Home > American Water Heater > Gas Heater > American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual

American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							41
    8. Route  the  control  wires  inside  the  junction  box  on  the  top 
    of  the  water  heater;  see  Figure  3  on  page  8  to  locate  the 
    junction  box.  Use  an  available  knock-out  to  route  the  wires 
    inside the junction box.
    9.  Install  field  supplied  control  wiring  and  conduit  as  required 
    by  national  and  local  codes  between  the  water  heater’s 
    junction  box  and  the  external  supervisory  control.  Connect 
    the wiring from the external control to the control wires inside 
    the junction box using wire nuts and electrical tape.
    10.  Connect  the  control  wiring  to  a  set  of  dry  contacts  on  the 
    external control. Follow the control manufacturer’s instructions 
    for making connections.
    11.  Restore power to the water heater.
    12.  From  the  water  heaters  UIM  “Heater  Information  Screen” 
    select    “Use  External  Enable”  and  change  to  “Yes”.  See 
    Figure 3 on page 8 to locate the UIM.
    NOTE:  Whenever  the  external  control  opens  the  set  of  dry 
    contacts  used,  water  heating  operation  will  be  disabled. 
    Whenever  the  external  control  closes  the  set  of  dry  contacts 
    used, water heating operation will be enabled. A diagonal line and 
    circle appears over the thermometer icon on the UIM when water 
    heating operation is disabled. See the Status Icons descriptions 
    in Table 16 on page 45.
    NOTE:  Ensure  the  water  heater  is  protected  from  freezing 
    temperatures when water heating operation is disabled. Damage 
    to  the  water  heater  caused  by  freezing  temperatures  is  not 
    covered under the limited warranty.
    WATER LINE CONNECTIONS
    The  water  piping  installation  must  conform  to  these  instructions 
    and  to  all  local  and  national  code  authority  having  jurisdiction. 
    Good practice requires that all heavy piping be supported.
    Read  and  observe  all  requirements  in  the  following  sections 
    before installation of the water piping begins:
    1.  Mixing Valves on page 14.
    2.  Dishwashing Machines on page 14.
    3.  Temperature-Pressure Relief Valve on page 15.
    4.  Closed Systems and Thermal Expansion on page 14.
    5.  For  multiple  water  heater  installations  see  Water  Piping 
    Diagrams beginning on page 68.
    WATER PIPING DIAGRAMS
    This  manual  provides  detailed  water  piping  diagrams  for  typical 
    methods  of  application  for  the  water  heaters,  see  Water  Piping 
    Diagrams beginning on page 68.
    The  water  heater  may  be  installed  by  itself,  or  with  a  separate 
    storage  tank.  When  used  with  a  separate  storage  tank,  the 
    circulation may be either by gravity or by means of a circulating 
    pump.  When  a  circulating  pump  is  used,  it  is  important  to  note 
    that the flow rate should be slow so that there will be a minimum 
    of turbulence inside the water heater storage tank.
    Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 
    circulating line on the outlet side of the pump. Never throttle flow 
    on  the  suction  side  of  a  pump.  See  the  Water  Piping  Diagrams 
    beginning on page 68.
    NOTE: In addition to the factory installed Temperature-Pressure 
    Relief  Valve  (T&P  valve)  on  the  water  heater,  each  remote 
    storage tank that may be installed and piped to a water heating 
    appliance  must  also  have  its  own  properly  sized,  rated  and 
    approved Temperature-Pressure Relief Valve installed. 
    Call  the  toll  free  technical  support  phone  number  listed  on  the 
    back cover of this manual for further assistance in sizing a T&P 
    valve for remote storage tanks.
    NOTE:  If  electrical  connections  are  made  directly  to  the 
    terminal  block  remove  the  jumper  wires  before  making 
    connection.
    5.  Connect the ground wire from the power supply to the green 
    jumper  wire  or  the  ground  terminal  location  inside  of  the 
    junction  box  located  on  top  of  the  water  heater.  If  the  green 
    jumper  wire  is  used,  make  the  connection  inside  of  the 
    junction box with a properly sized wire nut and wrap electrical 
    tape  around  the  wire  nut  and  wire  end.  See  junction  box 
    Figure 49 and wiring diagram Figure 58 on page 66.
    6.  Replace the junction box cover when connections are complete.
    NOTE: Do not apply power to the water heater before installation 
    is complete and the water heater is filled with water.
    Heater Wiring(Factory Installed)
    MOVGround
    Ground
    Terminal
    Jumper Wire
    L1
    Neutral
    Figure 49
    ENABLE/DISABLE CIRCUIT  
    ( For Building Management Systems)
    The  water  heaters  covered  in  this  manual  are  equipped  with 
    an  enable/disable  circuit  for  use  with  field  supplied  external 
    supervisory controls such as time clocks or Building Management 
    Systems.  The  enable/disable  circuit  may  be  used  to  disable 
    heating operation during periods when the building is unoccupied 
    or there is no demand for hotwater.
    To  use  the  enable/disable  circuit  it  must  first  be  activated  by 
    selecting the “Use External Enable” from the UIM. Field supplied 
    wiring  is  then  installed  between  the  water  heater’s  CCB  and  a 
    set  of  “dry  contacts”  (no  voltage  or  load)  on  the  field  supplied 
    external control.
    NOTE:  The  water  heater’s  enable/disable  circuit  is  a  switching 
    circuit  only:  Do  not  apply  external  voltage  or  connect  any  load 
    (IE:  relay  coil)  to  this  circuit.  This  will  damage  the  CCB  circuit 
    board and is not covered under the limited warranty.
    CONNECTING AN EXTERNAL SUPERVISORY CONTROL
    The enable/disable circuit is accessed from the CCB’s J17 plug 
    inside the CCB enclosure; see Figure 3 on page 8 to locate the 
    CCB enclosure and Figure 57 on page 65 for the CCB layout. 
    Install field wiring to the enable/disable circuit:
    1.  Turn  off  power  at  the  water  heater’s  enable/disable  switch 
    and the breaker that supplies power to the water heater.
    2.  Locate the CCB enclosure.
    3.  Carefully  remove  the  Temperature  Probe  connectors  and 
    CCB enclosure cover.
    4.  Locate pins 1 and 2 on the CCB J17 plug. See Figure 57 on 
    page 65.
    5.  Connect  the  two  field  supplied  control  wires  to  pins  1  and  2 
    on the CCB J17 plug. 
    6.  Thread  the  control  wires  out  of  the  CCB  enclosure  with  the 
    other  wiring  and  carefully  replace  the  CCB  enclosure  cover. 
    Ensure all wiring is routed through the intended area provided 
    for strain relief. Ensure no wiring is being pinched.
    7.  Reinstall the CCB enclosure cover.  
    						
    							42
    This  water  heater  is  provided  with  a  properly  rated/sized  and 
    certified  combination  temperature  -  pressure  (T&P)  relief  valve 
    by the manufacturer. See Temperature-Pressure Relief Valve on 
    page 15 for information on replacement and other requirements.
    Water Damage Hazard
    Temperature-Pressure Relief V alve discharge
    pipe must terminate at adequate drain.
    CAUTION
    Install a discharge pipe between the T&P valve discharge opening 
    and  a  suitable  floor  drain.  Do  not  connect  discharge  piping 
    directly  to  the  drain  unless  a  6”  (15.2  cm)  air  gap  is  provided. 
    To  prevent  bodily  injury,  hazard  to  life,  or  property  damage,  the 
    relief  valve  must  be  allowed  to  discharge  water  in  adequate 
    quantities should circumstances demand. If the discharge pipe is 
    not connected to a drain or other suitable means, the water flow 
    may cause property damage.
    T&P Valve Discharge Pipe Requirements:
    •  Shall not be smaller in size than the outlet pipe size of the 
    valve, or have any reducing couplings or other restrictions.
    •  Shall not be plugged or blocked.
    •  Shall not be exposed to freezing temperatures.
    •  Shall be of material listed for hot water distribution.
    •  Shall be installed so as to allow complete drainage of both 
    the Temperature-Pressure Relief Valve and the discharge 
    pipe.
    •  Must terminate a maximum of six inches above a floor 
    drain or external to the building. In cold climates, it is 
    recommended that the discharge pipe be terminated at an 
    adequate drain inside the building.
    •  Shall not have any valve or other obstruction between the 
    relief valve and the drain.
    THERMOMETERS (NOT SUPPLIED)
    Thermometers are installed in the water piping system as a means 
    of  detecting  the  temperature  of  the  hot  water  supply  at  critical 
    points  in  the  system.  Field  supplied  thermometers  should  be 
    obtained and installed. See Water Piping Diagrams on page 68.
    WATER (POTABLE) HEATING AND SPACE HEATING
    1. All  water  piping  components  connected  to  the  water  heater 
    that  are  for  space  heating  applications  shall  be  suitable  for 
    use with potable water.
    2.  Toxic  chemicals,  such  as  those  used  for  boiler  treatment, 
    must NEVER be introduced into this system.
    3.  The  water  heaters  covered  in  this  manual  may  never  be 
    connected  to  any  existing  heating  system  or  component(s) 
    previously used with non-potable water heating appliance.
    4.  When  the  system  requires  water  for  space  heating  that 
    exceed safe temperatures at domestic water fixtures a mixing 
    valve must be installed, see Mixing Valves on page 14.
    5.  These  water  heaters  cannot  be  used  in  space  heating 
    applications only.
    T&P VALVE DISCHARGE PIPE
    Explosion Hazard
    Temperature-Pressure Relief  Valve
    must comply with  ANSI Z21.22-
    CSA 4.4 and  ASME code.
    Properly sized temperature-
    pressure relief valve must be
    installed in opening provided.
    Can result in overheating and
    excessive tank pressure .
    Can cause serious injury or death.  
