Honeywell Tz 4 Manual
Have a look at the manual Honeywell Tz 4 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

TZ-4 TOTALZONE® ZONE CONTROL PANEL 11 68-0259-1 Fig. 16. Wiring conventional heating and cooling equipment to TZ-4 panel. Heat Pump Equipment See Fig. 17-22 for heat pump wiring. Refer to manufacturer instructions for additional wiring details and substitute the TZ-4 equipment terminals for the thermostat terminals shown. — Connect the changeover relay to O/B equipment terminal. — Set switch number 5-7 to on for O (cool) changeover, or to off for B (heat) changeover. — Set switch number 5-1 to off for heat pump equipment. — Set DIP switches 4-1, 4-2, 4-3, and 4-4. See Single Stage and Multi-Stage Operation in the Operation section. IMPORTANT Some heat pump manufacturers (such as York and Trane) use the B terminal as the transformer common. Do not connect the common from the equipment to the zone control panel.Single-Speed Compressor: Wire the compressor to the Y1 terminal. If the same heat source is used for auxiliary heat and emergency heat: — Wire a jumper from W2 (auxiliary heat) to W1/E (emergency heat). — Do not connect W3/AUX. See Fig. 17. If auxiliary heat is separate from emergency heat: — Connect the auxiliary heat to W2 jumped to W3/AUX. — Connect the emergency heat to W1/E. See Fig. 18. M20520B ZONE DAMPER MOTORS M1 - common M4 - power open M6 - power closed HVAC Equipment DIP SWITCH S4 SETTINGS 1 2ND STAGE OPERATION: TABLE 1 2 2ND STAGE OPERATION: TABLE 1 3 3RD STAGE OPERATION: TABLE 1 4 3RD STAGE OPERATION: TABLE 1 5 STAGE TIMER: TABLE 2 6 STAGE TIMER: TABLE 2 7 STAGE TIMER: TABLE 2 8 UNUSED DIP SWITCH S5 SETTINGS 1 SYSTEM TYPE 2 DATS LOW LIMIT 3 PURGE TIME 4 PURGE FAN 5 PURGE DAMPER 6 HEAT FAN 7 O/B ENERGIZED 8 DUAL FUEL LED STATES: Heat LED Heating Mode Flashing Heat LED High Limit Cool LED Cooling Mode Flashing Cool LED Low Limit Purge LED Purge Mode Flashing Purge LED Sensor Failure Fan LED Fan Mode EM Heat LED EM Heat Mode TABLE 1#1/#3 #2/#4 OPERATION 1 1 STAT 1 0 TIMER 0 1 % ZONES 0 0 OFF TABLE 2 #5 #6 #7 TIME 1 1 1 5 MIN 1 1 0 10 MIN 1 0 1 15 MIN 1 0 0 20 MIN 0 1 1 30 MIN 0 1 0 40 MIN 0 0 1 50 MIN 0 0 0 60 MIN ON OFF 1 0 CONV HP 40F 48F 2.0 MIN 3.5 MIN HVAC PANEL NO CHG OPEN HVAC PANEL COOL HEAT DISABLED ENABLED R HRCW1/E W 2W3/AUXZONE LEDs ON Damper open or opening OFF Damper closed or closing MOMENTARY PUSH BUTTONS Boot – Clears microprocessor Purge Overide – Bypass Purge Mode BOOTPURGE OVERRIDE Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). 1 “C” terminal connection is not required on battery powered, power stealing, or some electromechanical thermostats. 2 Leave jumper disconnected for conventional thermostats. R C T1 T2 AZ2 AZ1 OFF ON EM Heat UnoccupOccup Zone- A-Lone Y1Y2GO/B Heating Transformer 24 VAC Equip. Cooling Transformer First Stage Heating Second Stage Heating Relay Third Stage Heating First Stage Cooling Relay Second Stage Cooling Relay Fan Relay This diagram shows the typicalthree-stage equipment, thermostat,and damper motor connections.For specific wiring for otherthermostats, damper motors, andHVAC Equipment, refer to the nstallation Instructions. M6 M4M1 DATS DATS 1 Zone 4 Thermostat CR C R Power-closed Spring-open (Model ZD)Power-closed Spring-open (Model ARD)Power-closed Spring-open (Model ARD) 24VAC, 40VA Transformer (Required if more than four dampers ) 24VAC, 40VA Transformer OCOCRemote Zone-A-Lone Add-A-Zone Panel(s) DAMPER XFRM PANEL XFRM HEATCOOLPURGEFANEM. HEATZONE 1ZONE 2ZONE 3 ZONE 4 DIP SWITCH S4DIP SWITCH S5 1O N 2345678 1 O N 2345678 M6 M4M1 1 Zone 3 Thermostat M6 M4M1 1 Zone 2 Thermostat 456Z 123X Power-open Power-closed (Opposed Blade Damper Motors) O/B Y2 GW2M6M4M1W3/ AUXY1W1/ ER C Y1 W3/ AUX W2 W1 R CY2GLO/B Y1 W3/ AUX W2 W1 R CY2GLO/B Y1 W3/ AUX W2 W1 R CY2GLO/B Y1 W3/ AUX W2 W1 R CY2GLO/B LO/B Y2 GW2W3/ AUX Y1 W1/ E R C LO/B Y2 GW2W3/ AUX Y1 W1/ E R C LO/B Y2 GW2W3/ AUX Y1 W1/ E R C L 1 Zone 1 Thermostat ZONE 12Thermostat DATSOT OTOT Sensor130 F 120 F 110 F140 F 150 F 160 F MAX. DUCT TEMP. 25 F 20 F 15 F35 F 30 F 40 F 45 F DUAL FUEL OT SETTING DamperZONE 22ThermostatDamperZONE 32ThermostatDamperZONE 42ThermostatDamper

TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 12 Fig. 17. Wiring single-stage heat pump with auxiliary heat. Fig. 18. Wiring single-stage heat pump with separate auxiliary and emergency heat. Two-speed Compressor: Wire the first stage compressor to Y1 and the second stage compressor to Y2. If the same heat source is used for auxiliary heat and emergency heat: — Wire a jumper from W3/AUX (auxiliary heat) to W1/E (emergency heat), see Fig. 19. If auxiliary heat is separate from emergency heat: — Wire the auxiliary heat to W3/AUX. — Wire emergency heat to W1/E, see Fig.20.Fig. 19. Wiring two-stage heat pump with auxiliary heat. Fig. 20. Wiring two-stage heat pump with separate auxiliary and emergency heat. Dual Fuel Heat Pumps: Install C7089B1000 Outdoor Temperature Sensor to terminals OT and OT. — Set outdoor sensor setting to: — Balance point temperature of heat pump or — Outdoor temperature above which the heat pump is to be used and below which the fossil fuel is to be used. — Set DIP switch number 5-8 to off for dual fuel operation. — Connect compressor to Y1. See Fig. 21. — Connect fossil fuel heat to W1/E. — Connect second stage of fossil fuel to W3/AUX. — Connect second stage of compressor to Y2. See Fig. 22. M20521B HVAC Equipment RHRCW1/E W 2W3/AUX Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). Y 1Y2G O/B Heating Transformer 24 VAC Equip. Cooling Transformer Auxiliary Heat Compressor Reversing Valve Fan Relay 1 1 FIELD INSTALLED JUMPER. M20522B HVAC Equipment RHRCW1/E W 2W3/AUX Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). Y 1Y2G O/B Heating Transformer 24 VAC Equip. Cooling Transformer Emergency Heat Auxiliary Heat Compressor Reversing Valve Fan Relay 1 FIELD INSTALLED JUMPER. 1 M20523B HVAC Equipment RHRCW1/E W 2W3/AUX Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). Y 1Y2G O/B Heating Transformer 24 VAC Equip. Cooling Transformer Auxiliary Heat First Stage Compressor Second Stage Compressor Reversing Valve Fan Relay 1 1 FIELD INSTALLED JUMPER. M20524A HVAC Equipment RHRCW1/E W 2W3/AUX Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). Y 1Y2G O/B Heating Transformer 24 VAC Equip. Cooling Transformer Emergency Heat Auxiliary Heat First Stage Compressor Second Stage Compressor Reversing Valve Fan Relay

TZ-4 TOTALZONE® ZONE CONTROL PANEL 13 68-0259-1 Fig. 21. Dual Fuel with single-stage heat pump and single- stage fossil fuel. Fig. 22. Dual fuel with two-stage heat pump and one- or two-stage fossil fuel. Water Source Heat Pumps Wire the equipment, as applicable, to the TZ-4 as shown in Fig. 17-19. Refer to manufacturer instructions for additional wiring instructions and substitute the TZ-4 equipment terminals for the thermostat terminals shown. — Wire first stage compressor to Y1, second stage compressor to Y2. — Connect auxiliary heat to W3/AUX and emergency heat to W1/E. — If auxiliary heat and emergency heat are the same, wire a jumper from W1/E to W3/AUX. — Connect changeover relay to O/B equipment terminal. — Set DIP switch 5-7 to on for O (cool) changeover, or to off for B (heat) changeover. — Set DIP switch 5-1 to off for heat pump equipment. STARTUP AND CHECKOUT After the installation is complete, verify correct operation: 1.Place the Em Heat switch in the Off (down) position. 2.Place the Zone-A-Lone switch in the Occup/Remote (up) position. 3.Verify that DIP switches are set correctly. See Sequence of Operation section and Table 8 for correct configuration. 4.Power up the TZ-4 and set the thermostats so no zones are calling. The board then enters the Purge mode where all dampers open and the fan operates for two or three and one-half minutes (configurable). (If there is no Discharge Air Temperature Sensor connected to the panel, the purge LED flashes in all modes other than purge.) The damper LEDs are green to indicate the dampers are open. Press Purge Override button on panel to exit Purge mode. 5.Set zone one thermostat to heat and raise the setpoint to call for heat. Verify that the heat LED is red and zone one damper remains green while the other damper LEDs turn off. 6.Raise zone two setpoint to call for heat. Lower zone one setpoint to stop the call for heat to that zone. Verify that zone one LED turns off and zone two LED turns green. 