Home > American Water Heater > Gas Heater > American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual

American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							21
    • Centrotherm InnoFlue vent system
    AL29-4C Stainless Steel - See page 29
    •  HeatFab Saf-T Vent
    •  Duravent FasNSeal
    NOTE:  The use of cellular core PVC (ASTM F891), cellular core 
    CPVC,  or  Radel®  (polyphenolsulfone)  in  non-metallic  venting 
    systems  is  prohibited.  Covering  non-metallic  vent  pipe  and 
    fittings with thermal insulation is prohibited.
    CATEGORY IV APPLIANCE
    Category  IV  appliances  operate  with  a  positive  vent  (exhaust) 
    static  pressure  and  with  vent  gas  temperatures  low  enough  to 
    produce condensate in the vent piping.
    POWER VENT CONFIGURATION
    Power  Vent  configurations  derive  all  combustion  air  from  the 
    room  where  they  are  installed  and  discharge  all  flue  gases  to 
    the  outdoor  atmosphere  through  a  sealed  vent  (exhaust)  pipe. 
    Power vent configurations have one vent pipe connected to the 
    water  heater  which  can  be  terminated  in  a  vertical  or  horizontal 
    arrangement. See Figure 36 and Figure 37 on page 34.
    DIRECT VENT CONFIGURATION
    Direct  Vent  configurations  derive  all  combustion  air  directly 
    from the outdoor atmosphere through a sealed intake air pipe 
    and discharge all flue gases to the outdoor atmosphere through 
    a  sealed  vent  (exhaust)  pipe.  Direct  Vent  configurations  have 
    two pipes connected to the water heater, one vent pipe and one 
    intake air pipe. Direct Vent configurations can be terminated in 
    one  of  seven  different  arrangements.  See  Figure  38  on  page 
    34 through Figure 44 on page 35.
    GENERAL VENTING INSTRUCTIONS
    These instructions must be followed on all installations.
    1.  DO NOT   install  the  water  heater  in  a  Power  Vent 
    configuration  unless  there  is  adequate  supply  of  fresh  air, 
    see  Air Requirements on page 17. If the installation space 
    does not provide an adequate supply of fresh air the water 
    heater must be installed in a Direct Vent configuration.
    2.  If  the  water  heater  is  to  be  installed  in  a  beauty  shop, 
    barber  shop,  cleaning  establishment,  a  laundry  with  dry 
    cleaning equipment or any space with contaminated air it is 
    imperative that the water heater(s) be installed in a Direct 
    Vent configuration so that all air for combustion is derived 
    from the outdoor atmosphere.
    3.  The vent and intake air piping must terminate outdoors.
    4.  The minimum clearance from combustible materials for the 
    vent (exhaust) and intake air piping shall be 0 inches. Vent 
    piping  passing  through  a  combustible  wall  or  ceiling  must 
    be a continuous run (no joints).
    5.  The  water  heater  must  be  protected  from  freezing 
    downdrafts during shutdown periods.
    6.  The vent (exhaust) pipe must not be combined or connected 
    to any other appliance’s vent system or chimney.
    7.  The intake air pipe must not be combined or connected to 
    any other appliance’s intake air piping.
    8.  Locate  the  water  heater  where  the  vent  (exhaust)  and 
    intake air piping will remain within the maximum equivalent 
    lengths allowed. See Venting Requirements on page 22.
    9.  Do not install the vent or intake air piping in a manner that 
    will allow water to be trapped in the piping.
    10.  Vent pipes must be pitched a minimum of a 1/4 inch per foot 
    back to the water heater (to allow drainage of condensate).
    11.  Do not anchor the vent or intake air pipe directly to framed 
    walls, floors or ceilings unless rubber isolation pipe hangers 
    are used to prevent vibration noise from being transmitted.
    12.  Use only approved vent/intake air pipe sizes and materials. 
    See Venting Requirements on page 22.
    VENTING INSTALLATION
    Breathing carbon monoxide can cause brain damage or death.
    Always read and understand the instruction manual .
    Install vent system in accordance with codes. 
    Do not operate water heater if exposed to flooding or
    water damage
    Special consideration must be taken with installations
    above 10,000 feet (3,048 m) refer to high altitude
    section of this manual.
    Breathing Hazard - Carbon Monoxide Ga s
    
    
    Do not operate if soot buildup.Do not obstruct water heater air intake with insulating
    jacket or blanket.
    Do not place chemical vapor emitting products near
    water heater.
    Gas and carbon monoxide detectors are available.Never operate the heater unless it is vented to th e
    outdoors and has adequate air supply to avoid risks
    of improper operation, fire, explosion or asphyxiation .
    Analyze the entire vent system to make sure that
    condensate will not become trapped in a section of
    vent pipe and therefore reduce the open cross
    sectional area of the vent. 
    Never  operate  water  heater  unless  it  is  vented  to  the  outdoors. 
    Instructions  in  this  section  of  the  manual  must  be  followed  to 
    avoid  choked  combustion  or  recirculation  of  flue  gases.  Such 
    conditions  cause  sooting  of  the  combustion  chamber,  burners 
    and flue tubes and creates a risk of asphyxiation.
    GENERAL VENTING INFORMATION
    The  water  heaters  covered  in  this  manual  are  operationally 
    equivalent  to  Category  IV  appliances  and  may  be  installed  in 
    either a Power Vent or Direct Vent configuration.
    APPROVED MATERIALS
    Approved vent and intake air pipe materials that may be used 
    in the United States:
    PVC pipe materials:
    • DWV ASTM-D2665 or CSA B181.2
    •  Schedule 40, 80, 120 ASTM-D1785 or CSA B137.3
    •  SDR Series ASTM-D2241 or CSA B137.3
    CPVC pipe materials:
    •  CPVC 41 ASTM-D2846 or CSA B137.6
    •  Schedule 40, 80 ASTM-F441 or CSA B137.6
    •  SDR Series ASTM-F442
    Polypropylene - See page 28
    •  M & G Duravent Polypro vent system
    •  Centrotherm InnoFlue vent system
    AL29-4C Stainless Steel - See page 29
    •  HeatFab Saf-T Vent
    •  Duravent FasNSeal
    Approved vent pipe materials that must be used in Canada:
    •  ULC S636 PVC / CPVC
    •  ULC S636 Polypropylene - See Page 27.
    •  AL29-4C Stainless Steel - See Page 28.
    Intake air pipe materials that may be used in Canada:
    PVC pipe materials:
    •  DWV ASTM-D2665 or CSA B181.2
    •  Schedule 40, 80, 120 ASTM-D1785 or CSA B137.3
    •  SDR Series ASTM-D2241 or CSA B137.3
    CPVC pipe materials:
    •  CPVC 41 ASTM-D2846 or CSA B137.6
    •  Schedule 40, 80 ASTM-F441 or CSA B137.6
    •  SDR Series ASTM-F442
    Polypropylene - See page 28
    •  M & G Duravent Polypro vent system  
    						
    							22
    Six Inch Pipe
    The  water  heaters  covered  in  this  manual  are  certified  to 
    a  maximum  length  of  6  inch  pipe  for  the  exhaust  venting 
    arrangement  of  120  equivalent  feet  (36.5  m).  The  certified 
    maximum  length  of  6  inch  pipe  for  intake  air  piping  is  also  120 
    equivalent  feet  (36.5  m).  IE:  On  Direct  Vent  installations  both 
    pipes can be up to 120 equivalent feet (36.5 m).
    INTAKE AIR AND VENT PIPE CLEARANCES
    The minimum clearance from combustible materials for the vent 
    (exhaust) and intake air piping shall be 0 inches. Vent or intake 
    air piping passing through a combustible wall or ceiling must be 
    a continuous run (no joints).
    MINIMUM EQUIVALENT LENGTHS
    Four Inch Pipe
    The  water  heaters  covered  in  this  manual  are  certified  to 
    a  minimum  length  of  4  inch  pipe  for  the  vent  (exhaust)  of  15 
    equivalent  feet  (4.6  m).  There  is  no  minimum  equivalent  feet 
    requirement for the intake air pipe.
    Six Inch Pipe
    The  water  heaters  covered  in  this  manual  are  certified  to 
    a  minimum  length  of  6  inch  pipe  for  the  vent  (exhaust)  of  70 
    equivalent  feet  (21.3  m).  There  is  no  minimum  equivalent  feet 
    requirement for the intake air pipe.
    MAXIMUM NUMBER OF ELBOWS
    The vent pipe may have a maximum of six 90° elbows installed. 
    The  intake  air  pipe  may  have  a  maximum  of  six  90°  elbows 
    installed. IE: in a Direct Vent configuration each pipe can have up 
    to six (6) 90° elbows installed. Two (2) 45° elbows equal one (1) 
    90° elbow. Each 90° elbow is equivalent to 5 feet (1.5 m) of linear 
    pipe, 45° elbows are equivalent to 2.5 feet (0.75 m) of linear pipe.
    Note:  Refer  to Table  10  and Table  11  for  equivalent  linear  pipe 
    length of AL29-4C
    ® 45° and 90° elbows.
    FACTORY SUPPLIED FITTINGS
    The  water  heater  ships  with  two  (2)  factory  supplied  4  inch 
    terminations  (PVC  45°  elbows  with  debris  screen).  Factory 
    supplied  vent  and  intake  air  terminations  or  concentric  and  low 
    profile terminations must be used. Factory supplied terminations 
    and  installed  fittings  (exhaust  elbow  and  intake  air  connection) 
    add zero equivalent feet to the vent and intake air piping.
    NOTE:  3  inch  vent  and/or  intake  pipe  as  well  as  3  inch 
    terminations  previously  used  on  older  (A)HCG3  119T  300/400 
    models must be replaced with 4 inch or 6 inch pipe and 4 inch or 
    6 inch terminations depending on installed length.
    TABLE 7-PVC/CPVC and Polypropylene
    Number of 
    90° Elbows  Installed 4 Inch Pipe
    6 Inch Pipe
    Maximum Feet (Meters) Maximum Feet (Meters)
    One (1) 65 feet (19.8 meters) 115 feet (35.0 meters)
    Two (2) 60 feet (18.2 meters) 110 feet (33.5 meters)
    Three (3) 55 feet (16.8 meters) 105 feet (32.0 meters)
    Four (4) 50 feet (15.2 meters) 100 feet (30.5 meters)
    Five (5) 45 feet (13.7 meters) 95 feet (29.0 meters)
    Six (6) 40 feet (12.2 meters) 90 feet (27.4 meters)
    6 INCH EXTENDED VENT TERMINATIONS
    When 6 inch intake air or vent pipe is installed using standard 
    terminations,  factory  supplied  6  inch  terminations  must  be 
    used. Contact your local distributor or call the parts department 
    (phone number listed on the back cover of this manual) to order 
    6  inch  termination(s).  See  Optional  Direct  Vent  Terminations 
    on page 12.
    13. Use only factory supplied vent and intake air, concentric or low 
    profile terminations. See Venting Requirements on page 22.
    14.  Do not locate the vent (exhaust) or intake air terminations 
    where  they  would  be  objectionable  due  to  noise  at  the 
    termination(s).  This  includes  locations  close  to  or  across 
    from windows and doors.
    15.  Direct venting into dead air spaces such as alleys, atriums, 
    and  inside  corners  can  cause  recirculation  of  flue  gases. 
    Recirculation  of  flue  gases  will  cause  sooting,  premature 
    failure  of  the  heat  exchanger  and  icing  of  the  combustion 
    air  intake  during  severe  cold  weather.  To  prevent  the 
    recirculation  of  flue  gases,  maintain  as  much  distance  as 
    possible between the intake air and vent terminations.
    16.  Do not locate the vent termination over a public area where 
    condensate or vapor can cause a nuisance or ice hazard.
    17.  Ensure the screens in the factory supplied terminations are 
    securely installed to prevent blockage in the vent system.
    18.  Stress  levels  in  pipe/fittings  can  be  significantly  increased 
    by  improper  installation.  If  rigid  pipe  clamps  are  used  to 
    hold  the  pipe  in  place,  or  if  the  pipe  cannot  move  freely 
    through a wall penetration, the pipe may be stressed, or high 
    thermal  stresses  may  be  formed  when  the  pipe  heats  up 
    and expands. Install accordingly to minimize such stresses.
    19.  Carefully  read  Venting  Requirements  on  page  22  and  then 
    proceed to the Venting Installation Sequence on page 23.
    VENTING REQUIREMENTS
    FIELD SUPPLIED FITTINGS
    Field supplied fittings should be equivalent to the piping material 
    being installed. Field installed/supplied fittings will add equivalent 
    feet  to  the  vent  or  intake  air  piping  as  indicated  below. All  field 
    supplied/installed  fittings  and  piping  must  be  factored  into  the 
    equivalent feet calculations. 
    •  90° elbows (short or long radius) are equivalent to 5 linear 
    feet (152 cm) of pipe. 
    •  45° elbows (short or long radius) are equivalent to 2.5 linear 
    feet (76 cm) of pipe.
    Note:  Refer  to Table  10  and Table  11  for  equivalent  linear  pipe 
    length of AL29-4C
    ® 45° and 90° elbows.
    PRIMER AND CEMENT
    Tetrahydrofuran  (THF)  primer  should  be  used  to  prepare  the 
    surfaces of pipe and fittings for solvent welding. If CPVC pipe and 
    fittings are used, then the proper cement must be used for all joints, 
    including joining the pipe to the factory provided terminations (PVC 
    material). PVC Materials should use ASTM D-2564 Grade Cement; 
    CPVC Materials should use ASTM F-493 Grade Cement.
    PIPE SIZE REQUIREMENTS
    The water heaters covered in this manual are certified for the use 
    of 4 and 6 inch pipe for the vent (exhaust) and intake air piping. 
    If  the  installed  equivalent  length  for  the  intake  air  or  vent  piping 
    will be 70 feet (21.3 m) or less, 4 inch pipe must be used. If the 
    installed equivalent length will be more than 70 feet (21.3 m), 6 
    inch pipe must be used.
    NOTE:  Install  the  pipe  size  required  for  the  installed  equivalent 
    length of each pipe independently. IE: If the intake air pipe will be 
    70 equivalent feet or less and the vent pipe will be more than 70 
    equivalent feet; the intake air pipe must be installed using 4 inch 
    pipe and the vent must be installed using 6 inch pipe.
    MAXIMUM EQUIVALENT LENGTHS
    Four Inch Pipe
    The  water  heaters  covered  in  this  manual  are  certified  to  a 
    maximum length of 4 inch pipe for the exhaust venting arrangement 
    of  70  equivalent  feet  (21.3  m).  The  certified  maximum  length  of 
    4  inch  pipe  for  intake  air  piping  is  also  70  equivalent  feet  (21.3 
    m).  IE:  On  Direct  Vent  installations  both  pipes  can  be  up  to  70 
    equivalent feet (21.3 m).   
    						
    							23
    9. All vent (exhaust) pipes must be pitched a minimum of a 1/4 
    inch  per  foot  back  to  the  water  heater  (to  allow  drainage  of 
    condensate).
    10.  If  installing  4  inch  vent  pipe  connect  the  vent  pipe  to  the 
    exhaust elbow on the water heater.
    11.  If  installing  6  inch  pipe  transition  to  4  inch  pipe  as  shown  in 
    Figure  15.  The  field  installed  4”  pipe  between  the  exhaust 
    elbow and the 6” x 4” reducer coupling should be 18 inches 
    (45 cm) or less in length.
    DIRECT VENT INSTALLATION
    1. Read the General Venting Instructions on page 21 and Venting 
    Requirements on page 22 before proceeding. These instructions 
    and requirements must be followed in addition to the instructions 
    below that are specific for Direct Vent configurations.
    2.  Determine  which  Direct  Vent  arrangement  will  be  used  for 
    the installation. There are seven (7) Direct Vent arrangement 
    options, see pages 34 and 35.
    3.  Determine  vent  and  intake  air  pipe  size  to  be  used  for  the 
    installation; see Venting Requirements on page 22.
    4.  Plan  the  layout  of  the  vent  and  intake  air  piping  backwards 
    from  the  termination  point  outdoors  to  the  water  heater. 
    Layout  the  vent  and  intake  air  piping  to  use  a  minimum  of 
    pipe and elbows.
    5.  Install the terminations first. 
    If  standard  terminations  are  being  used  and  the  intake  air 
    or  vent  piping  will  terminate  vertically,  through  a  roof,  see 
    Vertical Termination Installation on page 24. 
    If standard terminations are being used and the intake air or 
    vent piping will terminate horizontally, through a sidewall, see 
    Sidewall Termination Installation on page 26. 
    If  a  concentric  termination(s)  will  be  used  see  Concentric 
    Termination Installation on page 29. If a low-profile termination 
    will be used see Low Profile Termination Table 12 on page 33.
    6.  When  installation  of  the  termination(s)  is  complete  Install 
    necessary piping and fittings to route the intake air and vent 
    piping back to the water heater.
    7.  The  intake  air  and  vent  piping  must  be  supported  properly 
    to  avoid  bending  or  failure.  The  water  heater  manufacturer 
    recommends that the vent and intake air piping be supported 
    every 5 feet (152 cm) of vertical run and every 3 feet (91 cm) 
    of horizontal run.
    8.  Do not install the vent or intake air piping in a manner that will 
    allow water to be trapped in the piping.
    9.  A  field  supplied  condensate  Tee  fitting  and  drain  hose  must 
    be  installed  in  the  intake  air  piping  near  the  water  heater  in 
    colder climates with heavy snow accumulations and in areas 
    that regularly experience high humidity. The drain hose must 
    be routed to an adequate floor drain separate from any other 
    condensate drains. See Figure 16 on page 24.
    NOTE: Snow being pulled into the intake air piping and then 
    melting can lead to excessive amounts of water accumulation 
    and damage water heater components. Warm, humid outdoor 
    air  can  lead  to  excessive  condensation  inside  the  intake  air 
    piping and may also damage water heater components.
    10.  All vent (exhaust) pipes must be pitched a minimum of a 1/4 
    inch  per  foot  back  to  the  water  heater  (to  allow  drainage  of 
    condensate).
    11.  If  installing  4  inch  vent  pipe  connect  the  vent  pipe  to  the 
    exhaust elbow on the water heater.
    12.  If  installing  6  inch  vent  pipe  transition  to  4  inch  pipe  at  the 
    exhaust  elbow  on  the  water  heater  as  shown  in  Figure  15. 
    The  field  installed  4”  pipe  between  the  exhaust  elbow  and 
    the 6” x 4” reducer coupling should be 18 inches (45 cm) or 
    less in length.
    The  water  heaters  covered  by  this  manual  may  be  installed  in  a 
    Direct  Vent  configuration  using  a  6  inch  concentric  or  6  inch  low 
    profile termination.
    Contact your local distributor or call the parts department phone 
    number listed on the back cover of this manual to order.
    •  6” Concentric Termination Part # 9008841005
    •  6" Low Profile Termination Part # 9008935005
    VENTING INSTALLATION SEQUENCE
    1.  Read the General Venting Instructions on page 21 and Venting 
    Requirements on page 22 before proceeding. These instructions 
    and requirements must be followed on all installations.
    2.  Determine  whether  the  water  heater  will  be  installed  in  a 
    Power Vent or Direct Vent configuration and which vent system 
    arrangement  will  be  used  for  the  installation.  See  the  various 
    venting arrangements on pages 34 and 35.
    3.  Proceed  to  the  applicable  installation  instructions  that  follow;  
    Power Vent Installation or Direct Vent Installation.
    POWER VENT INSTALLATION
    1. Read  the  General  Venting  Instructions  on  page  21  and 
    Venting Requirements on page 22 before proceeding. These 
    instructions  and  requirements  must  be  followed  in  addition 
    to  the  instructions  below  that  are  specific  for  Power  Vent 
    configurations.
    2.  Determine  which  Power  Vent  arrangement  will  be  used  for 
    the installation; vertical or horizontal termination. See Figure 
    36 and Figure 37 on page 34.
    3.  Determine the vent pipe size for the installation, see Venting 
    Requirements on page 22.
    4.  Plan  the  layout  of  the  vent  piping  backwards  from  the 
    termination  point  outdoors  to  the  water  heater.  Layout  the 
    vent piping to use a minimum of pipe and elbows.
    5.  Install the termination first.
    If the vent piping will terminate vertically, through a roof, see 
    Vertical Termination Installation on page 24. 
    If  the  vent  piping  will  terminate  horizontally,  through  a 
    sidewall, see Sidewall Termination Installation on page 26.
    4” PIPE FIELD SUPPLIED
    ALUMINUMEXHAUST/
    CONDENSA TE
    ELBOW VENT
    CONNECTION
    FA CT OR Y
    INST ALLED 6” PIPE FIELD
    SUPPLIED
    6” x 4” REDUCER
    FIELD SUPPLIED
    VENT (EXHAUST) CONNECTION
    Figure 15
    6.  When  installation  of  the  termination  is  complete  install 
    necessary piping and fittings to route the vent piping back to 
    the water heater.
    7.  The  vent  pipe  must  be  supported  properly  to  avoid  bending 
    or  failure.  The  water  heater  manufacturer  recommends  that 
    the vent pipe be supported every 5 feet (152 cm) of vertical 
    run and every 3 feet (91 cm) of horizontal run.
    8.  Do not install the vent piping in a manner that will allow water 
    to be trapped in the piping.  
    						
    							24
    14. If installing 4 inch intake air pipe connect the intake air pipe to 
    the intake air connection on the water heater.
    15.  If installing 6” intake air pipe transition to 4” pipe at the intake 
    air  connection  on  the  water  heater  as  shown  in  Figure  18. 
    The field installed 4” pipe between the intake air connection 
    and the 6” x 4” reducer coupling should be 18 inches (45 cm) 
    or less in length.
    3” PIPE F ACTORY
    INST ALLED
    6” PIPE FIELD
    SUPPLIED 4” PIPE FIELD
    SUPPLIED
    6” x 4” REDUCER
    FIELD SUPPLIED 4” x 3” REDUCER
    FA
    CT OR Y INST ALLED
    INT AKE  AIR CONNECTION
    INT AKE  AIR CONNECTION
    INT
    AKE  AIR
    COMBUSTION
    BLOWER
    Figure 18
    VERTICAL TERMINATION INSTALLATION
    1.  Determine the location for the termination(s).
    2.  If  installing  only  the  vent  (exhaust)  piping  in  a  Power  Vent 
    configuration  vertically  through  the  roof;  ensure  that  all 
    exterior  vertical  clearance  requirements  shown  in  Figure 
    19  and  Figure  20  on  page  25  are  being  maintained.  These 
    clearances and those cited by local and national codes must 
    be maintained.
    NOTE: On flat roof installations the vent termination must be 
    a minimum of 24 inches (60 cm) above any parapet, vertical 
    wall or structure within 10 feet (3 m) horizontally. See Figure 
    20 on page 25.
    3.  If  installing  both  intake  air  and  vent  piping  in  a  Direct  Vent 
    configuration  vertically  through  the  roof;  ensure  that  all 
    exterior  vertical  clearance  requirements  shown  in  Figure 
    20  and  Figure  21  on  page  25  are  being  maintained.  These 
    clearances and those cited by local and national codes must 
    be maintained.
    NOTE:  On  flat  roof  installations  the  intake  air  and  the  vent 
    terminations must be a minimum of 24 inches (60 cm) above 
    any  parapet,  vertical  wall  or  structure  within  10  feet  (3  m) 
    horizontally. See Figure 20 on page 25.
    4.  If  installing  only  vent  piping  in  a  Power  Vent  configuration 
    vertically  through  the  roof  the  following  instructions  must  be 
    followed:
    The  vent  termination  must  be  oriented  facing  downward  as 
    shown in Figure 19 and Figure 20 on page 25.
    The bottom edge of the vent termination must be a minimum 
    of  12  inches  (30  cm),  18  inches  (45  cm)  in  Canada,  above 
    the  average  or  expected  snow  level  as  shown  in  Figure  19 
    on page 25. 
    5.  If  installing  both  intake  air  and  vent  piping  in  a  Direct  Vent 
    configuration  vertically  through  the  roof  the  following 
    instructions must be followed:
    The intake air and vent pipes must penetrate the same side 
    of the roof as shown in Figure 21 on page 25.
    The intake air and vent terminations must be oriented facing 
    downward  and  in  the  same  direction  as  shown  in  Figure  21 
    on page 25.
    The  intake  air  and  vent  terminations  must  have  a  minimum 
    INT AKE  AIR CONDENSA TE TEE INST ALLATION
    INSTALL TEE FITTING  AS CLOSE
    TO  WA TER HEAT ER INTAKE AIR
    CONNECTION  AS POSSIBLE
    FIELD SUPPLIED
    4” x 4 ” x 1/2”  TEE
    WITH HOSE BARB
    FITTING INST ALLEDFA
    CT OR Y
    INST ALLED
    INT AKE  AIR
    CONNECTION
    (4” x 3” REDUCER)
    INT AKE  AIR
    CONNECT  FIELD
    SUPPLIED FLEXIBLE
    DRAIN HOSE  TO BARB
    FITTING  AND FORM  A
    LOOP  WATER  TRAP  IN
    DRAIN HOSE
    RUN DRAIN HOSE
    TO  SUIT ABLE FLOOR
    DRAIN SEP ARATELY
    FROM OTHER
    CONDENSA TE DRAINS
    Figure 16
    13.  Ensure the Intake Air Screen on the Intake Air Connection is 
    removed  before  connecting  the  intake  air  pipe  to  the  water 
    heater, see Figure 17. 
    Do not obstruct water heater air intake.
    Gas and carbon monoxide detectors
    are available.
    Install water heater in accordance with
    the instruction manual.
    Breathing carbon monoxide can cause brain damage or
    death.  Always read and understand instruction manual.
    Breathing Hazard - Carbon Monoxide Ga s
    NOTE:  Do  not  leave  the  screen  inside  the  Intake  Air 
    connection  in  Direct  Vent  installations.  Once  the  intake  air 
    pipe  is  installed  the  screen  will  be  hidden  from  view  and 
    may  become  clogged  with  debris  over  time.  This  will  cause 
    improper combustion.
    INTAKE  AIR CONNECTION DET AIL
    4” x 3” REDUCER
    COUPLING - F ACTORY INST ALLED
    INTAKE  AIR SCREEN(remove for Direct V ent)
    Figure 17  
    						
    							25
    INTAKE  AIR AND/OR VENT
    TERMINA TION(S) MUST  BE A 
    MINIMUM OF 24 INCES (60 cm) 
    ABOVE  ANY PARAPET, VERTICAL
    WA LL OR STRUCTURE WITHIN
    10 FEET  (3 m) HORIZONT ALLY.
    VERTICAL  TERMINATION(S) FLA T ROOF CLEARANCEINTAKE  AIR AND/OR VENT  (EXHAUST)
    24 INCHES (60 cm)
    MINIMUM HEIGHT  ABOVE
    IF LESS 
    THAN
    10 FEET  (3 m)
    Figure 20
    11.  Return to Power Vent Installation on page 23 or Direct Vent 
    Installation  on  page  23  to  complete  the  installation  of  the 
    intake air and/or vent piping between the termination(s) and 
    the water heater.
    VERTICAL  TERMINATION - DIRECT VEN TSTANDARD  TERMINATIONS
    24 INCHES (61 cm) MINIMUM
    48 INCHES (122 cm) IN COLDER CLIMA TES
    FA CT OR Y SUPPLIED
    ST ANDARD  TERMINATIONS
    POINTED DOWNW ARD
    FIELD
    SUPPLIED
    90° ELBOW
    VENT  (EXHAUST)
    TERMINA TION INT
    AKE  AIR
    TERMINA TION
    FIELD SUPPLIED
    PLUMBING
    ROOF BOOTS
    OR FLASHINGS
    MAINTA IN 12” (30 cm)
    18” (45 cm) FOR CANADA
    MINIMUM CLEARANCE
    ABOVE HIGHEST  
    ANTICIPA TED SNOW LEVEL.
    Figure 21
    separation of 24” (61 cm) measured on center line as shown 
    in  Figure  21  on  page  25.  In  colder  climates  this  separation 
    should be increased to at least 48 inches (122 cm).
    The  bottom  edge  of  the  intake  air  and  vent  terminations 
    must be a minimum of 12 inches (30 cm), 18 inches (45 cm) 
    in  Canada,  above  the  average  or  expected  snow  level  as 
    shown in Figure 19 and Figure 21 on page 25.
    6.  When  the  intake  air  and/or  vent  piping  from  multiple 
    water  heaters  will  terminate  in  the  same  location  the  vent 
    terminations  can  be  grouped  together  in  close  proximity  0 
    inches/touching. Intake air terminations can also be grouped 
    together in close proximity 0 inches/touching. 
    The  distance  between  the  closest  vent  and  intake  air 
    terminations  must  be  a  minimum  of  24  inches  (61  cm)  as 
    shown in Figure 21. In colder climates this separation should 
    be increased to at least 48 inches (122 cm).
    7.  Cut a 5 inch (13 cm) diameter hole for 4 inch pipe or 7 inch 
    (18  cm)  diameter  hole  for  6  inch  pipe  where  the  pipe(s)  will 
    pass through the roof.
    NOTE: Beware of concealed wiring and piping when cutting 
    through the roof.
    8.  Suspend  the  pipe(s)  through  center  of  hole  using  field 
    supplied  metal  strapping  or  equivalent  support  materials  as 
    shown in Figure 19.
    9.  Slide  a  roof  boot  or  equivalent  flashing  over  the  pipe  and 
    secure roof boot or equivalent flashing to roof (see Figure 19) 
    and seal around the flashing.
    10.  Install the factory supplied intake air and/or vent termination(s) 
    using field supplied pipe and one field supplied 90° elbow as 
    shown  in  Figure  19. The  short  section  of  pipe  that  connects 
    between the field supplied 90° elbow and the factory supplied 
    termination  must  not  be  excessive  in  length.  The  exposed 
    portion  of  this  pipe  shall  be  no  more  than  2  inches  (5  cm), 
    see Figure 19.
    2” (5 cm)
    MAXIMUM FACT OR Y SUPPLIED
    ST ANDARD  TERMINATION
    POINTED DOWN  TOWA RDS
    THE GROUND
    VERTICAL  TERMINATION(S) INST ALLATIONINTAKE  AIR AND/OR VENT  (EXHAUST)
    FIELD
    SUPPLIED
    90° ELBOW
    FIELD
    SUPPLIED
    STRAP/SUPPOR T
    FIELD SUPPLIED
    PLUMBING
    ROOF BOOT
    OR FLASHING
    MAINTAIN 12” (30 cm)
    18” (45 cm) FOR CANADA
    MINIMUM CLEARANCE
    ABOVE HIGHEST  ANTICIPAT ED
    SNOW LEVEL.
    Figure 19  
    						
    							26
    SIDEWALL TERMINATION INSTALLATION
    1. Determine the location for the termination(s).
    2.  If  installing  only  vent  (exhaust)  piping  in  a  Power  Vent 
    configuration  through  a  sidewall;  ensure  that  all  exterior 
    sidewall  clearance  requirements  for  the  termination,  shown 
    in  Figure  45a  on  page  36,  are  being  maintained.  These 
    clearances and those cited by local and national codes must 
    be maintained.
    3.  If  installing  both  intake  air  and  vent  piping  in  a  Direct  Vent 
    configuration  through  a  sidewall;  ensure  that  all  exterior 
    sidewall  clearance  requirements  for  the  terminations, 
    shown in Figure 45b on page 37, for the vent and intake air 
    termination  are  being  maintained.  These  clearances  and 
    those cited by local and national codes must be maintained. 
    4.  If installing both an intake air and vent termination in a Direct 
    Vent configuration through a sidewall there must be a minimum 
    of 24 inches (61 cm) separation, measured on vertical center 
    line, between the intake air and vent terminations, see Figure 
    22.
    NOTE:  In  colder  climates  this  separation  should  be 
    increased  to  at  least  48  inches  (122  cm)  between  the 
    intake air and vent termination or any other appliance vent 
    that discharges moisture-laden air such as clothes dryers. 
    This  will  reduce  possibility  of  frost  over  from  side  winds 
    blowing exhaust vapors to the intake air termination and is 
    recommended for Canadian installations.
    5.  If  installing  both  intake  air  and  vent  terminations  in  a  Direct 
    Vent  configuration  through  a  sidewall  the  intake  air  and 
    vent  terminations  must  be  installed  at  the  same  elevation 
    measured on horizontal center line - see Figure 22.
    VENT (EXHAUST)
    TERMINA TION INT
    AKE  AIR
    TERMINA TION
    INST ALL ON
    ELEVATION
    CENTERLINE
    24 INCHES (61 cm) MINIMUM
    48 INCHES (122 cm) IN COLDER CLIMA TES
    KEEP INTAKE AND VENT
    TERMINAT ION SCREENS
    CLEAR OF DEBRIS
    SIDEWA LL TERMINA TION - DIRECT  VENT
    STANDARD  TERMINATIONS
    Figure 22
    6.  When  the  intake  air  and/or  vent  piping  from  multiple  water 
    heaters will terminate at the same location through a sidewall, 
    the  vent  terminations  can  be  grouped  together  in  close 
    proximity  -  0  inches/touching.  The  intake  air  terminations 
    can  also  be  grouped  together  in  close  proximity  -  0  inches/
    touching. 
    However,  the  distance  between  the  closest  vent  and  intake 
    air  terminations  must  be  a  minimum  of  24  inches  (61  cm). 
    In  colder  climates  this  separation  should  be  increased  to  at 
    least 48 inches (122 cm). See Figure 22. 7. 
    Cut a 5 inch (13 cm) diameter hole for 4 inch pipe or 7 inch 
    (18  cm)  diameter  hole  for  6  inch  pipe  where  the  pipe(s)  will 
    pass through the wall.
    NOTE: Beware of concealed wiring and piping when cutting 
    through the wall.
    8.  Cut  a  length(s)  of  pipe  being  installed  3.5  inches  (8.9  cm) 
    to 9.5 inches (24.1 cm) longer than the wall thickness at the 
    opening. See Figure 23.
    NOTE:  Vent  Termination  –  exhaust  gases  of  this  water 
    heater  are  less  than  140°F.  In  cold  climates  water  vapor  in 
    the exhaust gases will condense into a cloud of vapor where 
    the vent exits the building. This vapor can gradually discolor 
    exterior  building  surfaces.  The  vent  termination  should  be 
    located  where  this  vapor  cloud  and  potential  discoloration 
    are not a  concern. Extending the exposed vent piping up to 
    a maximum of  6 inches (15.2 cm)  from the wall helps vapor 
    from  being  trapped  along  a  building’s  face.  To  avoid  this 
    problem,  the  vent  can  also  be  terminated  vertically  through 
    the roof, see Vertical Termination Installation on page 24.
    9.  Cement the intake air and/or vent termination to the section(s) 
    of pipe cut to length in the above Step.
    10.  Slide the included metal wall plate(s) over the pipe(s) to stop 
    against  the  intake  air  and/or  vent  termination.  Place  some 
    silicone  caulking  (field  supplied)  on  the  back  of  the  wall 
    plate(s) to secure it to the wall.
    11.  Working  from  outside,  slide  the  pipe  and  termination(s) 
    assembled  in  the  above  steps  through  the  wall.  Ensure  the 
    termination(s)  is  pointed  down  towards  the  ground.  See 
    Figure 23.
    INTERIOR WA LL EXTERIOR WALL
    FROM
    WA
    TER
    HEAT ER
    COUPLING
    SIDEWA LL TERMINA TION INST ALLATION
     INTAKE  AIR AND/OR VENT (EXHAUST)
    MET AL PLAT ES
    INST ALL INSIDE
    AND/OR OUTSIDE
    FACT OR Y SUPPLIED
    ST ANDARD  TERMINATION
    POINTED DOWN 
    TO WA RDS  THE GROUND
    INCREASE EXPOSED VENT
    PIPING UP
     TO A MAXIMUM
    OF 6 INCHES (15.2 cm) FROM  
    WA LL TO  HELP  PREVENT V APOR
    FROM DISCOLORING  THE WALL
    SURF ACE IN COLDER CLIMA TES
    Figure 23
    12.  Place a bead of silicone caulking (field supplied) around the 
    gap between the installed pipe(s) and the wall. Apply enough 
    to fill the gap between the pipe(s) and wall.
    13.  Press the wall plate flush against the outside wall.
    14.  Working  from  the  inside  apply  enough  silicone  caulking  on 
    the  back  of  the  interior  wall  plate(s)  to  hold  it  in  place  and 
    slide the wall plate over the installed pipe(s).
    15.  Install a coupling to the end of the pipe(s) inside the building. 
    Before  the  silicone  caulking  has  time  to  completely  set  go 
    outside  the  building  and  ensure  the  termination(s)  is  still 
    pointing down towards the ground. See Figure 23.
    16.  Return to Power Vent Installation on page 23 or Direct Vent 
    Installation  on  page  23  to  complete  the  installation  of  the 
    intake air and/or vent piping between the termination(s) and 
    the water heater.  
    						
    							27
    Installations  must  comply  with  applicable  national,  state,  and 
    local codes. For Canadian installation, Polypropylene vent must 
    be listed as a ULC-S636 approved system. If Polypropylene vent 
    is  not  required  by  your  local  code,  you  may  use  either  PVC  or 
    CPVC pipes for your water heater that allows non-metallic venting 
    material installations.
    Polypropylene vent systems do not use cement to connect the pipe 
    and elbow sections but use a push together gasket seal method. 
    Do not attempt to connect Polypropylene with sealant cement. All 
    vent  connections  MUST  be  secured  by  the  vent  manufacturer’s 
    joint  connector.  The  installer  must  use  a  specific  vent  starter 
    adapter  at  the  flue  connection.  The  adapter  is  supplied  by  the 
    vent manufacturer to adapt to its vent system.
    In order to be in full compliance with UL 1738 or ULC-S636 and 
    to meet the requirements of the water heater manufacturer, you 
    must  use  the  metal  joint  connector  rings,  available  from  the 
    Polypropylene  vent  manufacturer,  to  stiffen  the  joints  of  4”  and 
    6” diameter pipes.POLYPROPYLENE INSTALLATIONS
    The  water  heaters  covered  by  this  manual  have  been 
    approved  to  be  installed  with  Polypropylene  vent  material 
    as shown in Table 8 and Table 9. The approved application 
    of  single  wall,  non-flexible,  non-concentric  Polypropylene 
    vent  material  is  offered  by  two  specific  manufacturers 
    (Centrotherm ECO Systems and DuraVent Polypropylene). 
    These listed products must be installed by following the vent 
    manufacturer’s instructions. Refer to Table 7-PVC/CPVC and 
    Polypropylene on Page 22 to determine the maximum pipe 
    length and number of elbows that can be used.
    Insulation should not be used on Polypropylene venting materials. 
    The use of insulation will cause increased vent wall temperatures, 
    which could result in vent pipe failure.
    Use  only  the  adapters  and  vent  system  listed  in  Tables  below. 
    DO  NOT  mix  vent  systems  of  different  types  or  manufacturers. 
    Failure to comply could result in severe personal injury, death, or 
    substantial property damage.
    TABLE 8
    M & G Duravent PolyPro Vent system part numbers
    Nominal Pipe  Diameter Flue Outlet 
    Adapter Adapter 
    Connector Ring 
    Connector 90 Degree Elbow
    Vent Material Vent Terminal(s)
    4” 4PPS-AD PPS-PAC4PPS-LB4PPS-E90B PPS4PPS-E45B for Exhaust;
    4PPS-E45B for Intake (Direct Vent only)
    6” 6PPS-06PVCM-
    6PPF PPS-PACL
    6PPS-LBC 6PPS-E90 PPS6PPS-E45 for Exhaust;
    6PPS-E45 for Intake (Direct Vent only)
    TABLE 9
    Centrotherm InnoFlue SW Vent system part numbers
    Nominal Pipe  Diameter Flue Outlet 
    Adapter Adapter Connector Ring 
    Connector 90 Degree Elbow
    Vent Material Vent Terminal(s)
    4” ISAGL 0404 IAFC04IANS04ISEL0487 Polypropylene ISELL0445UV for Exhaust;
    ISELL0445UV for Intake (Direct Vent  only)
    6” ISAGL 0606 IAFC06IANS06ISEL0687 Polypropylene ISELL0645UV for Exhaust;
    ISELL0645UV for Intake (Direct Vent  only) 
    						
    							28
    AL29-4C® VENT INSTALLATIONS
    (AL29-4C® is a registered trademark of Allegheny Technologies, Inc.)
    The  water  heaters  covered  by  this  manual  are  approved  to  be  installed  with  AL29-4C®  stainless  steel  vent  material  using  parts 
    from the manufacturers listed in Table 10 and Table 11 below. These listed systems must be installed using the vent manufacturer’s 
    instructions  including  their  listed  clearances  to  combustible  and  noncombustible  materials.  Refer  to  Table  7-PVC/CPVC  and 
    Polypropylene on page 22 for the maximum and minimum equivalent linear vent lengths and number of elbows that may be used. 
    However, use Table 10 and Table 11 below to find the appropriate equivalent linear vent lengths for the AL29-4C® elbows.
    Note: The  equivalent  lengths  of  the AL29-4C®  elbows  are  different  than  those  from  smooth  walled  plastic  vents.  Consult Table  10 
    and Table 11 for the correct equivalent linear vent lengths.
    Listed vent systems composed of AL29-4C® must not mix parts from the different manufacturers. The joints of these products are 
    sealed by internal gaskets. Do not use any other type of sealant. When assembling these vent systems, follow the vent manufacturer’s 
    instructions for cleaning and lubricating the joints, if required. Each section must be locked together using the method supplied by 
    the vent manufacturer. 
    The water heaters covered by this manual are approved to be installed using the approved vent terminations shown in this manual. 
    This means that, the installer must use the adapter listed in Table 10 and Table 11 and a short piece of PVC pipe to complete the end 
    of the vent system with an approved termination. In Canada, the PVC pipe length must be listed to ULC636.
    TABLE 10
    HeatFab Saf–T Vent AL29-4C® Vent System Parts
    Diameter Flue Outlet 
    Adapter *Straight Pipe (3’ 
    Section) 45° ElbowEquivalent Linear 
    Length, 45° Elbow 90° Elbow
    Equivalent Linear 
    length, 90° Elbow Adapter to PVC
    4" 9401 PVC 9307 94115 feet 941410 feet9454CPVC
    6" 9601 PVC 960796115 feet 961410 feet9656CPVC
    *Consult vent manufacturer’s catalog for other available lengths.
    TABLE 11
    Duravent FasNSeal AL29-4C® Vent System Parts
    Diameter Flue Outlet 
    Adapter *Straight Pipe (3’ 
    Section) 45° ElbowEquivalent Linear 
    Length, 45° Elbow 90° elbowEquivalent Linear 
    Length, 90° Elbow Adapter to PVC
    4" 810005545 FSVL3604FSELB4504 5 feetFSELB9004 10 feet810009529
    6" 810005225 FSVL3606FSELB4506 5 feetFSELB9006 10 feet81005572 
    *Consult vent manufacturer’s catalog for other available lengths.  
    						
    							29
    termination  caps  for  all  concentric  terminations  must 
    be  at  the  same  height  measured  from  ground.  See 
    Multiple  Concentric  Termination  Arrangements  on 
    page 31.
    9.  Determine  if  the  concentric  termination  will  need  to  be 
    shortened  to  accommadate  required  clearances  or 
    to  ensure  all  vent  caps  are  at  the  same  height  when 
    installing multiple terminations vertically through the roof 
    in the same location.
    See Figure 25 for the minimum lengths allowed for the 6 inch 
    concentric termination.
    Note:  When shortening the length of the termination carefully 
    measure  and  cut  the  larger  (intake  air)  pipe  first.  Cut 
    the same amount of pipe off of the smaller (vent) pipe.
    Note:  Lengthening of the Concentric Vent Termination is not 
    permitted.
    CONCENTRIC  TERMINATION(S)
    MUST  BE A MINIMUM OF 10 FEET
    (3 m)  AWAY FROM  ANY PA RAPET,
    VER TICAL WA LL OR 
    STRUCTURE.
    6 INCH CONCENTRIC TERMINA TION
    FLA T ROOF CLEARANCE
    Figure 24
    CONCENTRIC TERMINATION INSTALLATION
    1. Concentric terminations must be ordered separately. (A)
    HCG3  119T300/400/500  models  must  use  the  6  inch 
    concentric  termination  for  both  4"  &  6"  vent  diameters; 
    Part Number: 9008841005. Contact your local distributor 
    or  call  the  parts  department  phone  number  on  the  back 
    cover of this manual to order concentric terminations.
    2.  Determine the location for the termination.
    NOTE:  Roof  termination  is  preferred  since  it  is  less 
    susceptible  to  damage,  has  reduced  chances  to  intake 
    contaminants and vent vapors are less visible.
    3.  When  installing  a  concentric  termination  vertically 
    through the roof; ensure that all exterior vertical clearance 
    requirements  for  the  concentric  termination,  shown  in 
    Figure  24  on  page  29  and  Figure  26  on  page  30,  are 
    being  maintained.  These  clearances  and  those  cited  by 
    local and national codes must be maintained.
    4.  When  installing  a  concentric  termination  vertically 
    through  a  flat  roof,  the  termination's  vent  cap  must  be  a 
    minimum of 10 feet (3 m) away from any parapet, vertical 
    wall or structure as shown in Figure 24. 
    NOTE: If this required distance to a parapet, vertical wall 
    or structure cannot be maintained, standard terminations 
    must  be  used.  See  Vertical  Termination  Installation  on 
    page 24.
    5.  When  installing  a  concentric  termination  through  a 
    sidewall;  ensure  that  all  exterior  sidewall  clearance 
    requirements  for  the  termination,  shown  in  Figure  45b 
    on  page  37,  are  being  maintained.  These  clearances 
    and  those  cited  by  local  and  national  codes  must  be 
    maintained.
    6.  When installing multiple concentric terminations vertically 
    through  a  roof  or  horizontally  through  a  sidewall  ensure 
    the  required  clearances  between  terminations  and 
    groupings  of  multiple  terminations  are  maintained.  See 
    pages 31 and 32 for more information.
    7.  Cut a 7 inch (18 cm) diameter hole for 6 inch concentric 
    terminations where they will pass through the wall or roof.
    NOTE:  Beware  of  concealed  wiring  and  piping  when 
    cutting through the wall or roof.
    8.  When  installing  multiple  concentric  terminations 
    vertically  through  the  roof  in  the  same  location  the   
    						
    							30
    6 INCH CONCENTRIC TERMINATION INSTALLATION
    6 INCH CONCENTRIC TERMINATION KITFIELD ASSEMBL Y REQUIRED
    VENT PIPE
    INT
    AKE  AIR CONNECTION
    VENT  CONNECTION - 4 INCH PVC
    INTAKE  AIR PIPE
    Y FITTING  ASSEMBLY
    VENT  CAP
    VENT  PIPE  ASSEMBL Y
    VENT
     PIPE IS 4 INCH SDR-26 PIPE
    SUPPLIED LENGTH 46.50” (1 18 cm)
    MINIMUM  ALLOWABLE LENGTH 16.38” (41.6 cm)
    INT AKE  AIR PIPE IS 6 INCH SDR-26 PIPE
    SUPPLIED LENGTH 25.38” (64.5 cm )
    MINIMUM  ALLOWABLE LENGTH 12” (30 cm )VENT
     CAP
    INT
    AKE  AIR PIPE
    6” x 6” x 6”
    Y FITTIN G
    6” x 4” BUSHING
    (FACTO RY
    INST ALLED)
    Figure 25
    Assemble and install the 6 inch concentric termination. Refer to 
    Figure 25, Figure 26 and Figure 27 for these instructions:
    1.  Cement the Y fitting to the larger diameter intake air pipe.
    2.  Slide the intake air pipe and Y fitting assembly from inside the 
    building  through  the  hole  cut  for  the  termination  in  the  roof 
    or  sidewall.  Ensure  no  foreign  materials  such  as  insulation 
    accumulate inside the assembly.
    3.  Secure  the  intake  air  Y  fitting  assembly  using  field  supplied 
    metal strapping or equivalent support materials.
    4.  On  installations  installed  through  the  roof  slide  a  field 
    supplied plumbing boot or roof flashing over the intake air Y 
    fitting assembly and secure it to the roof.
    5.  Seal around the plumbing boot or roof flashing.
    6.  Cement  the  vent  cap  onto  the  vent  pipe. Alternately  a  field-
    supplied  stainless  steel  screw  may  be  used  to  secure  the  2 
    components  together  when  field  disassembly  is  desired  for 
    cleaning. A pilot hole must be drilled for the screw to prevent 
    damage/cracking of the vent cap and/or vent pipe.
    7.  Install  the  vent  cap/vent  pipe  assembly  into  the  intake  air  Y 
    fitting assembly, Ensure small diameter vent pipe is cemented 
    and bottomed in the Y fitting.
    8.  Connect the intake air and vent piping from the water heater  to the 6 inch concentric termination using field supplied 6” x 
    4” reducer couplings as needed.
    9.  Return  to  Direct  Vent  Installation  on  page  23  to  complete 
    the installation of the intake air and vent piping between the 
    concentric termination and the water heater.
    NOTE: SECURING STRAP  
    MUST  BE FIELD INST ALLED 
    TO  PREVENT MOVEMENT 
    OF  TERMINA TION KIT
    MAINT
    AIN 12” (30 cm)
    18” (45 cm) FOR CANADA
    MINIMUM CLEARANCE
    ABOVE HIGHEST  ANTICIPAT ED
    SNOW LEVEL. MAXIMUM OF
    24” (60 cm)  ABOVE ROOF .
    ROOF FLASHING
    (field supplied) STRAP
    (field supplied)
    VENT PIPE INT
    AKE
    AIR PIPE
    COMBUSTION
    AIR VENT
    6 INCH CONCENTRIC 
    TERMINATION
    VER TICAL  INSTALLATION
    Figure 26
    NOTE: SECURING STRAP  MUST BE
    FIELD INST ALLED TO PREVENT
    MOVEMENT  OF TERMINA TION KIT
    IN SIDEW ALL.
    STRAP
    (field supplied)
    VENT
    PIPE
    INT AKE
    AIR PIPE COMBUSTION
    AIR
    VENT
    1 INCH
    MAXIMUM
    6 INCH CONCENTRIC  TERMINATION
    SIDEW ALL INST ALLATION
    Figure 27 
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual