Home > Honeywell > Control panel > Honeywell Tz 4 Manual

Honeywell Tz 4 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Tz 4 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    11 68-0259-1
    Fig. 16. Wiring conventional heating and cooling equipment to TZ-4 panel.
    Heat Pump Equipment
    See Fig. 17-22 for heat pump wiring. Refer to manufacturer 
    instructions for additional wiring details and substitute the   
    TZ-4 equipment terminals for the thermostat terminals shown. 
    — Connect the changeover relay to O/B equipment terminal. 
    — Set switch number 5-7 to on for O (cool) changeover, or to 
    off for B (heat) changeover. 
    — Set switch number 5-1 to off for heat pump equipment. 
    — Set DIP switches 4-1, 4-2, 4-3, and 4-4. See Single Stage 
    and Multi-Stage Operation in the Operation section. 
    IMPORTANT
    Some heat pump manufacturers (such as York and 
    Trane) use the B terminal as the transformer 
    common. Do not connect the common from the 
    equipment to the zone control panel.Single-Speed Compressor: Wire the compressor to the Y1 
    terminal. 
    If the same heat source is used for auxiliary heat and 
    emergency heat:
    — Wire a jumper from W2 (auxiliary heat) to W1/E 
    (emergency heat).
    — Do not connect W3/AUX. See Fig. 17.
    If auxiliary heat is separate from emergency heat:
    — Connect the auxiliary heat to W2 jumped to W3/AUX.
    —  Connect the emergency heat to W1/E. See Fig. 18. 
    M20520B
    ZONE DAMPER MOTORS
    M1 - common
    M4 - power open
    M6 - power closed
    HVAC Equipment
    DIP SWITCH S4 SETTINGS  
    1  2ND STAGE OPERATION: TABLE 1
    2  2ND STAGE OPERATION: TABLE 1
    3  3RD STAGE OPERATION: TABLE 1
    4  3RD STAGE OPERATION: TABLE 1
    5  STAGE TIMER: TABLE 2
    6  STAGE TIMER: TABLE 2
    7  STAGE TIMER: TABLE 2
    8 UNUSED
    DIP SWITCH S5 SETTINGS
    1 SYSTEM TYPE
    2  DATS LOW LIMIT
    3 PURGE TIME
    4 PURGE FAN
    5 PURGE DAMPER
    6 HEAT FAN
    7 O/B ENERGIZED
    8 DUAL FUEL
    LED STATES:
    Heat LED      Heating Mode
    Flashing Heat LED     High Limit
    Cool LED      Cooling Mode
    Flashing Cool LED     Low Limit
    Purge LED      Purge Mode
    Flashing Purge LED  Sensor Failure
    Fan LED      Fan Mode
    EM Heat LED      EM Heat Mode
    TABLE 1#1/#3 #2/#4 OPERATION 1    1      STAT
     1    0      TIMER
     0    1      % ZONES
     0    0      OFF
    TABLE 2
    #5 #6  #7  TIME
    1 1  1 5 MIN
    1 1  0 10 MIN
    1 0  1 15 MIN
    1 0  0 20 MIN
    0 1  1 30 MIN
    0 1  0 40 MIN
    0 0  1 50 MIN
    0 0  0 60 MIN
      
     ON  OFF
     1  0
     CONV  HP
     40F  48F
     2.0  MIN  3.5  MIN
     HVAC  PANEL
      NO CHG  OPEN
     HVAC  PANEL
     COOL  HEAT
    DISABLED ENABLED R
    HRCW1/E
    W
    2W3/AUXZONE LEDs
    ON  Damper open or opening
    OFF  Damper closed or closing
    MOMENTARY PUSH BUTTONS
    Boot – Clears microprocessor
    Purge Overide – Bypass Purge Mode
    BOOTPURGE
    OVERRIDE Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    1 “C” terminal connection 
      is not required on battery 
      powered, power stealing, 
      or some electromechanical 
     thermostats.
    2  Leave jumper disconnected 
      for conventional thermostats.
    R
    C
    T1
    T2
    AZ2 AZ1
    OFF ON
    EM
    Heat
    UnoccupOccup
    Zone-
    A-Lone
    Y1Y2GO/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    First Stage Heating
    Second Stage Heating Relay
    Third Stage Heating
    First Stage Cooling Relay
    Second Stage Cooling Relay
    Fan Relay
    This diagram shows the typicalthree-stage equipment, thermostat,and damper motor connections.For specific wiring for otherthermostats, damper motors, andHVAC Equipment, refer to the
    nstallation Instructions.
    M6 M4M1
    DATS
    DATS
    1
    Zone 4 Thermostat
    CR C R
    Power-closed
    Spring-open
    (Model ZD)Power-closed
    Spring-open
    (Model ARD)Power-closed
    Spring-open
    (Model ARD)
    24VAC, 40VA 
    Transformer
    (Required if
    more than
    four dampers
    )
    24VAC, 40VA 
    Transformer
    OCOCRemote
    Zone-A-Lone
    Add-A-Zone
    Panel(s)
    DAMPER
    XFRM
    PANEL
    XFRM
    HEATCOOLPURGEFANEM. HEATZONE 1ZONE 2ZONE 3 ZONE 4
    DIP SWITCH S4DIP SWITCH S5
    1O
    N
    2345678 1
    O
    N
    2345678
    M6 M4M1
    1
    Zone 3 Thermostat
    M6 M4M1
    1
    Zone 2 Thermostat
    456Z
    123X
    Power-open
    Power-closed
    (Opposed Blade
    Damper Motors)
    O/B Y2 GW2M6M4M1W3/
    AUXY1W1/
    ER C
    Y1 W3/
    AUX W2 W1 R CY2GLO/B Y1 W3/
    AUX W2 W1 R CY2GLO/B Y1 W3/
    AUX W2 W1 R CY2GLO/B Y1 W3/
    AUX W2 W1 R CY2GLO/B LO/B Y2 GW2W3/
    AUX Y1 W1/
    E R C
    LO/B Y2 GW2W3/
    AUX Y1 W1/
    E R C
    LO/B Y2 GW2W3/
    AUX Y1 W1/
    E R C
    L
    1
    Zone 1 Thermostat
    ZONE 12Thermostat
    DATSOT
    OTOT
    Sensor130 F
    120 F
    110 F140 F
    150 F
    160 F
    MAX. DUCT TEMP.
    25 F
    20 F
    15 F35 F 30 F
    40 F
    45 F
    DUAL FUEL OT SETTING
    DamperZONE 22ThermostatDamperZONE 32ThermostatDamperZONE 42ThermostatDamper 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 12
    Fig. 17. Wiring single-stage heat pump with auxiliary heat.
    Fig. 18. Wiring single-stage heat pump with separate 
    auxiliary and emergency heat.
    Two-speed Compressor: Wire the first stage compressor to 
    Y1 and the second stage compressor to Y2.
    If the same heat source is used for auxiliary heat and 
    emergency heat:
    —  Wire a jumper from W3/AUX (auxiliary heat) to W1/E 
    (emergency heat), see Fig. 19.
    If auxiliary heat is separate from emergency heat:
    — Wire the auxiliary heat to W3/AUX.
    — Wire emergency heat to W1/E, see Fig.20.Fig. 19. Wiring two-stage heat pump with auxiliary heat.
    Fig. 20. Wiring two-stage heat pump with separate 
    auxiliary and emergency heat.
    Dual Fuel Heat Pumps: Install C7089B1000 Outdoor 
    Temperature Sensor to terminals OT and OT.
    — Set outdoor sensor setting to:
    — Balance point temperature of heat pump or
    — Outdoor temperature above which the heat pump is to 
    be used and below which the fossil fuel is to be used. 
    — Set DIP switch number 5-8 to off for dual fuel operation. 
    — Connect compressor to Y1. See Fig. 21.
    — Connect fossil fuel heat to W1/E.
    — Connect second stage of fossil fuel to W3/AUX. 
    — Connect second stage of compressor to Y2. See 
    Fig. 22.
    M20521B
    HVAC Equipment
    RHRCW1/E
    W
    2W3/AUX
    Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    Y
    1Y2G
    O/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    Auxiliary Heat 
    Compressor
    Reversing Valve
    Fan Relay
    1
    1
    FIELD INSTALLED JUMPER.
    M20522B
    HVAC Equipment
    RHRCW1/E
    W
    2W3/AUX
    Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    Y
    1Y2G
    O/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    Emergency Heat
    Auxiliary Heat 
    Compressor
    Reversing Valve
    Fan Relay
    1
    FIELD INSTALLED JUMPER.
    1
    M20523B
    HVAC Equipment
    RHRCW1/E
    W
    2W3/AUX
    Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    Y
    1Y2G
    O/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    Auxiliary Heat 
    First Stage Compressor
    Second Stage Compressor
    Reversing Valve
    Fan Relay
    1
    1
    FIELD INSTALLED JUMPER.
    M20524A
    HVAC Equipment
    RHRCW1/E
    W
    2W3/AUX
    Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    Y
    1Y2G
    O/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    Emergency Heat
    Auxiliary Heat
    First Stage Compressor
    Second Stage Compressor
    Reversing Valve
    Fan Relay 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    13 68-0259-1
    Fig. 21. Dual Fuel with single-stage heat pump and single-
    stage fossil fuel.
    Fig. 22. Dual fuel with two-stage heat pump and            
    one- or two-stage fossil fuel.
    Water Source Heat Pumps
    Wire the equipment, as applicable, to the TZ-4 as shown in 
    Fig. 17-19. Refer to manufacturer instructions for additional 
    wiring instructions and substitute the TZ-4 equipment 
    terminals for the thermostat terminals shown.
    — Wire first stage compressor to Y1, second stage 
    compressor to Y2. 
    — Connect auxiliary heat to W3/AUX and emergency heat to       
    W1/E. 
    — If auxiliary heat and emergency heat are the same, wire a 
    jumper from W1/E to W3/AUX. 
    — Connect changeover relay to O/B equipment terminal. 
    — Set DIP switch 5-7 to on for O (cool) changeover, or to off 
    for B (heat) changeover. 
    — Set DIP switch 5-1 to off for heat pump equipment.
    STARTUP AND CHECKOUT
    After the installation is complete, verify correct operation:
    1.Place the Em Heat switch in the Off (down) position.
    2.Place the Zone-A-Lone switch in the Occup/Remote 
    (up) position.
    3.Verify that DIP switches are set correctly. See 
    Sequence of Operation section and Table 8 for correct 
    configuration. 
    4.Power up the TZ-4 and set the thermostats so no zones 
    are calling. The board then enters the Purge mode 
    where all dampers open and the fan operates for two or 
    three and one-half minutes (configurable). (If there is no 
    Discharge Air Temperature Sensor connected to the 
    panel, the purge LED flashes in all modes other than 
    purge.) The damper LEDs are green to indicate the 
    dampers are open. Press Purge Override button on 
    panel to exit Purge mode. 
    5.Set zone one thermostat to heat and raise the setpoint 
    to call for heat. Verify that the heat LED is red and zone 
    one damper remains green while the other damper 
    LEDs turn off.
    6.Raise zone two setpoint to call for heat. Lower zone one 
    setpoint to stop the call for heat to that zone. Verify that 
    zone one LED turns off and zone two LED turns green.
    7.Repeat for zones three and four.
    8.Alternately, lower the setpoint to call for cooling. Verify 
    that the green cool LED illuminates.
    OPERATION
    Identifying DIP Switches
    This panel has two banks of DIP switches, DIP switch 4 (S4) 
    and DIP switch 5 (S5). Each bank has eight individual 
    switches that are identified by two numbers; the first number 
    is the bank number (4 or 5) and the second number identifies 
    the individual switch. For example, DIP 5-1 is bank 5, 
    switch 1.
    Sequence of Operation
    • When there is no call for heat, cool or fan, the board is in 
    idle mode, no system LEDs are illuminated and the green 
    damper LEDs indicate open. 
    • On a call for heat, cool, or fan, the calling zone damper 
    stays open, and other zone dampers close:
    — TZ-4 panel energizes the HVAC equipment and condi-
    tioned air is delivered to the calling zone. 
    — Heat LED (red), cool LED (green), or fan LED (green) 
    illuminates to indicate equipment operation. 
    — Fan LED illuminates only on a call for circulation; it 
    does not illuminate during a call for heat or cool. 
    — When the call is satisfied, the system enters the Purge 
    mode. After purge, all dampers return to the Open 
    position, depending on the setting of DIP switch S5-5. 
    • Any zone thermostat can call for heating or cooling. If there 
    are co-existing calls for heat and cool, the panel accepts 
    the first call. 
    • Once that call is satisfied, or a maximum of 20 minutes has 
    elapsed, the panel switches to allow the opposite call after 
    completing Purge mode.
    M20525A
    HVAC Equipment
    RHRCW1/E
    W
    2W3/AUX
    Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    Y
    1Y2G
    O/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    First Stage Fossil Fuel
    First Stage Compressor
    Reversing Valve
    Fan Relay
    M20526A
    HVAC Equipment
    RHRCW1/E
    W
    2W3/AUX
    Single Transformer Heating/Cooling
    systems require a jumper to be installed
    connecting R
    H and RC (factory installed).
    Y
    1Y2G
    O/B Heating Transformer
    24 VAC
    Equip.
    Cooling Transformer
    First Stage Fossil Fuel
    Second Stage Fossil Fuel
    First Stage Compressor
    Second Stage Compressor
    Reversing Valve
    Fan Relay 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 14
    Purge Mode
    At the end of every call for heat or cool, the panel enters a 
    Purge mode that holds open the calling zone damper for two 
    (default) or three and one-half minutes.
    During this time, the panel or the HVAC equipment can be 
    configured to operate the fan. The Purge LED lights to signal 
    that the system is in the Purge mode. Pressing the purge 
    override button overrides the Purge mode. 
    Unless there is a new call for heat or cool during the Purge 
    mode, all dampers are moved to the Open position at the end 
    of purge. 
    The panel can be configured to open all dampers during the 
    purge mode.
    Individual Zone Fan Control
    When all zones are satisfied, the fan switch of each 
    thermostat controls the fan operation for that zone. 
    — When the fan switch is in the On position, the fan is 
    energized, and dampers close to zones where fan switch is 
    in Auto position.
    — During a call for heat or cool at this time, the circulation 
    mode ceases, and the heat or cool call is honored. 
    — When the zone calling is satisfied, the circulation call 
    resumes.
    Single and Multi-Stage Operation
    The panel can control up to three stages of heating and two 
    stages of cooling:
    — First stage is energized by the thermostat. 
    — Second stage of heating or cooling and third stage of 
    heating can be energized by the thermostat, timer, or the 
    percentage of zones calling. (For instance, first and second 
    stage of heat and cool can be thermostat energized and 
    third stage heat can be configured for timer energizing.)
    — See Tables 5 and 6 for second and third stage 
    configuration. Note that second and third stage can be 
    controlled differently. Set stages not used to Off.DIP Switch bank 4, switches 1-4, are used to configure the 
    staging method: 
    — Switches 1 and 2 configure second stage control. See 
    Table 4.
    — Switches 3 and 4 configure third stage control. See Table. 
    5.
    — When stage two or three is not used, disable that stage by 
    turning off the corresponding switches. 
    Single Stage
    If equipment is single stage, set bank 4, DIP switches 1-4 Off:
    THERMOSTAT-CONTROLLED STAGES
    Use a thermostat that energizes W2 and Y2 for second stage 
    of heat and cool, and W3 for third stage of heat. Configure for 
    thermostat as shown in Tables 4 and 5.
    TIMER-CONTROLLED STAGES 
    — The Timer energizes second stage of heat or cool after the 
    first stage begins calling for the set amount of time.
    — The third stage of heat is energized once the second stage 
    of heat is calling for the set amount of time.
    — Second and third stages remain energized until the call for 
    heat or cool is satisfied.
    See Table 6 for stage timer configuration of DIP switch bank 4, 
    switches 5, 6, and 7.
    PERCENTAGE OF ZONES CALLING—CONTROLLED STAGES
    Percentage of zones calling energizes second or third stage 
    based on the percentage of zones called for heat or cool on 
    the TZ-4 and TAZ-4. 
    The percentage of zones necessary to turn stages two and 
    three on and off:
    DIP Switch 
    NumberStatusPurge Operation
    5-3Off3.5 minutes
    5-3On2 minutes
    5-4OffPanel control of fan in 
    purge
    5-4OnHVAC control of fan 
    in purge
    5-5OffAll dampers open 
    during purge
    5-5On Damper positions 
    unchanged during 
    purge
    DIP Switch 
    NumberStageStatus
    4-12nd Sta geOff
    4-22nd Sta geOff
    4-33rd StageOff
    4-43rd StageOff
    StageOnOff
    Stage 2 Heat>33%33%66%
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    15 68-0259-1
    HEAT PUMP OPERATION
    The panel can control single- or two-stage heat pumps with or 
    without auxiliary heat. Set DIP switch 5-1 to Off for heat pump 
    control. This energizes equipment terminal Y1 on a call for 
    first stage heat or cool. If second stage is configured to 
    operate with DIP switch 4-1 and 4-2, Y2 energizes to call for 
    second stage compressor. When in heat pump mode, the 
    panel energizes the fan with a call for heat and a call for cool. 
    Configure DIP switch 5-7 for correct changeover valve control. 
    See Table 7.
    DUAL FUEL OPERATION
    The panel can control a heat pump and a fossil fuel furnace in 
    a dual-fuel application. A C7089B1000 Outdoor Temperature 
    Sensor is wired to the OT and OT terminals on the TZ-4 to 
    switch the panel from heat pump to fossil fuel operation. DIP 
    switch 5-8 is set to Off to enable dual-fuel operation.
    The dual-fuel OT setting (see Fig. 16 for location) is set to the 
    outdoor temperature that locks out the heat pump and uses 
    the fossil fuel mode. The fan is energized by the panel for two 
    minutes after the changeover and the Em Ht LED illuminates 
    when in the fossil fuel mode.
    IMPORTANT
    A C7089B1000 Outdoor Temperature Sensor and a 
    C7735A1000 Discharge Air Temperature Sensor are 
    required for dual fuel operation.
    Table 4. DIP Switch Bank 4, Stage 2 Configuration.
    Operation Switch 4-1 Switch 4-2
    Thermostat On On
    Timer On Off
    % of Zones Off On
    Off Off Off
    Table 5. DIP Switch Bank 4, Stage 3 Configuration.
    Operation Switch 4-3 Switch 4-4
    Thermostat On On
    Timer On Off
    % of zones calling Off On
    Off Off Off
    Table 6. DIP Switch Bank 4, Stage Timer Configuration.
    TimeDIP Switch 
    4-5DIP Switch
     4-6DIP Switch 
    4-7
    5 minutesOnOnOn
    10OnOnOff
    15OnOffOn
    20OnOffOff
    30OffOnOn
    40OffOnOff
    50OffOffOn
    60OffOffOff
    Table 7. DIP Switch Bank 5 Settings and Functions.
    DIP Switch Function On (Default) Off
    5-1System TypeConventionalHeat Pump
    5-2DATS low limit.40°F48°F
    5-3Purge mode timing.Two minutes.Three and one-half minutes.
    5-4Fan control during purge.HVAC controlled.Panel controlled.
    5-5Damper control during purgeLast zone(s) calling open.All dampers open.
    5-6Fan control in heat.Fan controlled by panel in cool 
    and HVAC equipment in heat.Panel in heat and cool controlling 
    fan.
    5-7Operation of O/B heat pump 
    changeover equipment terminal.O/B equipment terminal is 
    energized in cool (O).O/B equipment terminal is 
    energized in heat (B).
    5-8Dual fuel operation.Disabled.Enabled. 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 16
    Thermostat Operation
    Conventional Thermostats
    Conventional (R,W,Y,G) heat/cool thermostats can be used 
    with the TZ-4 to control single or multi-stage gas, electric or oil 
    systems and heat pumps with auxiliary heat. 
    The panel can be configured to control second stage heat and 
    cool and third stage heat using a 5-60 minute timer, or staging 
    can be controlled by the percentage of zones calling. 
    When using conventional thermostats on heat pump 
    applications, set DIP switch 5-1 to Off for heat pump 
    equipment. Set DIP switch 5-7 for correct reversing valve 
    operation. See Table 7.
    Heat Pump Thermostats
    HEAT PUMP THERMOSTATS WITH SINGLE Y OUTPUT
    Thermostats that have a single Y terminal for first stage heat 
    and cool and those with separate Y1 and W1 can be used. 
    Thermostats of either wiring type can be used on any zone.
    For thermostats with a single Y, the reversing valve wire must 
    be connected to O/B: 
    — Connect the thermostat Y terminal to Y1 on the panel. 
    — If the thermostat energizes O on a call for cool, connect the 
    O/B jumper located near the thermostat wiring terminals.
    —  If the thermostat energizes B on a call for heat, leave the 
    O/B jumper disconnected.
    HEAT PUMP THERMOSTATS WITH SEPARATE Y1 AND W1 
    TERMINALS
    Heat pump thermostats with separate Y1 and W1 terminals for 
    first stage heat and cool are wired to Y1 and W1/E. Leave the 
    O/B jumper, located near the thermostat wiring terminals, 
    disconnected.
    Emergency Heat Control
    Emergency heat is defined as using an auxiliary heat source 
    without using the heat pump. When the Em Heat switch is in 
    the emergency heat position, the heat pump is locked out and 
    calls for heat are sent to the W1/E equipment terminal for 
    fixed stage emergency heat. Second stage emergency heat 
    energizes equipment terminals W3/Aux. Second stage 
    emergency heat is configured with DIP switch S41 and 2. 
    When the panel is in the heat pump mode, W1/E is energized 
    only in emergency heat.
    A recommended heat pump thermostat can also control 
    emergency heat from the thermostat system switch. See 
    Table 1.
    Multi-Stage Thermostats
    Use multi-stage thermostats to control up to three stages of 
    heat and two stages cool with the W1/E,W2, W3/AUX, Y1, 
    and Y2 thermostat terminals. 
    Manual and Automatic Changeover Thermostats
    Manual or automatic changeover thermostats can be used. 
    The panel determines the call for heat or cool based on which 
    was called for first. Subsequent calls for heat or cool are 
    honored when the initial call is satisfied, or 20 minutes has 
    elapsed. 
    Rebooting Microprocessor 
    To reset the panel, press and release the Boot button.The 
    system reboots and enters the Purge mode. 
    Discharge Air Temperature Sensor
    The C7735A1000 Discharge Air Temperature Sensor (not 
    included) is a supply-duct-mounted temperature probe used 
    to control capacity and prevent high limit or coil-icing. The 
    sensor attaches to the two DATS terminals on the panel. 
    When a high or low limit is reached, the panel shuts off the 
    equipment and keeps the fan operating for 2-1/2 minutes. 
    After this time, it re-energizes the equipment after the 
    discharge air recovers by 10 degrees. When the DATS 
    exceeds the high or low limit, the Heat (red) or Cool (green) 
    LED flashes.
    Set the temperature from 110°F to 160°F. See Fig. 23. The 
    recommended setting for fossil fuel/ electric systems is 160°F 
    (default factory setting). For heat pump systems, the 
    recommended setting is 120°F.   When using a heat pump 
    with dual fuel activated (DIP 5-8), the high limit will auto-
    matically be set for 120 degrees when the outputs call for 
    compressor only operation. When the outputs call for non-
    heat pump operation, the high limit will be set to the adjustable 
    110° to160°F setting.
    The cooling temperature limit can be set at 40°F or 48°F. 
    Fig. 23. DATS high-limit temperature dial.
    IMPORTANT
    Be sure the Discharge Air Temperature Sensor wir-
    ing does not run parallel with line voltage wiring 
    unless more than 12 in. of separation exists or 
    shielded cable is used.
    130  F
    MAX DUCT
    TEMP
    M19079A
    120  F
    110  F
    140  F
    150  F
    160  F 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    17 68-0259-1
    Use DIP switch 5-2 to change cooling limit settings: 
    Zone-A-Lone Switch 
    When the Zone-A-Lone switch is in the occupied (up) position 
    and the OC/OC terminals are not used, the system functions 
    as a zone control system. 
    When switched to the unoccupied (down) position, all 
    dampers are opened and all requests for heat, cool, or fan, 
    except from zone one, are not honored. 
    The zone one thermostat becomes the controlling thermostat 
    for the entire system. During long unoccupied periods, one 
    thermostat can be set back instead of adjusting each zone 
    thermostat in the building. 
    The T8601D2027 and T8611G2051 include two OC terminals. 
    When wired to the TZ-4 OC terminals, and with the Zone-A- 
    Lone switch in the occupied (up) position, the board enters the 
    unoccupied mode during the Leave and Sleep programs. This 
    feature requires two extra wires to the Zone 1 thermostat. 
    Circuit Breaker Protection 
    A built-in thermal circuit breaker protects the TotalZone panel. 
    This circuit breaker protects the panel against shorts in the 
    thermostat and damper wiring. It does not protect against 
    shorts in the wiring of the HVAC equipment into the panel.When the circuit breaker is tripped, none of the LEDs 
    illuminate and the yellow rectangular component located left 
    of the R and C terminals is hot to touch. Remove power to the 
    panel for at least five minutes to allow the circuit breaker to 
    cool off and reset. To eliminate the short, verify the dampers 
    and thermostat wiring.
    Fan On In Heat
    The system blower can be set to come on with a call for heat 
    as required for hydro-air or electric heat systems. Set the 
    blower function using DIP switch 5-6.
    When DIP switch 5-1 is set to Off for heat pump control, the 
    panel brings the fan on with a call for heat and a call for cool.
    TotalZone Add-A-Zone Panels
    Using TotalZone Add-A-Zone Panels, the system can be 
    expanded to up to 32 zones using TAZ-4 Add-A-Zone panels. 
    Two wires connect the AZ1 and AZ2 terminals on the TZ-4 to 
    the matching terminals on the TAZ board(s).
    See Fig. 15 and the TAZ installation instructions for more 
    information.
    Dip SwitchStatus
    Cooling Temperature 
    Limit
    5-2On40°F
    5-2Off48°F
    DIP Switch 5-6Fan Control
    OnHVAC system 
    OffFan on in heat 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    68-0259-1 18
    TROUBLESHOOTING 
    Table 8. Troubleshooting.
    SymptomPossible CauseAction
    No LEDs are IlluminatedNo power to the board.Check for 24 Vac (±10%) across R and C.
    Transformers out of phaseIf 48 Vac across R and T1, reverse T1 and T2 wires.
    Shorted wire.Check thermal circuit breaker. If hot, a short exists in 
    thermostat or damper wiring.
    Damper LEDs on, but no 
    other LEDs illuminated.Insufficient voltage.Check for 24 Vac (±10%) across R and C.
    Incorrect configuration.Check jumpers and DIP switches for correct configuration.
    Heat pump operates 
    incorrectly or not at all.Incorrectly wired.Verify equipment and thermostat terminal wiring.
    Incorrectly configured.Verify DIP switch configuration.
    Verify position of O/B thermostat type jumper.
    Erratic OperationEmergency Heat switch 
    on.Turn off (down) Emergency Heat switch.
    Zone-A-Lone Feature on.Turn off (up) Zone-A-Lone.
    Heat LED flashing.High limit reached.LED stops flashing with ten-degree fall and 2-1/2 minute 
    delay.
    Cool LED flashing.Low limit reached.LED stops flashing with ten-degree rise and 2-1/2 minute 
    delay.
    Purge LED flashes 
    continuously.DATS or OT problem or not 
    connected.Verify that DATS and OT (if any) are connected and wired 
    correctly.
    Add-A-Zone not operating. Incorrectly configured.
    Verify DIP switch settings on the TAZ panels.
    Incorrectly wired.
    Check AZ1and AZ2 for correct wiring.
    Verify that a separate transformer is used for each TAZ-4 
    panel.
    Be sure that AZ1 and AZ2 are at least 12 in. from line voltage 
    wiring. 
    						
    							TZ-4 TOTALZONE® ZONE CONTROL PANEL
    19 68-0259-1
    Table 9. LED Indicators.
    LEDColorIlluminatedNot IlluminatedFlashing
    HeatRedHeat call.No heat calls.High limit reached.
    CoolGreenCool call.No cool calls.Low limit reached.
    PurgeAmberPurge mode.Not in Purge mode.•DATS failure: slow flash.
    •OT failure: fast flash.
    •DATS and OT failure: 
    alternating fast and slow flash.
    FanGreenFan only call.No fan only call.—
    EM HeatRedEmergency Heat mode or 
    dual-fuel mode.Not in emergency Heat mode or 
    dual-fuel mode.—
    Zones 
    1,2,3.4GreenDamper is open or 
    opening.Damper is closed or closing.— 
    						
    							68-0259-1   G.H.   Rev. 12-02 www.honeywell.com/yourhome Automation and Control Solutions
    Honeywell Honeywell Limited-Honeywell Limitée
    1985 Douglas Drive North 35 Dynamic Drive
    Golden Valley, MN  55422 Scarborough, Ontario
    M1V 4Z9
    TZ-4 TOTALZONE® ZONE CONTROL PANEL 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Tz 4 Manual