shooting to insure proper refrigerant charge is present. 
     
    A.  Air Condition Selected, Compressor/Condenser Motor Does Not Turn. 
     
    1.  Connect service pressure gauge to service ports located near 
    compressor/condenser pallet. 
    2.  Connect ground power to aircraft. 
    3.  Select air conditioning system to ON. 
    4.  Check that load shed start conditions in the Description and Operation 
    paragraph are met. 
    5.  Check for power at comp/cond relay located on the pallet assembly, if not 
    present check 100A circuit breaker (4).  Replace if necessary. 
    6.  Check continuity of pressure switch (Ref. 21-50-03 IPL Fig. 1, item 11).  If 
    no continuity and gauge set reads adequate pressure, replace pressure 
    switch.  Switch can be removed without discharge of refrigeration.  Back 
    switch off in a counter clockwise direction.  Re-install in reverse order.  
    Lubricate o-ring in switch per 21-50-02 page 202.  
    						
    							 Products, Inc. 
                                                                Maintenance Manual 
     
    21-50-01 
        May 15/95 
    Page 102 
     
      
    7.  Check for power at motor .  If power is present, proceed to step 8.  If 
    power is not present on either pin and load/shed conditions of step 4 are 
    met, check power on the load shed unit at connector Pin 1.  If power is 
    present, system problem exists in load shed system start unit.  If power is 
    not present, check 15 amp CB (3) and mode switch (26). 
    8.  Fault is isolated to compressor/condenser motor.  Unit should be 
    replaced. 
    9.  Select air conditioning OFF, remove electrical power, disconnect service 
    gauge when troubleshooting is complete. 
     
    B.   FWD Evaporator Blower will not operate in high or low speed.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power and ground present at fan wire splices and GND terminal 
    strip.   If power and ground are present, blower motor (Ref. 21-50-04 IPL 
    Fig.1, item 15, or IPL Fig. 2, item 24) has failed.  
    4.  Select air conditioning OFF, remove electrical power. 
    5.  Remove blower assy from aircraft.  Remove the four screws attaching the 
    motor to the housing.  Using a 1/8 allen wrench remove blower wheel 
    (use extreme care not to bend blower wheel). Cut power wires at splice 
    and remove Gnd wire from GND terminal. Install new motor in reverse 
    order. 
     
    C.  FWD Evaporator Blower will not operate in the low speed setting.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power is present at wire EVAP-FL (at splice).  If power is 
    present, the low speed resistor (Ref. 21-50-04 IPL Fig. 1, item 17, or IPL 
    Fig. 2, item 23) has failed. 
    4.  Select air conditioning OFF, remove electrical power. 
    5.  Remove blower assembly and using a #21 drill remove the two rivets 
    securing the resistor. Cut the wires at the splice and remove GND wire 
    from GND terminal.  Install new resistor in reverse order. 
     
    D.   AFT Evaporator Blower will not operate in high or low speed.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power and ground present at fan wire splices and GND terminal 
    strip.   If power and ground are present, blower motor (Ref. 21-50-05 IPL 
    Fig.1, item 15) has failed.  
    4.  Select air conditioning OFF, remove electrical power.  
    						
    							 Products, Inc. 
                                                               Maintenance Manual 
     
     
    20-50-01 
    May 15/95 
    Page 103 
       
    5.  Remove blower assy from aircraft.  Remove the four screws attaching the 
    motor to the housing.  Using a 1/8 allen wrench remove blower wheel  (use 
    extreme care not to bend blower wheel). Cut power wires at splice and 
    remove Gnd wire from GND terminal. Install new motor in reverse order. 
     
    E.  AFT Evaporator Blower will not operate in the low speed setting.  
    1.  Connect ground power to aircraft. 
    2.  Select air conditioning system to ON. 
    3.  Check if power is present at wire EVAP-AL (at splice).  If power is present, 
    the low speed resistor (Ref. 21-50-05 IPL Fig. 1, item 9) has failed. 
    4.  Select air conditioning OFF, remove electrical power. 
    5.  Remove blower assembly and using a #21 drill remove the two rivets 
    securing the resistor. Cut the wires at the splice and remove GND wire from 
    GND terminal.  Install new resistor in reverse order. 
     
     
     
     
     
     
     
     
     
        
    						
    							 Products, Inc. 
                                                                Maintenance Manual 
     
    21-50-01 
    May 15/95 
    Page 1001 
      
     
     
    Figure 1.  Electrical System 
    						
    							 Products, Inc. 
                                                                Maintenance Manual 
     
    21-50-01 
    May 15/95 
    Page 1002 
      
     
     
    FIG. ITEM  
     PART 
     NUMBER  
     NOMENCLATURE  
     EFFECT  
     UNITS  
     PER  
     ASSY 
     
    1 1 
     
     2 
     
    3 
     
    4 
     
    5 
     
    6 
     
    7 
     
    8 
     
    9 
     
    10 
     
    11 
     
    12 
     
    13 
     
    14 
     
      
    82-02-106 
     
    JBS11001-1 
     
    MS3320-15 
     
    MS25361-100 
     
    ES32036-1 
     
    JBS5005-1 
     
    JBS2030-3 
     
    JBS2048-3 
     
    MS25181-2 
     
    MS25036-101 
     
    ES50162-1 
     
    MS25036-125 
     
    MS25036-157 
     
    MS25036-123 
     
      
    Electrical Installation  
     
    Light (Blue) 
     
    Circuit Breaker 
     
    Circuit Breaker 
     
    Grommet 
     
    Compressor/Condenser 
     
    FWD Evaporator 
     
    AFT Evaporator 
     
    Butt Connector 
     
    Terminal 
     
    Lamp 
     
    Terminal  
     
    Terminal 
     
    Terminal 
     
      
     
      
     RF 
     
    1  
     
    1 
     
    1 
     
    1 
     
    1 ref 
     
    1 ref 
     
    1 ref 
     
    7 
     
    5 
     
    1 
     
    1 
     
    1 
     
    1 
     
     
     
     
     
     
     
    Air Conditioning System - Electrical System 
    IPL FIGURE 1  
    						
    							 Products, Inc. 
                                                               Maintenance Manual 
     
    21-50-01 
    May 15/95 
    Page 1003 
      
    FIG. ITEM  
     PART 
     NUMBER  
     NOMENCLATURE  
     EFFECT  
     UNITS  
     PER  
     ASSY 
     
     15 
     
     16 
     
     17 
     
     18 
     
     21 
     
    22 
     
    23 
     
    24 
     
    25 
     
    26  
    MS25036-106 
     
    MS25036-108 
     
    84-00-07-8 
     
    ES57016-3 
     
    ES53010-3 
     
    MS25036-124 
     
    MS25036-156 
     
    ES55077-2 
     
    ES57016-6 
     
    ES57016-5  
    Terminal 
     
    Terminal 
     
    Load Shed Assy 
     
    Switch 
     
    Connector 
     
    Terminal 
     
    Terminal 
     
    Terminal 
     
    Switch 
     
    Switch 
     
     
     
     
     
     
     
     
     
     
     
      
      
     15 
     
     3 
     
     1 
     
     1 
     
     1 
     
    1 
     
    1 
     
    1 
     
    1 
     
    1 
     
     
    Air Conditioning System - Electrical System 
    IPL FIGURE 1  
    						
    All AirComm Corporation manuals Comments (0)

    Related Manuals for AirComm Corporation Cessna Citation 550 560 Maintenance Manual