7.Repeat for zones three and four. 8.Alternately, lower the setpoint to call for cooling. Verify that the green cool LED illuminates. OPERATION Identifying DIP Switches This panel has two banks of DIP switches, DIP switch 4 (S4) and DIP switch 5 (S5). Each bank has eight individual switches that are identified by two numbers; the first number is the bank number (4 or 5) and the second number identifies the individual switch. For example, DIP 5-1 is bank 5, switch 1. Sequence of Operation • When there is no call for heat, cool or fan, the board is in idle mode, no system LEDs are illuminated and the green damper LEDs indicate open. • On a call for heat, cool, or fan, the calling zone damper stays open, and other zone dampers close: — TZ-4 panel energizes the HVAC equipment and condi- tioned air is delivered to the calling zone. — Heat LED (red), cool LED (green), or fan LED (green) illuminates to indicate equipment operation. — Fan LED illuminates only on a call for circulation; it does not illuminate during a call for heat or cool. — When the call is satisfied, the system enters the Purge mode. After purge, all dampers return to the Open position, depending on the setting of DIP switch S5-5. • Any zone thermostat can call for heating or cooling. If there are co-existing calls for heat and cool, the panel accepts the first call. • Once that call is satisfied, or a maximum of 20 minutes has elapsed, the panel switches to allow the opposite call after completing Purge mode. M20525A HVAC Equipment RHRCW1/E W 2W3/AUX Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). Y 1Y2G O/B Heating Transformer 24 VAC Equip. Cooling Transformer First Stage Fossil Fuel First Stage Compressor Reversing Valve Fan Relay M20526A HVAC Equipment RHRCW1/E W 2W3/AUX Single Transformer Heating/Cooling systems require a jumper to be installed connecting R H and RC (factory installed). Y 1Y2G O/B Heating Transformer 24 VAC Equip. Cooling Transformer First Stage Fossil Fuel Second Stage Fossil Fuel First Stage Compressor Second Stage Compressor Reversing Valve Fan Relay

TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 14 Purge Mode At the end of every call for heat or cool, the panel enters a Purge mode that holds open the calling zone damper for two (default) or three and one-half minutes. During this time, the panel or the HVAC equipment can be configured to operate the fan. The Purge LED lights to signal that the system is in the Purge mode. Pressing the purge override button overrides the Purge mode. Unless there is a new call for heat or cool during the Purge mode, all dampers are moved to the Open position at the end of purge. The panel can be configured to open all dampers during the purge mode. Individual Zone Fan Control When all zones are satisfied, the fan switch of each thermostat controls the fan operation for that zone. — When the fan switch is in the On position, the fan is energized, and dampers close to zones where fan switch is in Auto position. — During a call for heat or cool at this time, the circulation mode ceases, and the heat or cool call is honored. — When the zone calling is satisfied, the circulation call resumes. Single and Multi-Stage Operation The panel can control up to three stages of heating and two stages of cooling: — First stage is energized by the thermostat. — Second stage of heating or cooling and third stage of heating can be energized by the thermostat, timer, or the percentage of zones calling. (For instance, first and second stage of heat and cool can be thermostat energized and third stage heat can be configured for timer energizing.) — See Tables 5 and 6 for second and third stage configuration. Note that second and third stage can be controlled differently. Set stages not used to Off.DIP Switch bank 4, switches 1-4, are used to configure the staging method: — Switches 1 and 2 configure second stage control. See Table 4. — Switches 3 and 4 configure third stage control. See Table. 5. — When stage two or three is not used, disable that stage by turning off the corresponding switches. Single Stage If equipment is single stage, set bank 4, DIP switches 1-4 Off: THERMOSTAT-CONTROLLED STAGES Use a thermostat that energizes W2 and Y2 for second stage of heat and cool, and W3 for third stage of heat. Configure for thermostat as shown in Tables 4 and 5. TIMER-CONTROLLED STAGES — The Timer energizes second stage of heat or cool after the first stage begins calling for the set amount of time. — The third stage of heat is energized once the second stage of heat is calling for the set amount of time. — Second and third stages remain energized until the call for heat or cool is satisfied. See Table 6 for stage timer configuration of DIP switch bank 4, switches 5, 6, and 7. PERCENTAGE OF ZONES CALLING—CONTROLLED STAGES Percentage of zones calling energizes second or third stage based on the percentage of zones called for heat or cool on the TZ-4 and TAZ-4. The percentage of zones necessary to turn stages two and three on and off: DIP Switch NumberStatusPurge Operation 5-3Off3.5 minutes 5-3On2 minutes 5-4OffPanel control of fan in purge 5-4OnHVAC control of fan in purge 5-5OffAll dampers open during purge 5-5On Damper positions unchanged during purge DIP Switch NumberStageStatus 4-12nd Sta geOff 4-22nd Sta geOff 4-33rd StageOff 4-43rd StageOff StageOnOff Stage 2 Heat>33%33%66%

TZ-4 TOTALZONE® ZONE CONTROL PANEL 15 68-0259-1 HEAT PUMP OPERATION The panel can control single- or two-stage heat pumps with or without auxiliary heat. Set DIP switch 5-1 to Off for heat pump control. This energizes equipment terminal Y1 on a call for first stage heat or cool. If second stage is configured to operate with DIP switch 4-1 and 4-2, Y2 energizes to call for second stage compressor. When in heat pump mode, the panel energizes the fan with a call for heat and a call for cool. Configure DIP switch 5-7 for correct changeover valve control. See Table 7. DUAL FUEL OPERATION The panel can control a heat pump and a fossil fuel furnace in a dual-fuel application. A C7089B1000 Outdoor Temperature Sensor is wired to the OT and OT terminals on the TZ-4 to switch the panel from heat pump to fossil fuel operation. DIP switch 5-8 is set to Off to enable dual-fuel operation. The dual-fuel OT setting (see Fig. 16 for location) is set to the outdoor temperature that locks out the heat pump and uses the fossil fuel mode. The fan is energized by the panel for two minutes after the changeover and the Em Ht LED illuminates when in the fossil fuel mode. IMPORTANT A C7089B1000 Outdoor Temperature Sensor and a C7735A1000 Discharge Air Temperature Sensor are required for dual fuel operation. Table 4. DIP Switch Bank 4, Stage 2 Configuration. Operation Switch 4-1 Switch 4-2 Thermostat On On Timer On Off % of Zones Off On Off Off Off Table 5. DIP Switch Bank 4, Stage 3 Configuration. Operation Switch 4-3 Switch 4-4 Thermostat On On Timer On Off % of zones calling Off On Off Off Off Table 6. DIP Switch Bank 4, Stage Timer Configuration. TimeDIP Switch 4-5DIP Switch 4-6DIP Switch 4-7 5 minutesOnOnOn 10OnOnOff 15OnOffOn 20OnOffOff 30OffOnOn 40OffOnOff 50OffOffOn 60OffOffOff Table 7. DIP Switch Bank 5 Settings and Functions. DIP Switch Function On (Default) Off 5-1System TypeConventionalHeat Pump 5-2DATS low limit.40°F48°F 5-3Purge mode timing.Two minutes.Three and one-half minutes. 5-4Fan control during purge.HVAC controlled.Panel controlled. 5-5Damper control during purgeLast zone(s) calling open.All dampers open. 5-6Fan control in heat.Fan controlled by panel in cool and HVAC equipment in heat.Panel in heat and cool controlling fan. 5-7Operation of O/B heat pump changeover equipment terminal.O/B equipment terminal is energized in cool (O).O/B equipment terminal is energized in heat (B). 5-8Dual fuel operation.Disabled.Enabled.

TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 16 Thermostat Operation Conventional Thermostats Conventional (R,W,Y,G) heat/cool thermostats can be used with the TZ-4 to control single or multi-stage gas, electric or oil systems and heat pumps with auxiliary heat. The panel can be configured to control second stage heat and cool and third stage heat using a 5-60 minute timer, or staging can be controlled by the percentage of zones calling. When using conventional thermostats on heat pump applications, set DIP switch 5-1 to Off for heat pump equipment. Set DIP switch 5-7 for correct reversing valve operation. See Table 7. Heat Pump Thermostats HEAT PUMP THERMOSTATS WITH SINGLE Y OUTPUT Thermostats that have a single Y terminal for first stage heat and cool and those with separate Y1 and W1 can be used. Thermostats of either wiring type can be used on any zone. For thermostats with a single Y, the reversing valve wire must be connected to O/B: — Connect the thermostat Y terminal to Y1 on the panel. — If the thermostat energizes O on a call for cool, connect the O/B jumper located near the thermostat wiring terminals. — If the thermostat energizes B on a call for heat, leave the O/B jumper disconnected. HEAT PUMP THERMOSTATS WITH SEPARATE Y1 AND W1 TERMINALS Heat pump thermostats with separate Y1 and W1 terminals for first stage heat and cool are wired to Y1 and W1/E. Leave the O/B jumper, located near the thermostat wiring terminals, disconnected. Emergency Heat Control Emergency heat is defined as using an auxiliary heat source without using the heat pump. When the Em Heat switch is in the emergency heat position, the heat pump is locked out and calls for heat are sent to the W1/E equipment terminal for fixed stage emergency heat. Second stage emergency heat energizes equipment terminals W3/Aux. Second stage emergency heat is configured with DIP switch S41 and 2. When the panel is in the heat pump mode, W1/E is energized only in emergency heat. A recommended heat pump thermostat can also control emergency heat from the thermostat system switch. See Table 1. Multi-Stage Thermostats Use multi-stage thermostats to control up to three stages of heat and two stages cool with the W1/E,W2, W3/AUX, Y1, and Y2 thermostat terminals. Manual and Automatic Changeover Thermostats Manual or automatic changeover thermostats can be used. The panel determines the call for heat or cool based on which was called for first. Subsequent calls for heat or cool are honored when the initial call is satisfied, or 20 minutes has elapsed. Rebooting Microprocessor To reset the panel, press and release the Boot button.The system reboots and enters the Purge mode. Discharge Air Temperature Sensor The C7735A1000 Discharge Air Temperature Sensor (not included) is a supply-duct-mounted temperature probe used to control capacity and prevent high limit or coil-icing. The sensor attaches to the two DATS terminals on the panel. When a high or low limit is reached, the panel shuts off the equipment and keeps the fan operating for 2-1/2 minutes. After this time, it re-energizes the equipment after the discharge air recovers by 10 degrees. When the DATS exceeds the high or low limit, the Heat (red) or Cool (green) LED flashes. Set the temperature from 110°F to 160°F. See Fig. 23. The recommended setting for fossil fuel/ electric systems is 160°F (default factory setting). For heat pump systems, the recommended setting is 120°F. When using a heat pump with dual fuel activated (DIP 5-8), the high limit will auto- matically be set for 120 degrees when the outputs call for compressor only operation. When the outputs call for non- heat pump operation, the high limit will be set to the adjustable 110° to160°F setting. The cooling temperature limit can be set at 40°F or 48°F. Fig. 23. DATS high-limit temperature dial. IMPORTANT Be sure the Discharge Air Temperature Sensor wir- ing does not run parallel with line voltage wiring unless more than 12 in. of separation exists or shielded cable is used. 130 F MAX DUCT TEMP M19079A 120 F 110 F 140 F 150 F 160 F

TZ-4 TOTALZONE® ZONE CONTROL PANEL 17 68-0259-1 Use DIP switch 5-2 to change cooling limit settings: Zone-A-Lone Switch When the Zone-A-Lone switch is in the occupied (up) position and the OC/OC terminals are not used, the system functions as a zone control system. When switched to the unoccupied (down) position, all dampers are opened and all requests for heat, cool, or fan, except from zone one, are not honored. The zone one thermostat becomes the controlling thermostat for the entire system. During long unoccupied periods, one thermostat can be set back instead of adjusting each zone thermostat in the building. The T8601D2027 and T8611G2051 include two OC terminals. When wired to the TZ-4 OC terminals, and with the Zone-A- Lone switch in the occupied (up) position, the board enters the unoccupied mode during the Leave and Sleep programs. This feature requires two extra wires to the Zone 1 thermostat. Circuit Breaker Protection A built-in thermal circuit breaker protects the TotalZone panel. This circuit breaker protects the panel against shorts in the thermostat and damper wiring. It does not protect against shorts in the wiring of the HVAC equipment into the panel.When the circuit breaker is tripped, none of the LEDs illuminate and the yellow rectangular component located left of the R and C terminals is hot to touch. Remove power to the panel for at least five minutes to allow the circuit breaker to cool off and reset. To eliminate the short, verify the dampers and thermostat wiring. Fan On In Heat The system blower can be set to come on with a call for heat as required for hydro-air or electric heat systems. Set the blower function using DIP switch 5-6. When DIP switch 5-1 is set to Off for heat pump control, the panel brings the fan on with a call for heat and a call for cool. TotalZone Add-A-Zone Panels Using TotalZone Add-A-Zone Panels, the system can be expanded to up to 32 zones using TAZ-4 Add-A-Zone panels. Two wires connect the AZ1 and AZ2 terminals on the TZ-4 to the matching terminals on the TAZ board(s). See Fig. 15 and the TAZ installation instructions for more information. Dip SwitchStatus Cooling Temperature Limit 5-2On40°F 5-2Off48°F DIP Switch 5-6Fan Control OnHVAC system OffFan on in heat

TZ-4 TOTALZONE® ZONE CONTROL PANEL 68-0259-1 18 TROUBLESHOOTING Table 8. Troubleshooting. SymptomPossible CauseAction No LEDs are IlluminatedNo power to the board.Check for 24 Vac (±10%) across R and C. Transformers out of phaseIf 48 Vac across R and T1, reverse T1 and T2 wires. Shorted wire.Check thermal circuit breaker. If hot, a short exists in thermostat or damper wiring. Damper LEDs on, but no other LEDs illuminated.Insufficient voltage.Check for 24 Vac (±10%) across R and C. Incorrect configuration.Check jumpers and DIP switches for correct configuration. Heat pump operates incorrectly or not at all.Incorrectly wired.Verify equipment and thermostat terminal wiring. Incorrectly configured.Verify DIP switch configuration. Verify position of O/B thermostat type jumper. Erratic OperationEmergency Heat switch on.Turn off (down) Emergency Heat switch. Zone-A-Lone Feature on.Turn off (up) Zone-A-Lone. Heat LED flashing.High limit reached.LED stops flashing with ten-degree fall and 2-1/2 minute delay. Cool LED flashing.Low limit reached.LED stops flashing with ten-degree rise and 2-1/2 minute delay. Purge LED flashes continuously.DATS or OT problem or not connected.Verify that DATS and OT (if any) are connected and wired correctly. Add-A-Zone not operating. Incorrectly configured. Verify DIP switch settings on the TAZ panels. Incorrectly wired. Check AZ1and AZ2 for correct wiring. Verify that a separate transformer is used for each TAZ-4 panel. Be sure that AZ1 and AZ2 are at least 12 in. from line voltage wiring.

TZ-4 TOTALZONE® ZONE CONTROL PANEL 19 68-0259-1 Table 9. LED Indicators. LEDColorIlluminatedNot IlluminatedFlashing HeatRedHeat call.No heat calls.High limit reached. CoolGreenCool call.No cool calls.Low limit reached. PurgeAmberPurge mode.Not in Purge mode.•DATS failure: slow flash. •OT failure: fast flash. •DATS and OT failure: alternating fast and slow flash. FanGreenFan only call.No fan only call.— EM HeatRedEmergency Heat mode or dual-fuel mode.Not in emergency Heat mode or dual-fuel mode.— Zones 1,2,3.4GreenDamper is open or opening.Damper is closed or closing.—

68-0259-1 G.H. Rev. 12-02 www.honeywell.com/yourhome Automation and Control Solutions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 TZ-4 TOTALZONE® ZONE CONTROL PANEL