Home > American Water Heater > Gas Heater > American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual

American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							31
    Four Concentric Terminations
    1. When installing four concentric terminations through a roof or 
    through  a  sidewall  in  close  proximity  they  may  be  arranged 
    into stacked rows of two as shown in Figure 30 or lateral rows 
    of two as shown in Figure 31.
    2.  Four is the maximum number of concentric terminations that 
    may  be  installed  in  a  group  where  all  terminations  are  in 
    close proximity as shown in Figure 30.
    A
    A
    A = 0 - 2 INCHES (0 - 5 cm)
    CLOSE PROXIMITY
    CONCENTRIC
    TERMINA TION
    CAPS END VIEW
    FOUR CONCENTRIC  TERMINATIONS(THROUGH  A ROOF OR SIDE WALL)
    Figure 30
    ABA
    FOUR CONCENTRIC  TERMINATIONS(THROUGH  A ROOF OR SIDE WALL)
    A = 0 - 2 INCHES (0 - 5 cm)
    CLOSE PROXIMITY B = 24 INCHES (61 cm)
    OR GREA TER
    CONCENTRIC
    TERMINA TION
    CAPS END VIEW
    Figure 31
    Groups Of Terminations
    1.  When  installing  multiple  groups  of  concentric  terminations 
    through  a  roof  or  through  a  sidewall  in  close  proximity  they 
    can  be  installed  into  stacked  groups  of  four  as  shown  in 
    Figure 32. Lateral groups of four as shown in Figure 31 may 
    be  a  more  convenient  installation  arrangement  for  multiple 
    groups depending on available space.
    A
    AB
    A = 0 - 2 INCHES (0 - 5 cm)
    CLOSE PROXIMITY
    CONCENTRIC
    TERMINA TION
    CAPS END VIEW
    EIGHT  CONCENTRIC  TERMINATIONS(THROUGH  A ROOF OR SIDE WALL)
    B = 24 INCHES (61 cm)
    OR GREA TER BETWEEN
    GROUPS OF FOUR
    Figure 32
    MULTIPLE CONCENTRIC TERMINATION CLEARANCES 
    When installing multiple concentric terminations vertically through 
    a  roof  or  horizontally  through  a  sidewall  ensure  the  required 
    clearances  (separation)  between  terminations  are  maintained. 
    Ensure  multiple  terminations  are  arranged  or  grouped  as 
    required.
    NOTE:  These  clearances  must  be  maintained  to  prevent  the 
    recirculation of vent (exhaust) gases to the intake air. Clearances 
    are  measured  between  the  edges  of  the  concentric  termination 
    caps.
    When  installing  multiple  concentric  terminations  through  a  roof 
    or  through  a  sidewall  the  clearances  shown  in  Figure  28  must 
    be maintained. 
    See Multiple Concentric Termination Arrangements on page 31.
    Close Proximity & Standard Clearance
    1. 
    The clearance between multiple termination caps must be 0 
    inches (touching) to a maximum of 2 inches (5 cm), dimension 
    A - Figure 28, when installing concentric terminations in close 
    proximity. See Figure 28 through 32.
    2.  The  clearance  between  multiple  termination  caps  must  be 
    increased to a minimum of 24 inches (61 cm), dimension B - 
    Figure 28, when installation in close proximity (above) is not 
    possible. This is the standard clearance.
    A
    OR
    B
    A = 0 - 2 INCHES (0 - 5 cm)
    CONCENTRIC
    TERMINA TION CAPS
    END VIEW
    TWO CONCENTRIC  TERMINATIONS(THROUGH  A ROOF OR SIDE WALL)
    B = 24 INCHES (61 cm)
    OR GREA TER
    CLOSE PROXIMITY
    STANDARD CLEARANCE
    Figure 28
    Three Concentric Terminations
    1.  When installing three concentric terminations through a roof 
    or  through  a  sidewall  the  third  termination  may  be  installed 
    in close proximity as indicated by dimension A in Figure 29. 
    2.  If  close  proximity  installation  of  the  third  termination  is  not 
    possible  the  third  termination  may  be  installed  as  indicated 
    by dimension B in Figure 29.
    A = 0 - 2 INCHES (0 - 5 cm)
    CLOSE PROXIMITY
    CONCENTRIC
    TERMINA TION
    CAPS END VIEW
    THIRD
    TERMINA TION
    THREE CONCENTRIC  TERMINATIONS(THROUGH  A ROOF OR SIDE WALL)
    A
    AB
    B = 24 INCHES (61 cm)
    OR GREA TER
    Figure 29  
    						
    							32
    SIDEWALL
    ROOF
    Figure 34
    Eight Concentric Terminations
    Eight  concentric  terminations  may  be  installed  in  two  stacked 
    groups  of  four,  in  close  proximity,  as  shown  in  Figure  35.  See 
    Figure 32 on page 31 for detailed information on clearances. 
    Lateral groups of four as shown in Figure 31 on page 31 may be 
    a  more  convenient  installation  arrangement  for  multiple  groups 
    depending on available space.
    SIDEW ALL
    ROOF
    Figure 35 
    MULTIPLE CONCENTRIC TERMINATION ARRANGEMENTS
    The  illustrations  on  this  page  show  some  of  the  installation 
    arrangements  for  multiple  concentric  terminations  that  are 
    allowed.
    See Multiple Concentric Termination Clearances on page 31 for 
    detailed  information  on  clearances  and  additional  arrangement 
    options.
    NOTE:  When  multiple  concentric  terminations  are  installed 
    through a roof in the same location all termination caps must be 
    at the same height measured from the ground. 
    Two Concentric Terminations
    Two  concentric  terminations  may  be  installed  in  close 
    proximity as shown in Figure 33 or with standard clearances 
    when  this  arrangement  is  not  possible.  See  Figure  28 
    on  page  31  for  detailed  information  on  clearances.  See 
    Figure  29  on  page  31  when  installing  three  concentric 
    terminations.
    SIDEW ALL
    ROOF
    Figure 33
    Four Concentric Terminations
    Four concentric terminations may be installed in close proximity 
    as  shown  in  Figure  34.  See  Figure  30  and  Figure  31  on  page 
    30  for  detailed  information  on  clearances  and  additional 
    arrangement options.  
    						
    							33
    LOW PROFILE VENT INSTALLATION
    This water heater is certified for sidewall direct venting with IPEX 
    System  636  Low  Profile  Vent  Kit.  Follow  instructions  below  for 
    proper installations.
    All  termination  kits  must  be  located  and  installed  in  accordance 
    with  local  building  code  and  CSA  B149.1  Natural  Gas  and 
    Propane Installation Code.
    1. Once the proper location has been determined, cut 2 holes in 
    the wall large enough to accommodate the pipe. Pipe diameters 
    and distance between hole centers can be found in Table 12.
    2.  Slide  both  the  intake  and  exhaust  pipes  through  the  holes. 
    Solvent cement both pipes to the base of the vent termination 
    kit,  follow  the  solvent  cementing  procedures  outlined  in  the 
    IPEX System 636 Installation Guide, which is available on the 
    web www.ipexinc.com.
    3.  To  fasten  the  Base  to  the  wall,  use  the  supplied  screws  and 
    anchors. A 3/16” (5mm) hole, 1-3/16” (30mm) deep, will need 
    to be drilled for the anchors. Locate the anchor hole using the 
    base as a template.
    4.  Screw the Cap to the Base using the supplied screws.
    5.  Once  the  vent  termination  and  pipes  are  secured,  the  wall 
    penetrations  will  need  to  be  sealed  from  the  interior  using  a 
    PVC-compatible sealant material.
    6.  All  vent  pipes  and  air  inlets  must  terminate  at  the  same 
    height to avoid possibility of severe personal injury, death, or 
    substantial property damage.
    7.  Operate  heater  through  1  heat  cycle  to  ensure  combustion-
    air and vent pipes are properly connected to concentric vent 
    termination
    Figure 36
    Figure 37
    Figure 38
    TABLE 12
    Low Profile Termination Kits - Dimensions
    AOS Kit Number IPEX Part 
    Number DescriptionPipe Outside 
    Diameter Hole Spacing
     
    (Center to Center)
    9008934005 1969864" Flush Mount Vent Kit 4.50"5.63"
    9008935005 1960806" Flush Mount Vent Kit 6.61"7.63"
    Each Kit Contains
    Qty Item Description
    1 Base (two holes)
    1 Cap (one hole)
    8 Stainless Steel Screws
    4 Plastic Anchors  
    						
    							34
    VENTING ARRANGEMENTS
    Power Vent VerticalFigure 36
    Direct Vent Vertical Figure 38 Power Vent Horizontal
    Figure 37
    Direct Vent Horizontal Figure 39  
    						
    							35
    VENTING ARRANGEMENTS
    Direct Vent Vertical Vent Horizontal Intake
    Figure 40
    Direct Vent Horizontal Vent Vertical Intake
    Figure 41
    Direct Vent Vertical Concentric
    Figure 42
    Direct Vent Horizontal Concentric
    Figure 43
    Direct Vent Horizontal Low Profile
    Figure 44  
    						
    							36
    TERMINATION CLEARANCES SIDEWALL POWER VENT
    VXVENT TERMINAL AIR SUPPLY INLETA REA WHERE TERMINAL IS NOT PERMITTED
    v
    v
    A G
    V
    F
    IXE DCLOSED
    FIXE DCLOSED
    OPERABLE OPERABLEV
    C
    B
    B
    B
    B
    F
    BV
    V
    AJ
    V
    H
    M
    X XV
    VK
    B
    E
    DL
    POWER VENT(using room air for combustion)
    EXTERIOR CLEARANCES FOR SIDEW ALL VENT TERMINA TION
    Figure 45a
    Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion.
    CANADIAN INSTALLATIONS 1US INSTALLATIONS 2CANADIAN INSTALLATIONS 1US INSTALLATIONS 2
    AClearance above grade, 
    veranda, porch, deck or 
    balcony 12 inches (30 cm)
    12 inches (30 cm)H
    Clearance to each side 
    of center line extended 
    above meter/regulator  
    assembly3 feet (91 cm) within a height 15 feet 
    (4.5 m) above the meter/ 
    regulator assembly 3 feet (91 cm) within a 
    height 15 feet (4.5 m) 
    above the meter/regulator 
    assembly*
    BClearance to window 
    or door that may be 
    opened6 inches (15 cm) for appliances up to 
    10,000 Btu/hr (3 kW), 12 inches (30 
    cm) for appliances between 10,000 
    Btu/hr (3 kW) and 100,000 Btu/hr (30 
    kW), 36 inches (91 cm) for appliances 
    above 100,000 Btu/hr (30 kW) 4 feet (1.2 m) below 
    or to side of opening; 
    1 foot (30 cm) above 
    openingIClearance to service 
    regulator vent outlet
     
               3 feet (91 cm)
    3 feet (91 cm)*
    CClearance to 
    permanently closed 
    window12 inches (30 cm)*
    12 inches (30 cm)*J
    Clearance to a non 
    mechanical air supply 
    inlet into building or 
    combustion air inlet to 
    any other appliance6 inches (15 cm) for appliances up 
    to 10,000 Btu/hr (3 kW), 12 inches 
    (30 cm) for appliances between 
    10,000 Btu/hr (3 kW) and 100,000 
    Btu/hr (30kW), 36 inches (91cm) 
    for appliances above 100,000 Btu/
    hr (30 kW)
    4 feet (1.2 m) below or to 
    side of opening; 1 foot 
     
    (30 cm) above opening.
    D
    Vertical clearance to 
    ventilated soffit located 
    above the terminal 
    within a horizontal 
    distance of 2 feet (61 
    cm) from the center line 
    of the terminal 12 inches (30 cm)*
    12 inches (30 cm)*
    KClearance to a 
    mechanical air supply 
    inlet6 feet (1.83 m) 3 feet (91 cm) above if 
    within 
    10 feet (3 m) horizontally
    EClearance to 
    unventilated soffit
    12 inches (30 cm)*
    12 inches (30 cm)*L
    Clearance above paved 
    sidewalk or paved 
    driveway located on 
    public property7 feet (2.13 m)†
    7 feet  (2.13 m)
    FClearance to outside 
    corner2 feet (60 cm)*
    2 feet (60 cm)*MClearance under 
    veranda, porch, deck, or 
    balcony12 inches (30 cm) ‡
    12 inches (30 cm) ‡
    GClearance to inside 
    corner18 inches (45 cm)*
    18 inches (45 cm)*
    1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
    2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
    † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.  
    Where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
    ‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor .
    * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer ’s installation instructions.  
    						
    							37
    TERMINATION CLEARANCES SIDEWALL DIRECT VENT
    VXVENT TERMINAL AIR SUPPLY INLETA REA WHERE TERMINAL IS NOT PERMITTED
    v
    v
    A G
    V
    F
    IXE DCLOSED
    FIXE DCLOSED
    OPERABLE OPERABLEV
    C
    B
    B
    B
    B
    F
    BV
    V
    AJ
    V
    H
    M
    X XV
    VK
    B
    E
    DL
    DIRECT VENT(using outdoor air for combustion)
    EXTERIOR CLEARANCES FOR SIDEW ALL VENT TERMINA TION
    Figure 45b
    Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion.
    CANADIAN INSTALLATIONS 1US INSTALLATIONS 2CANADIAN INSTALLATIONS 1US INSTALLATIONS 2
    AClearance above grade, 
    veranda, porch, deck or 
    balcony 12 inches (30 cm)
    12 inches (30 cm)H
    Clearance to each side 
    of center line extended 
    above meter/regulator 
    assembly3 feet (91 cm) within a height 15 
    feet (4.5 m) above the meter/ 
    regulator assembly
    3 feet (91 cm) within a height 
    15 feet (4.5 m) above the 
    meter/regulator assembly*
    BClearance to window or 
    door that may be opened6 inches (15 cm) for appliances 
    up to 10,000 Btu/hr (3 kW), 12 
    inches (30 cm) for appliances 
    between 10,000 Btu/hr (3 kW) 
    and 100,000 Btu/hr (30 kW), 36 
    inches (91 cm) for appliances 
    above 100,000 Btu/hr (30 kW) 6 inches (15 cm) 
    for appliances up to 
    10,000 Btu/hr (3 kW), 
    9 inches (23 cm) for 
    appliances between 
    10,000 Btu/hr (3 kW) 
    and 50,000 Btu/hr (15 
    kW), 12 inches (30 cm) 
    for appliances above 
    50,000 Btu/hr (15 kW)IClearance to service 
    regulator vent outlet
    3 feet (91 cm)
    3 feet (91 cm)*
    CClearance to 
    permanently closed 
    window6 inches (15 cm)*
    6 inches (15 cm)*J
    Clearance to a non 
    mechanical air supply 
    inlet into building or 
    combustion air inlet to 
    any other appliance6 inches (15 cm) for appliances up 
    to 10,000 Btu/hr (3 kW), 12 inches  
    (30 cm) for appliances between 
    10,000 Btu/hr (3 kW) and 100,000 
    Btu/hr (30 kW), 36 inches (91 cm)  
    for appliances above 100,000 Btu/
    hr (30 kW) 6 inches (15 cm) for 
    appliances up to 10,000 
    Btu/hr (3 kW), 9 inches (23 
    cm) for appliances between 
    10,000 Btu/hr (3 kW) and 
    50,000 Btu/hr (15 kW), 12 
    inches (30 cm) for appliances 
    above 50,000 Btu/hr (15 kW)
    D
    Vertical clearance to 
    ventilated soffit located 
    above the terminal within 
    a horizontal distance of 
    2 feet (61 cm) from the 
    center line of the terminal
    12 inches (30 cm)*
    12 inches (30 cm)*
    KClearance to a 
    mechanical air supply 
    inlet6 feet (1.83 m)
    3 feet (91 cm) above if within 
    10 feet (3 m) horizontally
    EClearance to unventilated 
    soffit12 inches (30 cm)*
    12 inches (30 cm)*L
    Clearance above 
    paved sidewalk or 
    paved driveway located 
    on public property7 feet (2.13 m)†
    7 feet (2.13 m)†*
    FClearance to outside 
    corner2 feet (60 cm)*
    2 feet (60 cm)*MClearance under 
    veranda, porch, deck, 
    or balcony12 inches (30 cm) ‡
    12 inches (30 cm) ‡*
    GClearance to inside 
    corner18 inches (45 cm)*
    18 inches (45 cm)*
    1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
    2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
    † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.  
    Where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
    ‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor .
    * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer ’s installation instructions.  
    						
    							38
    3. Do not install an additional trap in the condensate drain piping.  
    DO NOT remove, modify or alter the factory condensate trap.
    INSTALLATION INSTRUCTIONS
    1.  Ensure  the  water  heater’s  Enable/Disable  switch  is  in  the 
    “Disable” position.
    2.  Install  a  1/2  inch  PVC  condensate  drain  line  between  the 
    condensate  drain  connection  on  the  Exhaust/Condensate 
    Elbow and a suitable building drain. The exhaust elbow has 
    a "built in" condensate trap. Do not install  an additional  trap 
    in the condensate drain piping, Figure 46.
    3.  Terminate the condensate drain piping with an elbow above 
    the drain. Ensure that any discharge will exit the condensate 
    drain line no more than 6 inches (15.2 cm) above a suitable 
    building drain, or external to the building, see Figure 46.
    NOTE:  In  cold  climates  it  is  recommended  the  condensate 
    drain be terminated at a suitable drain inside the building.
    4.  Ensure  the  condensate  drain  line  is  not  elevated  above  the 
    condensate  drain  connection  on  the  exhaust/condensate 
    elbow, see Figure 46.
    5.  Brace the condensate drain line with floor mounted standoffs 
    every three feet.
    6.  Ensure  the  condensate  drains  freely  during  start  up,  see 
    Start Up on page 52.
    7.  Condensate clean out cap must be on and tight when unit is 
    in operation.
    WATER HEATER INSTALLATION
    CONDENSATE DRAIN INSTALLATION
    Installation  must  conform  with  these  instructions  and  local 
    building codes.
    Condensate neutralizer kits are available. Contact your distributor 
    or Service Agency.
    Field supplied materials required for installation include:
    • Approved PVC cement and PVC primer.
    •  1/2  inch  PVC  pipe  -  minimum  length  to  equal  the  distance  
    between the water heater and a suitable building drain.
    •  1/2  inch  PVC  fittings  (elbows,  couplings  and  adapters) 
    necessary  to  install  a  condensate  drain  line  between  the 
    exhaust/condensate elbow assembly and a suitable building 
    drain.
    •  Floor mounted standoffs to brace the drain line.
    INSTALLATION NOTES
    1.  The  condensate  drains  from  the  water  heater’s  covered  by 
    this  instruction  have  PH  levels  between  4.3  and  5.0.  Install 
    a  commercially  available  neutralizing  kit  if  required  by  local 
    codes.  Lower  PH  levels  are  acidic.  Do  not  connect  a  metal 
    condensate  drain  line,  such  as  copper  pipe,  to  the  water 
    heater for this reason.
    2.  The  field  installed  condensate  drain  line  must  not  be  less 
    than  1/2  inch  PVC  in  size.  The  condensate  line  must  slope 
    to an open drain.
    CONDENSA TE DRAIN
    LINE - FIELD INST ALLED
    DRAIN LINE  TO
    TERMINA TE NO
    MORE  THAN 6
    INCHES (15.2 cm)
    ABOVE DRAIN
    BUILDING
    DRAIN
    1/2” NPT
    CONDENSA
    TE
    DRAIN
    CONNECTION
    CONDENSATE
    CLEANOUT
    EXHAUST/CONDENSA
    TE
    (VENT) ELBOW
    PRESSURE POR T
    Figure 46  
    						
    							39
    SUPPLY GAS LINE INSTALLATION
    Contact  your  local  gas  utility  company  to  ensure  that  adequate 
    gas  service  is  available  and  to  review  applicable  installation 
    codes for your area.
    Be sure that the gas meter has sufficient capacity to supply the 
    rated  gas  input  of  the  water  heater  as  well  as  the  requirements 
    of  all  other  gas  fired  equipment  supplied  by  the  meter.  If  the 
    gas  meter  is  undersized,  the  gas  company  will  have  to  install  a 
    properly sized gas meter.
    Fire and Explosion Hazard
    Turn of f gas lines during installation.
    Contact a qualified installer or servic e
    agency for installation and service.
    Excessive gas pressure to gas valve ca n
    cause serious injury or death. Do not use water heater with any gas
    other than the gas shown on the rating
    label.  
    Make sure gas supplied is same type listed on the water heater’s 
    rating label.
    The  water  heaters  covered  in  this  manual  are  not  intended  for 
    operation  at  higher  than  14.0”  W.  C.  (2.49  kPa)  for  natural  and 
    propane gas supply pressure, see Table 4 on page 10. The water 
    heaters covered in this manual require supply gas regulators to 
    maintain  required  supply  gas  pressure.  Exposure  to  higher  gas 
    supply  pressure  may  cause  damage  to  the  gas  controls  which 
    could  result  in  fire  or  explosion.  If  overpressure  has  occurred 
    such  as  through  improper  testing  of  gas  lines  or  malfunction  of 
    the supply system the water heater’s gas valve must be checked 
    for safe operation by a Qualified Service Agency. 
    Ensure supply regulator vent lines and the safety vent valves are 
    protected  against  blockage.  These  are  components  of  the  gas 
    supply  system,  not  the  water  heater.  Vent  blockage  may  occur 
    during ice storms.
    It  is  important  to  guard  against  gas  valve  fouling  from 
    contaminants in the gas ways. Such fouling may cause improper 
    operation, fire or explosion. If copper supply lines are used they 
    must be internally tinned and certified for gas service.
    REGULA TED GAS
    SUPPL Y LINE
    MAIN GAS
    SHUT OFF VA LVE
    TEE FITTING
    PIPE CAP SEDIMENT  TRAP
    Figure 47
    Ensure all gas pipe is clean on the inside before installation. To 
    trap any dirt or foreign material in the gas supply line a sediment 
    trap must be installed as shown in Figure 47. The sediment trap 
    must be readily accessible and not subject to freezing conditions. 
    Install in accordance with the recommendations of the local gas 
    utility company. GAS LINE SIZING
    Minimum required supply gas line sizes are shown in Table 5 on 
    page  10.  Depending  on  the  developed  equivalent  length  and/or 
    the number of appliances connected to a common main, the size 
    of supply gas lines may have to be increased.
    Size  the  supply/main  gas  line(s)  in  accordance  with  Table  13 
    or  Table  14.  The  values    given  in  Table  13  and  Table  14  are  for 
    straight lengths of iron pipe at 0.5" W. C. (125 Pa) pressure drop, 
    which  is  considered  normal  for  low  pressure  systems.  Note  that 
    fittings such as elbows and tees will add to the pipe pressure drop.
    Schedule 40 Steel or Wrought Iron Pipe is the preferred material 
    for the gas line of this water heater. It is imperative to follow the 
    sizing recommendations in the latest version of the National Fuel 
    Gas  Code  if  Corrugated  Stainless  Steel Tubing  (CSST)  is  used 
    as the gas line for this water heater.
    SUPPLY GAS LINE SIZING U. S. UNITS
    TABLE 13
    LENGTH
    IN
    FEET NORMAL  IRON PIPE SIZES (INCHES)
    INPUT IN THOUSANDS BTU/HR
    1 1/4” 1 1/2” 2”2 1/2” 3”4”
    10 140021003960630011000 23000
    20 9501460 27504360770015800
    30 7701180 2200 3520625012800
    40 6609901900 3000530010900
    50 5809001680 265047509700
    60 5308101520 240043008800
    70 4907501400 225039008100
    80 4606901300 205037007500
    90 4306501220 195034507200
    100 4006201150 1850 32506700
    125 3605501020 165029506000
    150 3255009501500 26505500
    175 3004608501370 24505000
    200 N/A430 8001280 22804600
    SUPPLY GAS LINE SIZING METRIC UNITS
    TABLE 14
    LENGTH IN
    METERS NORMAL  IRON PIPE SIZES (INCHES)
    INPUT IN kW
    1 1/4” 1 1/2” 2”2 1/2” 3”4”
    3.0 4106151160 1845 32216735
    6.1 2784288051277 22554626
    9.1 2253466441031 18303748
    12.2 1932905568781552 3192
    15.2 1702644927761391 2840
    18.3 1552374457031259 2577
    21.3 1432204106591142 2372
    24.4 1352023816001083 2196
    27.4 1261903575711010 2108
    30.5 11 7182 3375429521962
    38.1 1051612994838641757
    45.7 95146 2784397761610
    53.3 88135 2494017171464
    61.0 N/A126 2343756881347  
    						
    							40
    GAS LINE CONNECTION
    1. The water heaters covered by this manual are shipped from 
    the  factory  with  a  1  1/2”  supply  gas  connection,  see Table  1 
    on page 10. Connect the supply gas line to the water heater's 
    24 VAC Gas Valve in accordance with all applicable local and 
    national code requirements, see Figure 48.
    2.  (A)HCG3  119T500  natural  gas  models  require  a  1  1/2” 
    minimum supply gas line. All other water heaters covered by 
    this  manual  require  a  1  1/4”  minimum  supply  gas  line.  See 
    Table 5 on page 10.
    3.  Apply  thread  sealing  compounds  (pipe  dope/  Teflon  tape) 
    sparingly and only to the male threads of the pipe joints. Do 
    not apply sealing compound to the first two threads. Use pipe 
    dope or Teflon tape marked as being resistant to the action of 
    liquid petroleum (LP/propane) gases.
    4.  Use  only  a  smooth  jaw  adjustable  wrench  (such  as  a 
    monkey  wrench)  as  a  back  up  on  the  body  of  the  24  VAC 
    Gas Valve when tightening the first pipe nipple into the body 
    of the valve.  DO NOT use a standard pipe wrench (Stillson 
    wrench)  with  metal  tooth  jaws  as  this  may  permanently 
    damage the valve.
    5.  Use  a  standard  pipe  wrench  (Stillson  wrench)  as  a  back 
    up  on  the  first  pipe  nipple  installed  above  when  connecting 
    other  fittings  and  pipe  in  the  supply  gas  line  to  prevent  the 
    24  VAC  Gas  Valve  on  the  water  heater  from  twisting  during 
    installation.
    6.  To  prevent  damage,  care  must  be  taken  not  to  apply  too 
    much  torque  when  connecting  the  supply  gas  line  to  the 
    water heater. 
    7.  Install a sediment trap as shown in Figure 47 on page 39.
    8.  Install  a  Main  Gas  Shutoff  valve  in  the  supply  gas  line  as 
    shown in Figure 47 on page 39.
    NOTE:  Should  overheating  occur  or  the  gas  supply  fail  to  shut 
    off, turn off the Main Gas Shutoff valve to the water heater.
    Gas Line
    Connection
    Figure 48
    GAS LINE LEAK TESTING
    Fire and Explosion Hazar d
    Leak test gas connections
    before placing the water heater
    in operation.
    Disconnect gas piping at main
    gas shutoff valve before lea k
    testing heate r.
    Install sediment trap in accordanc e
    with NFPA  54 or CAN/CSA  149.1.
    Use joint compound or  Teflon tape
    compatible with propane gas .
    Any time work is done on the gas supply system perform a leak 
    test to avoid the possibility of fire or explosion.
    1. For  test  pressures  exceeding  1/2  psi  (3.45  kPa)  disconnect 
    the water heater and its Main Gas Shutoff Valve from the gas 
    supply  piping  system  during  testing,  see  Figure  47  on  page 
    39. The gas supply line must be capped when disconnected 
    from the water heater.
    2.  For  test  pressures  of  1/2  psi  (3.45  kpa)  or  less,  the  water 
    heater  need  not  be  disconnected,  but  must  be  isolated  from 
    the  supply  gas  line  by  closing  the  Main  Gas  Shutoff  Valve 
    during testing.
    3.  Paint all supply gas line joints and connections upstream 
    of    the  water  heater  with  a  rich  soap  and  water  solution 
    to test for leaks. Bubbles indicate a gas leak. Do not use 
    matches,  candles,  flame  or  other  sources  of  ignition  for 
    this purpose. 
    4.  Repair any leaks before placing the water heater in operation.
    PURGING
    Gas line purging is required with new piping or systems in which 
    air  has  entered.  Purging  should  be  performed  per  the  current 
    edition of NFPA 54 the National Fuel Gas Code.
    ELECTRICAL WIRING
    All  electrical  work  must  be  installed  in  accordance  with  the 
    National  Electrical  Code,  ANSI/NFPA  70  or  the  Canadian 
    Electrical Code, CSA C22.1 and local requirements.
    When  installed,  the  water  heater  must  be  electrically  grounded 
    in accordance with local codes or, in the absence of local codes, 
    with the National Electrical Code, ANSI/NFPA 70 or the Canadian 
    Electrical Code, CSA C22.1.
    If any of the original wire as supplied with the water heater must 
    be  replaced,  it  must  be  replaced  with  105°C  rated  wiring  or  its 
    equivalent,  except  in  the  burner  housing.  In  this  case  200°C 
    rated wire must be used.
    DEDICATED POWER WIRING AND BREAKERS
    Dedicated  power  supply  wires,  ground  wiring  and  dedicated 
    circuit  breakers  often  prevent  electrical  line  noise  and  are 
    required when installing the water heater.
    POWER SUPPLY CONNECTIONS
    Read the requirements for the Power Supply on page 13 before 
    connecting power.
    The  120  VAC  hot  wire  from  the  power  supply  must  connect  to  the 
    black  jumper  wire  or  the  "L1"  terminal  block  location  in  the  junction 
    box and the 120 VAC neutral wire must connect to the white jumper 
    wire  or  the  "Neutral"  terminal  block  location  in  the  junction  box  for 
    correct polarity. See Figure 49.
    Power supply connections must be made as follows: 
    1. Turn  off  power  at  the  water  heater's  enable/disable  switch  and 
    the breaker that supplies power to the water heater.
    2.  Remove  the  junction  box  cover.  See  Figure  3  on  page  8  for 
    junction box location. 
    3.  Connect the 120VAC hot wire from the power supply to the black 
    jumper wire or the terminal block location marked "L1" inside of 
    the  junction  box  located  on  top  of  the  water  heater.  If  the  black 
    jumper wire is used, make the connection inside of the junction 
    box with a properly sized wire nut and wrap electrical tape around 
    the wire nut and wire end. See junction box Figure 41 and wiring 
    diagram Figure 58 on page 66.
    4.  Connect the 120VAC neutral wire from the power supply to the 
    white jumper wire or the terminal block location marked "Neutral" 
    inside  of  the  junction  box  located  on  top  of  the  water  heater.  If 
    the white jumper wire is used, make the connection inside of the 
    junction  box  with  a  properly  sized  wire  nut  and  wrap  electrical 
    tape around the wire nut and wire end. See junction box Figure 
    on page 41 and wiring diagram Figure 58 on page 66.  
    						
    All American Water Heater manuals Comments (0)

    Related Manuals for American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual