41 8. Route the control wires inside the junction box on the top of the water heater; see Figure 3 on page 8 to locate the junction box. Use an available knock-out to route the wires inside the junction box. 9. Install field supplied control wiring and conduit as required by national and local codes between the water heater’s junction box and the external supervisory control. Connect the wiring from the external control to the control wires...
Page 42
42 This water heater is provided with a properly rated/sized and certified combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on page 15 for information on replacement and other requirements. Water Damage Hazard Temperature-Pressure Relief V alve discharge pipe must terminate at adequate drain. CAUTION Install a discharge pipe between the T&P valve discharge opening and a suitable floor drain. Do not connect...
Page 43
43 TABLE 15 Water Temperature °F (°C) Time for 1st Degree Burn (Less Severe Burns) Time for Permanent Burns 2nd & 3rd Degree (Most Severe Burns) 110 (43) (normal shower temp.) 116 (47) (pain threshold) 116 (47) 35 minutes 45 minutes 122 (50) 1 minute 5 minutes 131 (55) 5 seconds 25 seconds 140 (60) 2 seconds 5 seconds 149 (65) 1 second 2 seconds 154 (68) instantaneous 1 second (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)The water heaters covered in this manual...
Page 44
44 CONTROL SYSTEM OPERATION Tank Temperature 103°F Operating Set Point 120°F Status: Heating MENU HELP GASOFF ON MANUF ACTURER / MODEL INFORMATIONLCD Screen Information Display Status Icons 3 Operational buttons: enter/exit menus, select menu items, activate adjustment modes, confirm/cancel changes. Up & Down buttons: navigate menus, adjust user settings Title Bar Enable/Disable Switch Operational buttons are multi functional. Their current function is defined by the text that appears directly...
Page 45
45 STATUS ICONS The Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described in the table below. See Figure 54 on page 57 and the Sequence Of Operation on page 56. TABLE 16 IconDescription Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in response to water temperature in the storage tank as sensed from the Upper and Lower Temperature Probes. See Figure 3 on...
Page 46
46 OPERATING STATES The current operational state of the water heater is displayed on the Desktop screen as the "Status." The common operational states are described in the table below. See Figure 54 on page 57 and the Sequence Of Operation on page 56. TABLE 17 StateDescription Standby The water heater is not in an active heating cycle. IE: the Tank Temperature is at or above the Operating Set Point. Input Verification The control system is conducting a diagnostic check at the beginning of a...
Page 47
47 USER SETTINGS & CONTROL SYSTEM MENUS TEMPERATURES MENU Operating Set Point And Differential Adjustment The Operating Set Point is adjustable from 90°F (42°C) to 180°F (82°C). The factory setting is 120°F (49°C). The Differential is adjustable from 2° to 20°. The factory setting is 8°. These user settings are accessed from the Temperatures menu. The following instructions will explain how to adjust these settings and navigate the control system menus. When the...
Page 48
48 TEMPERATURES MENU (CONT) DESCRIPTION/ACTIONDISPLAY • Differential - Adjustable user setting that changes the tank temperature differential with a range of 2° to 20°F. The factory setting is 8°F. • Tank Temperature - non adjustable - control system sensed temperature (averaged from upper and lower temperature probes). • Tank Probe Offset - adjustable user setting, range -5° to +5° (factory setting 0°). NOTE: These settings should only be used if the hot water...
Page 49
49 DISPLAY SETTINGS DESCRIPTION/ACTIONDISPLAY Select Display Settings from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains adjustable display options for viewing information on the UIM’s LCD screen. Use the Up & Down Buttons to navigate the menu. • Temperature Units - Adjustable user setting that changes temperature units display to Celsius °C or Fahrenheit °F. • Backlight Delay - Adjustable user setting that...
Page 50
50 CURRENT FAULT DESCRIPTION/ACTIONDISPLAY Select Current Fault from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. Use the Up & Down Buttons to navigate the menu. This menu contains the current Fault or Alert error message. The time the Fault or Alert message occurred appears directly below. A brief description of what causes the particular Fault or Alert...