    						
    							43
    TABLE 15
    Water Temperature 
    °F (°C) Time for 1st Degree Burn
     
    (Less Severe Burns) Time for Permanent Burns
     
    2nd & 3rd Degree  
    (Most Severe Burns)
    110 (43) (normal shower temp.)
    116 (47) (pain threshold)
    116 (47) 35 minutes 45 minutes
    122 (50) 1 minute 5 minutes
    131 (55) 5 seconds 25 seconds
    140 (60) 2 seconds 5 seconds
    149 (65) 1 second 2 seconds
    154 (68) instantaneous 1 second
    (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)The  water  heaters  covered  in  this  manual  are  equipped  with 
    an  electronic  control  system  to  regulate  the  water  temperature 
    inside the storage tank. The control system senses temperature 
    from  two  factory  installed  temperature  probes,  one  installed  in 
    the  top  of  the  storage  tank  and  one  installed  near  the  bottom, 
    See Figure 3 on page 8 and Figure 4 on page 9 for location.
    The “Operating Set Point” is adjusted to regulate water temperature 
    inside  the  storage  tank.  This  is  an  adjustable  user  setting  in  the 
    control system’s “Temperatures Menu.” This and all control system 
    menus  are  accessed  through  the  UIM  (user  interface  module) 
    located on the front of the water heater, see Figure 52.
    The Operating Set Point is adjustable from 90°F (42°C) to 180°F 
    (82°C).  The  factory  setting  is  120°F  (49°C).  See  Operating  Set 
    Point And Differential Adjustment on page 47 for instructions on 
    how to adjust the Operating Set Point and other user settings.
    Set the Operating Set Point at the lowest setting which produces 
    an acceptable hot water supply. This will always provide the most 
    energy efficient operation.
    MODULATION
    The water heaters covered by this manual are capable of modulating 
    their  firing  rate.  The  CCB  monitors  the  water  temperature  in  the 
    tank and regulates the firing rate to achieve the target temperature 
    setpoint. The firing rate is dictated by the hot water draw, proximity 
    to  the  tank  temperature  setpoint,  and  various  other  temperature 
    limitations. Periodically, when the heater is in modulation mode,  the 
    CCB will increase the blower speed for a short period of time to clear 
    out any condensation that has accumulated in the heat exchanger 
    then decreases the blower speed back to the modulating firing rate 
    required  to  maintain  the  desired  tank  temperature  setpoint.  This 
    ramping  up  and  down  of  the  blower  speed  is  considered  normal 
    operation of the water heater.
    HIGH TEMPERATURE APPLICATIONS
    Higher  operating  temperatures  cause  more  wear  on  all  water 
    heaters and will decrease the life span of the water heater. Consider 
    installing  a  small  booster  water  heater  for  high  temperature 
    applications,  such  as  commercial  dishwashers,  to  raise  the  outlet 
    temperature  from  the  larger  primary  water  heater  to  the  desired 
    point of use temperature.
    Contact your local distributor or call the technical support phone number 
    listed on the back cover of this manual for further technical assistance.
    Tank  Temperature   103°F
    Operating Set Point   120°F
    Status: Heating
    MENU HELP
    UP
    DN
    GASOFF
    ON
    MANUF ACTURER / MODEL  INFORMATION
    Figure 50
    HIGH TEMPERATURE LIMIT CONTROL (ECO)
    This water heater is equipped with an ECO (energy cut off) non 
    adjustable high temperature limit switch. The ECO is a normally 
    closed switch that opens (activates) on a rise in temperature.
    The ECO is located inside the Upper Temperature Probe (two red 
    wires), see Figure 3 on page 8 for location. The ECO switch contacts 
    will  open  when  the  water  temperature  reaches  approximately 
    202°F (94°C) and close at approximately 140°F (49°C). 
    If  the  ECO  activates  (contacts  open)  due  to  abnormally  high 
    water  temperatures  in  the  storage  tank  the  control  system  will 
    immediately  de-energize  the  24  VAC  Gas  Valve  and  end  the 
    current heating cycle. The control system will "lock out" disabling 
    further  heating  operation.  The  control  system  will  display  the 
    "Energy  Cut  Out  (ECO)"  Fault  message  on  the  LCD  screen. 
    It  is  important  that  a  Qualified  Service  Agent  be  contacted  to 
    determine the reason for the ECO activation before resetting the 
    ECO.  Once  the  reason  has  been  determined  and  corrected  the 
    ECO can be reset as follows:
    Should the ECO activate, the water temperature must drop below 
    140°F  (49°C)  before  the  control  system  can  be  reset.  Once  the 
    water temperature has cooled below this point the power supply 
    to the water heater must be turned off and on again to reset the 
    control system.
    THERMOSTAT CONTROL
    Water temperature over 125°F (52°C)
    can cause severe burns instantly
    resulting in severe injury or death.
    Children, the elderly and the
    physically or mentally disabled are at
    highest risk for scald injury .
    Feel water before bathing or
    showering.
    Te mperature limiting devices such as
    mixing valves must be installed
    when required by codes and to
    ensure safe temperatures at fixtures.
    Hot  water  temperatures  required  for  automatic  dishwasher  and 
    laundry use can cause scald burns resulting in serious personal 
    injury  and/or  death.  Table  15  shows  the  approximate  time-to-
    burn relationship for normal adult skin.
    The temperature at which injury occurs varies with the person’s 
    age  and  duration  of  exposure.  The  slower  response  time  of 
    children,  the  elderly  or  disabled  persons  increases  the  hazards 
    to them. If anyone using hot water provided by the water heater 
    being  installed  fits  into  one  of  these  groups  or  if  there  is  a  local 
    code  or  state  law  requiring  a  certain  water  temperature  at  the 
    point of use, then special precautions must be taken.
    In addition to using the lowest possible temperature setting that 
    satisfies  the  demand  of  the  application  a  mixing  valve  can  be 
    installed at the water heater (see Figure 8 on page 14) or at the 
    hot water taps to further reduce system water temperature.
    Never allow small children to use a hot water tap or draw their own 
    bath water. Never leave a child or disabled person unattended in 
    a bathtub or shower. 
    The water heater should be located in an area where the general 
    public does not have access to set temperatures.
    Setting  the  Operating  Set  Point  at  120°F  (49°C)  will  reduce  the 
    risk  of  scalds.  Some  States  require  settings  at  specific  lower 
    temperatures.
    TEMPERATURE REGULATION  
    						
    							44
    CONTROL SYSTEM OPERATION
    Tank  Temperature   103°F
    Operating Set Point   120°F
    Status: Heating
    MENU HELP
    GASOFF
    ON
    MANUF ACTURER / MODEL  INFORMATIONLCD Screen
    Information
    Display
    Status Icons
    3 Operational buttons:
    enter/exit menus,
    select menu items,
    activate adjustment modes,
    confirm/cancel changes. Up & Down buttons:
    navigate menus,
    adjust user settings Title Bar
    Enable/Disable Switch
    Operational buttons are multi functional.  Their current function is defined by
    the text that appears directly above each button on the LCD screen.
    UIM (user interface module)
    Desktop Screen Shown
    UP
    DN
    Figure 52
    OVERVIEW
    The  water  heaters  covered  in  this  manual  are  equipped  with  an 
    electronic control system that regulates water temperature inside 
    the storage tank. Heating cycles and ignition are managed by the 
    control system. The ECO (energy cut out), flame sensor, pressure 
    switches  and  temperature  probes  are  monitored  by  the  control 
    system.  The  Combustion  Blower,  spark  ignition  control,  24  VAC 
    Gas Valve and anode rods are all powered by the control system. 
    The  main  components  of  the  control  system  are  a  UIM  (user 
    interface  module)  and  a  CCB  (central  control  board).  The  UIM  is 
    located on the top front side of the water heater. The CCB is mounted 
    on top of the water heater inside a protective enclosure. This unit is 
    equipped with an Enable/Disable switch. To operate unit, make sure 
    the switch is set to Enable. See Features And Components on page 
    7 for location of these and all water heater components.
    POWER
    SUPPLY
    BOARD
    TRANSFORMER
    CCBBOARD
    Figure 51
    CONTROL SYSTEM NAVIGATION
    All  operational  information  and  user  settings  are  displayed  and 
    accessed  from  the  UIM.  The  UIM  houses  the  control  system's 
    LCD  (liquid  crystal  display)  and  five  snap  acting  (momentary) 
    user  input  buttons;  an  up,  down  and  three  (3)  multi  functional 
    operational buttons below the LCD, see Figure 52. User Input Buttons
    •  The up and down buttons are used to navigate menus and 
    adjust user settings. 
    •  The operational buttons are used to enter/exit menus, 
    select menu items, activate adjustment modes and confirm 
    or cancel new user settings. The operational buttons are 
    multifunctional, their current function is defined by the text 
    that appears directly above each button on the LCD screen. 
    THE DESKTOP SCREEN
    During  normal  operation  the  control  system  will  display  the 
    "Desktop"  screen  on  the  LCD  which  is  the  default  screen.  The 
    control system will return to the Desktop screen when there are 
    no  active  Fault  or  Alert  conditions  or  when  there  has  been  no 
    user input for several minutes.  •  Manufacturer and water heater model information is 
    displayed in Title Bar at the top of the Desktop screen. 
    Menu titles are displayed in the Title Bar when navigating 
    the control system menus.
    •  The first temperature shown on the Desktop screen, Tank 
    Temperature, is the temperature of the water inside the 
    water heater's storage tank. 
    •  The second temperature shown on the Desktop screen 
    is the Operating Set Point. The Operating Set Point is the 
    temperature at which the control system will maintain the 
    water inside the storage tank. 
    •  Beneath the Operating Set Point is the "Status" line. The 
    Status line shows the current operational state of the 
    control system in real time, see Table 17 on page 46 for a 
    description of the various operational states.
    •  The Desktop screen also displays animated "Status Icons" 
    to convey operational information, see Table 16 on page 45 
    for descriptions of the Status Icons.  
    						
    							45
    STATUS ICONS
    The Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described 
    in the table below. See Figure 54 on page 57 and the Sequence Of Operation on page 56. 
    TABLE 16
    IconDescription
    Water  temperature  in  the  tank  has  fallen.  Shaded  area  of  the  animated  thermometer  icon  will  rise  and  fall  in  response  to 
    water temperature in the storage tank as sensed from the Upper and Lower Temperature Probes. See Figure 3 on page 8 
    and Figure 4 on page 9 for location of Temperature Probes.
    Water temperature in the tank has reached the Operating Set Point. The control system enters the Standby mode.
    The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by the control system 
    or  when  the  Enable/Disable  switch  on  front  panel  is  in  disable  position  or  Building  Management  system  Enable/Disable 
    circuit is an open circuit. Display will read "Status: Water Heating Disabled". For more information see Enable/Disable Circuit 
    on page 41.
    The Combustion Blower is being energized.
    The Blower Prover pressure switch contacts have closed. The check mark icon is visual confirmation of contact closure. See 
    Figure 3 on page 8 for Blower Prover Switch location.
    The spark igniter is being energized. See Figure 2 on page 7 for spark igniter location.
    GAS
    OFF
    ONThe 24 VAC Gas Valve is being energized.
    The control system has sensed flame at the Main Burner from the flame sensor. See the Sequence Of Operation Flow Chart 
    on page 57 and Figure 2 on page 7.
    The  control  system  has  declared  a  Fault  condition  and  must  be  inspected/serviced  by  a  Qualified  Service  Agent.  Fault 
    message details can be viewed in the Current Fault menu. Heating operation is disabled (lock out) until the condition that 
    caused the Fault is corrected. Power to the water heater must be cycled off and on at the breaker to reset the control system. 
    NOTE: Cycling power will not reset the control system if the condition that caused the Fault has not been corrected.
    The control system has declared an Alert condition and must be inspected/serviced by a Qualified Service Agent. The water 
    heater will continue to operate during an Alert condition.  
    						
    							46
    OPERATING STATES
    The current operational state of the water heater is displayed on the Desktop screen as the "Status." The common operational states 
    are described in the table below.  See Figure 54 on page 57 and the Sequence Of Operation on page 56.
    TABLE 17
    StateDescription
    Standby The water heater is not in an active heating cycle. IE: the Tank Temperature is at or above the Operating Set Point.
    Input Verification The control system is conducting a diagnostic check at the beginning of a heating cycle.
    Water heating 
    disabled A Fault condition is detected by the control or when the Enable/Disable switch on front panel is in disable position or the 
    Building Management system Enable/Disable is an open circuit.
    Pre-Purge The Combustion Blower is energized to flush residual flue gases from the combustion chamber prior to ignition.
    Spark Igniter 
    Energized The Spark Igniter is energized.
    Ignition Activation The 24 VAC Gas Valve is energized and opens to allow fuel gas to flow to the Main Burner.
    Ignition Verification The control system is monitoring the flame sensor for the required minimum flame sensing current.
    See the Sequence Of Operation on page 56 for minimum flame sensing current (DC micro amps) information.
    Inter-Purge The Combustion Blower is energized to flush residual fuel gas from the combustion chamber after a failed ignition attempt.
    Heating Ignition was successful, flame sensing current has been established.  The water in the storage tank is being heated.
    Post-Purge The Combustion Blower is energized to flush residual flue gases from the combustion chamber at the end of a heating 
    cycle.
    Fault The control system has detected a Fault condition. Heating operation is disabled until the Fault condition is corrected. 
    Power to the water heater must be cycled off and on at the breaker to reset the control system. 
    NOTE: Cycling power will not reset the control system if the condition that caused the Fault has not been corrected.
    CONTROL SYSTEM MENUS
    From the Desktop screen pressing the Operational button directly below "Menu" on the LCD will display the "Main Menu" this is where 
    all control system menus are located. The table below describes the control system menus.
    TABLE 18
    Menu
    Description
    Temperatures Most commonly accessed menu. Contains the Operating Set Point and Dif ferential user settings.
    Heater Status This  menus  displays  the  current  state  of  all  pressure  switches  and  the  ECO  (open/closed).  The  on/off  status  of  the 
    Combustion Blower, gas valve, spark igniter, flame sensor and other monitored water heater components are displayed 
    in this menu.
    Display Settings Temperature  units  (°F  or  °C),  the  LCD  appearance  (brightness/contrast)  and  backlight  delay  user  adjustable  settings 
    are located in this menu.
    Heater Information Elapsed  time  of  operation,  total  heating  cycle  time,  heating  cycle  count,  heating  on  time  along  with  UIM  and  CCB 
    software revisions can be viewed in this menu.
    Current Fault Displays any current Alert or Fault messages.
    Fault History This  control  system  menu  retains  a  list  of  the  last  nine  (9)  Fault  and Alert  messages  with  a  time  stamp.  The  newest 
    event will replace the oldest. Faults will clear after 30 days.
    Fault Occurrence This control system menu retains a running total of how many times each Fault condition has occurred since the water 
    heater was first installed. This screen does not clear and the information can not be reset.
    Restore Factory Defaults This  control  system  feature  allows  the  user  to  restore  control  system  user  settings  to  their  factory  default  settings. 
    Display Settings preferences ARE NOT changed when factory defaults are restored.
    Help Screens Text based operational and user information explaining how to change user settings, navigate the control system menus 
    and icon descriptions.  
    						
    							47
    USER SETTINGS & CONTROL SYSTEM MENUS
    TEMPERATURES MENU
    Operating Set Point And Differential Adjustment
    The  Operating  Set  Point  is  adjustable  from  90°F  (42°C)  to  180°F  (82°C).  The  factory  setting  is  120°F  (49°C).  The  Differential  is 
    adjustable  from  2°  to  20°. The  factory  setting  is  8°. These  user  settings  are  accessed  from  the Temperatures  menu. The  following 
    instructions will explain how to adjust these settings and navigate the control system menus.
    When the water temperature sensed by the control system from the two (upper and lower) Temperature Probes reaches the Operating 
    Set Point the control system will end the heating cycle. A heating cycle will be activated again when the sensed water temperature 
    drops below the Operating Set Point minus the Differential setting.
    NOTE:  Lower  Differential  settings  may  cause  excessive  heating  cycles  (short-cycling)  which  can  cause  premature  failure  of 
    components  such  as  the  Hot  Surface  Igniter.  Set  the  Differential  at  the  highest  setting  which  produces  an  acceptable  hot  water 
    supply. Set the Operating Set Point to the lowest setting which produces an acceptable hot water supply for most efficient use.
    DESCRIPTION/ACTIONDISPLAY
    From the Desktop screen, press the Operational Button under 
    MENU. The "Main Menu" screen will be displayed.
    Ta nk  Temperature   120°F
    Operating Set Point   120°F
    Status: Standby
    MENUHELP
    MANUF ACTURER / MODEL INFORMA TION
    The Main Menu is where all control system menus are listed, 
    see Table 18 on page 46 for a complete list and description of 
    control system menus. Use the Up and Down Buttons to view 
    all control system menus from the Main Menu.
    With Temperatures menu selected (highlighted in black) in 
    the Main Menu screen, press the Operational Button under 
    “SELECT” to enter the Temperatures menu.
    If the Temperatures menu is not selected use the Up and Down 
    Buttons to select this menu item.
    Temperatures
    Heater Status
    Display Settings
    Heater Information
    Current Fault
     SELECT  BACK HELP
    Main Menu
    With the Operating Set Point selected in the Temperatures 
    menu, press the Operational Button underneath “CHANGE” to 
    activate the adjustment mode for this menu item.
    If Operating Set Point is not selected use the Up and Down 
    Buttons to select this menu item.
    NOTE: Higher Temperature settings increase wear and 
    operating costs. Set the Operating Set Point to the lowest 
    setting which produces an acceptable hot water supply. This 
    will always provide the most energy efficient operation and 
    longer life.
    Operating Set Point   120°F
    Dif ferential   8°F
    Ta nk  Temperature   120°F
    Ta nk Probe Of fset   0°F
     CHANGE BACK HELP
    Temperatures
    With the adjustment mode for the Operating Set Point activated 
    the selection bar will change from a black fill to a black outline.
    Use the Up and Down Buttons to change the current setting.
    Press the Operational Button under "UPDATE" to save the 
    new setting. Press the Operational Button under "CANCEL" to 
    discard changes and return to the previously saved setting.
    NOTE: Use this same procedure to change the Differential 
    setting and other adjustable user settings in the control system 
    menus.
    Operating Set Point   140°F
    Dif ferential   8°F
    Ta nk  Temperature   120°F
    Ta nk Probe Of fset   0°F
     UPDATE  CANCEL
    Temperatures  
    						
    							48
    TEMPERATURES MENU (CONT)
    DESCRIPTION/ACTIONDISPLAY
    •  Differential  - Adjustable user setting that changes the tank 
    temperature  differential  with  a  range  of  2°  to  20°F.  The 
    factory setting is 8°F.
    •  Tank Temperature - non adjustable - control system sensed 
    temperature  (averaged  from  upper  and  lower  temperature 
    probes).
    •  Tank Probe Offset  -  adjustable  user  setting,  range  -5°  to 
    +5° (factory setting 0°). 
    NOTE: These  settings  should  only  be  used  if  the  hot  water 
    supply  temperature  varies  greatly  from  the  Operating  Set 
    Point setting. 
    The  Tank  Probe  Offset  is  used  to  calibrate  control  system 
    temperature  sensing.  This  can  improve  the  precision  of 
    temperature control in the storage tank and at points of use. 
    This  feature  can  also  be  used  to  compensate  for  building 
    recirculation  loops  (hot  water  returning  to  the  storage  tank) 
    that may cause the heating cycles to terminate prematurely.
    Example:  If  the  current  sensed  temperature  from  a 
    temperature probe is 120°F (49°C) and the Offset setting for 
    that  probe  is  adjusted  to  a  value  other  than  0°,  the  control 
    system  would  calibrate  or  “offset”  the  sensed  temperature 
    from the probe and the averaged tank temperature. Heating 
    cycles  would  be  activated  and  deactivated  based  on  the 
    calibrated  (offset)  temperature.  A  -5°  setting  results  in  +5° 
    hotter water.
    These  settings  are  adjusted  in  the  same  way  described 
    for  the  Operating  Set  Point  And  Differential  Adjustment  on   
    page 47.
    Operating Set Point   140°F
    Dif ferential   8°F
    Ta nk  Temperature   120°F
    Ta nk Probe Of fset   0°F
     CHANGE BACK HELP
    Temperatures
    HEATER STATUS MENU
    DESCRIPTION/ACTION DISPLAY
    Select  Heater  Status  from  the  Main  Menu  and  press  the 
    Operational  Button  under  "SELECT"  to  enter  this  menu.  This 
    menu contains non adjustable operational information. Use the 
    Up & Down Buttons to navigate the menu. •  Status - displays the current Operating State, see Table 17 
    on page 46.
    •  ECO Contact, Low Gas PS , Blocked Inlet PS, Blocked 
    Outlet PS , Blower Prover PS - displays the current state 
    of the switch contacts; open or closed.
    •  Igniter On , Gas Valve On - displays whether or not the 
    control system is currently energizing these water heater 
    components; yes = energized, no = de-energized.
    •  Flame Detected  - displays whether or not the control 
    system has detected Main Burner flame during ignition from 
    the flame sensor.
    NOTE: Menu display is shown with Enable/Disable switch in 
    Enable position. Top of Menu
    Status  
    Standby
    ECO Contact   Closed
    Low Gas PS   Closed
    Blocked Inlet PS   Closed
    Blocked Outlet PS   Closed
    Blower Prover PS   Open
    Igniter On   No
      BACK HELP
    Heater Status
    Bottom of Menu
    Gas Valve On   No
    Flame Detected   No
      BACK HELP
    Heater Status  
    						
    							49
    DISPLAY SETTINGS
    DESCRIPTION/ACTIONDISPLAY
    Select  Display  Settings  from  the  Main  Menu  and  press  the 
    Operational  Button  under  "SELECT"  to  enter  this  menu.  This 
    menu contains adjustable display options for viewing information 
    on  the  UIM’s  LCD  screen.  Use  the  Up  &  Down  Buttons  to 
    navigate the menu. •  Temperature Units  - Adjustable user setting that changes 
    temperature units display to Celsius °C or Fahrenheit °F.
    •  Backlight Delay - Adjustable user setting that determines 
    how long the UIM’s LCD backlight remains illuminated after 
    a key has been pressed. Available settings are; Always Off, 
    10, 30 or 60 seconds and Always On.
    •  Contrast - Adjustable user setting to adjust the UIM’s LCD 
    screen contrast between text and background.
    NOTE:  These  settings  are  adjusted  in  the  same  way 
    described  for  the  Operating  Set  Point  And  Differential 
    Adjustment on page 47.
    Te mperature Units   °F
    Backlight Delay   30s
    Contrast   60%
     CHANGE BACK HELP
    Display Settings
    HEATER INFORMATION
    DESCRIPTION/ACTION DISPLAY
    Select  Heater  Information  from  the  Main  Menu  and  press  the 
    Operational  Button  under  "SELECT"  to  enter  this  menu.  This 
    menu contains non adjustable operational information. •  Elapsed Time  - Total  accumulated  time  the  control  system 
    (water heater) has been energized.
    •  Burner On Time - Total accumulated time the control system 
    has been in the heating operating state; burner run time.
    •  Total Cycle Count  -  Total  accumulated  count  of  heating 
    cycles.
    •  CCB Version - Software version for central control board.
    •  UIM Version - Software version for user interface module.
    •  Config  CRC  -  Verifies  the  configuration  key  matches  the 
    CCB programming.
    •  Use External Enable -  Enables/Disables  the  external 
    enable circuit.
    •  External Enable Status -  displays  whether  or  not  the 
    external enable circuit has been activated.
    •  Ignition Trials - displays the number of ignition trials allowed.
    NOTE:  Historical  data  is  stored  in  the  configuration  key.  If 
    this 'key' is replaced during servicing the historical data will 
    be lost. The data stored in the new configuration key will no 
    longer reflect the entire history of the water heater.
    The Elapsed Time, Burner On Time and Cycle Count indicate 
    age, usage and wear.
    If  the  Cycle  Count  per  day  is  high  (divide  cycle  count  by 
    days  to  determine  cycles  per  day)  or  the  cycle  duration  is 
    short (determine burner on time total minutes, divide burner 
    on  time  total  minutes  by  cycle  count)  consider  rasing  the 
    Differential  setting  to  avoid  short  cycling  and  excessive 
    component  wear,  see  Operating  Set  Point  And  Differential 
    Adjustment on page 47.
    This  historical  data  can  also  be  used  to  assist  facilities 
    managers in forecasting planned replacement of equipment 
    to help avoid lengthy and costly hot water supply interruptions.
    Elapsed  Time
       10 day 0 hrs 0 mins
    Burner On  Time
       5 hrs 22 mins
    To tal Cycle Count   00000035
    CCB V ersion   X.XX
    Config CRC   0 x 605D
     CHANGE BACK HELP
    Heater Information
    UIM Version   X.XX
    Use External Enable   No
    External Enable Status   No
    Ignition  Trials   3
      BACK HELP
    Heater Information  
    						
    							50
    CURRENT FAULT
    DESCRIPTION/ACTIONDISPLAY
    Select  Current  Fault  from  the  Main  Menu  and  press  the 
    Operational  Button  under  "SELECT"  to  enter  this  menu.  This 
    menu contains non adjustable operational information. Use the 
    Up & Down Buttons to navigate the menu.
    This  menu  contains  the  current  Fault  or  Alert  error  message. 
    The  time  the  Fault  or Alert  message  occurred  appears  directly 
    below. A brief description of what causes the particular Fault or 
    Alert  condition  appears  below  that.  Pressing  the  Operational 
    Button  under  "ADVANCED"  will  give  more  detailed  service 
    information  and  a  list  of  possible  causes  for  the  Fault  or  Alert 
    condition.  See  Fault And Alert  Messages  on  page  59  for  more 
    detailed information and diagnostic procedures.
    If  there  is  no  Fault  or  Alert  condition  active  this  menu  will  not 
    contain any information, "(none)" will be shown next to Current 
    Fault in the Main menu.
     CHANGE  BACK ADV
    ANCED
    Blocked Exhaus tFault occurred 2 mins ago
    Restriction in exhaust pipe.
    Check exhaust pipe and
    termination for blockage.
    Call a service professional:
    Your Company Name Here
    (press [DOWN] for more.... )
    FAULT HISTORY
    DESCRIPTION/ACTION DISPLAY
    Select  Fault  History  from  the  Main  Menu  and  press  the 
    Operational  Button  under  "SELECT"  to  enter  this  menu.  This 
    menu contains non adjustable operational information. Use the 
    Up & Down Buttons to navigate the menu.
    This  menu  contains  a  list  of  the  last  nine  (9)  Fault  and  Alert 
    messages with a time stamp. The newest event will replace the 
    oldest.
    Press  the  Operational  Button  under  "VIEW"  to  view  details  for 
    each Fault or Alert message stored.
    1:   Blocked Air Intake (A7)
       51 mins ago
    2:   Blocked Exhaust (A8 )
       54 mins ago
    3:   Low Gas Pressure (A6 )
       57 mins ago
    4:   Blower Prover Failure (AC )
     VIEW BACK HELP
    Fault History
    FAULT OCCURRENCE
    DESCRIPTION/ACTION DISPLAY
    Select  Fault  Occurrence  from  the  Main  Menu  and  press  the 
    Operational  Button  under  "SELECT"  to  enter  this  menu.  This 
    menu contains non adjustable operational information. Use the 
    Up & Down Buttons to navigate the menu.
    This  menu  contains  a  running  total  of  how  many  times  each 
    Fault  condition  has  occurred  since  the  water  heater  was  first 
    installed.
    NOTE:  Historical data is stored in the Configuration Key. If this 
    'key' is replaced during servicing the historical data will be lost. 
    The  data  stored  in  the  new  configuration  key  will  no  longer 
    reflect the entire history of the water heater.
    Ignition Failure   10
    ECO   0
    Low Gas Pressure   10
    Blocked Intake  Air   0
    Blocked Exhaust   0
    Blower Prover   0
    Flame Detect Error   3
      BACK HELP
    Fault Occurrence
    RESTORE FACTORY DEFAULTS
    DESCRIPTION/ACTION DISPLAY
    Select Restore Factory Defaults from the Main Menu and press 
    the Operational Button under "SELECT" to enter this menu.
    To  restore  the  adjustable  user  settings  to  their  factory  default 
    settings  press  the  Operational  Button  underneath  “YES.”  The 
    display  will  show  text  confirming  the  factory  default  settings 
    have been restored.
    Press  the  Operational  Button  underneath  “BACK”  to  exit  the 
    Restore Factory Defaults menu.
     YES   NO
    Restore Factory Default s
    Are you sure you want to
    restore the system to factory
    defaults?  
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual