Home
>
American Water Heater
>
Gas Heater
>
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
Have a look at the manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

31 Four Concentric Terminations 1. When installing four concentric terminations through a roof or through a sidewall in close proximity they may be arranged into stacked rows of two as shown in Figure 30 or lateral rows of two as shown in Figure 31. 2. Four is the maximum number of concentric terminations that may be installed in a group where all terminations are in close proximity as shown in Figure 30. A A A = 0 - 2 INCHES (0 - 5 cm) CLOSE PROXIMITY CONCENTRIC TERMINA TION CAPS END VIEW FOUR CONCENTRIC TERMINATIONS(THROUGH A ROOF OR SIDE WALL) Figure 30 ABA FOUR CONCENTRIC TERMINATIONS(THROUGH A ROOF OR SIDE WALL) A = 0 - 2 INCHES (0 - 5 cm) CLOSE PROXIMITY B = 24 INCHES (61 cm) OR GREA TER CONCENTRIC TERMINA TION CAPS END VIEW Figure 31 Groups Of Terminations 1. When installing multiple groups of concentric terminations through a roof or through a sidewall in close proximity they can be installed into stacked groups of four as shown in Figure 32. Lateral groups of four as shown in Figure 31 may be a more convenient installation arrangement for multiple groups depending on available space. A AB A = 0 - 2 INCHES (0 - 5 cm) CLOSE PROXIMITY CONCENTRIC TERMINA TION CAPS END VIEW EIGHT CONCENTRIC TERMINATIONS(THROUGH A ROOF OR SIDE WALL) B = 24 INCHES (61 cm) OR GREA TER BETWEEN GROUPS OF FOUR Figure 32 MULTIPLE CONCENTRIC TERMINATION CLEARANCES When installing multiple concentric terminations vertically through a roof or horizontally through a sidewall ensure the required clearances (separation) between terminations are maintained. Ensure multiple terminations are arranged or grouped as required. NOTE: These clearances must be maintained to prevent the recirculation of vent (exhaust) gases to the intake air. Clearances are measured between the edges of the concentric termination caps. When installing multiple concentric terminations through a roof or through a sidewall the clearances shown in Figure 28 must be maintained. See Multiple Concentric Termination Arrangements on page 31. Close Proximity & Standard Clearance 1. The clearance between multiple termination caps must be 0 inches (touching) to a maximum of 2 inches (5 cm), dimension A - Figure 28, when installing concentric terminations in close proximity. See Figure 28 through 32. 2. The clearance between multiple termination caps must be increased to a minimum of 24 inches (61 cm), dimension B - Figure 28, when installation in close proximity (above) is not possible. This is the standard clearance. A OR B A = 0 - 2 INCHES (0 - 5 cm) CONCENTRIC TERMINA TION CAPS END VIEW TWO CONCENTRIC TERMINATIONS(THROUGH A ROOF OR SIDE WALL) B = 24 INCHES (61 cm) OR GREA TER CLOSE PROXIMITY STANDARD CLEARANCE Figure 28 Three Concentric Terminations 1. When installing three concentric terminations through a roof or through a sidewall the third termination may be installed in close proximity as indicated by dimension A in Figure 29. 2. If close proximity installation of the third termination is not possible the third termination may be installed as indicated by dimension B in Figure 29. A = 0 - 2 INCHES (0 - 5 cm) CLOSE PROXIMITY CONCENTRIC TERMINA TION CAPS END VIEW THIRD TERMINA TION THREE CONCENTRIC TERMINATIONS(THROUGH A ROOF OR SIDE WALL) A AB B = 24 INCHES (61 cm) OR GREA TER Figure 29

32 SIDEWALL ROOF Figure 34 Eight Concentric Terminations Eight concentric terminations may be installed in two stacked groups of four, in close proximity, as shown in Figure 35. See Figure 32 on page 31 for detailed information on clearances. Lateral groups of four as shown in Figure 31 on page 31 may be a more convenient installation arrangement for multiple groups depending on available space. SIDEW ALL ROOF Figure 35 MULTIPLE CONCENTRIC TERMINATION ARRANGEMENTS The illustrations on this page show some of the installation arrangements for multiple concentric terminations that are allowed. See Multiple Concentric Termination Clearances on page 31 for detailed information on clearances and additional arrangement options. NOTE: When multiple concentric terminations are installed through a roof in the same location all termination caps must be at the same height measured from the ground. Two Concentric Terminations Two concentric terminations may be installed in close proximity as shown in Figure 33 or with standard clearances when this arrangement is not possible. See Figure 28 on page 31 for detailed information on clearances. See Figure 29 on page 31 when installing three concentric terminations. SIDEW ALL ROOF Figure 33 Four Concentric Terminations Four concentric terminations may be installed in close proximity as shown in Figure 34. See Figure 30 and Figure 31 on page 30 for detailed information on clearances and additional arrangement options.

33 LOW PROFILE VENT INSTALLATION This water heater is certified for sidewall direct venting with IPEX System 636 Low Profile Vent Kit. Follow instructions below for proper installations. All termination kits must be located and installed in accordance with local building code and CSA B149.1 Natural Gas and Propane Installation Code. 1. Once the proper location has been determined, cut 2 holes in the wall large enough to accommodate the pipe. Pipe diameters and distance between hole centers can be found in Table 12. 2. Slide both the intake and exhaust pipes through the holes. Solvent cement both pipes to the base of the vent termination kit, follow the solvent cementing procedures outlined in the IPEX System 636 Installation Guide, which is available on the web www.ipexinc.com. 3. To fasten the Base to the wall, use the supplied screws and anchors. A 3/16” (5mm) hole, 1-3/16” (30mm) deep, will need to be drilled for the anchors. Locate the anchor hole using the base as a template. 4. Screw the Cap to the Base using the supplied screws. 5. Once the vent termination and pipes are secured, the wall penetrations will need to be sealed from the interior using a PVC-compatible sealant material. 6. All vent pipes and air inlets must terminate at the same height to avoid possibility of severe personal injury, death, or substantial property damage. 7. Operate heater through 1 heat cycle to ensure combustion- air and vent pipes are properly connected to concentric vent termination Figure 36 Figure 37 Figure 38 TABLE 12 Low Profile Termination Kits - Dimensions AOS Kit Number IPEX Part Number DescriptionPipe Outside Diameter Hole Spacing (Center to Center) 9008934005 1969864" Flush Mount Vent Kit 4.50"5.63" 9008935005 1960806" Flush Mount Vent Kit 6.61"7.63" Each Kit Contains Qty Item Description 1 Base (two holes) 1 Cap (one hole) 8 Stainless Steel Screws 4 Plastic Anchors

34 VENTING ARRANGEMENTS Power Vent VerticalFigure 36 Direct Vent Vertical Figure 38 Power Vent Horizontal Figure 37 Direct Vent Horizontal Figure 39

35 VENTING ARRANGEMENTS Direct Vent Vertical Vent Horizontal Intake Figure 40 Direct Vent Horizontal Vent Vertical Intake Figure 41 Direct Vent Vertical Concentric Figure 42 Direct Vent Horizontal Concentric Figure 43 Direct Vent Horizontal Low Profile Figure 44

36 TERMINATION CLEARANCES SIDEWALL POWER VENT VXVENT TERMINAL AIR SUPPLY INLETA REA WHERE TERMINAL IS NOT PERMITTED v v A G V F IXE DCLOSED FIXE DCLOSED OPERABLE OPERABLEV C B B B B F BV V AJ V H M X XV VK B E DL POWER VENT(using room air for combustion) EXTERIOR CLEARANCES FOR SIDEW ALL VENT TERMINA TION Figure 45a Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion. CANADIAN INSTALLATIONS 1US INSTALLATIONS 2CANADIAN INSTALLATIONS 1US INSTALLATIONS 2 AClearance above grade, veranda, porch, deck or balcony 12 inches (30 cm) 12 inches (30 cm)H Clearance to each side of center line extended above meter/regulator assembly3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/ regulator assembly 3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/regulator assembly* BClearance to window or door that may be opened6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30 kW), 36 inches (91 cm) for appliances above 100,000 Btu/hr (30 kW) 4 feet (1.2 m) below or to side of opening; 1 foot (30 cm) above openingIClearance to service regulator vent outlet 3 feet (91 cm) 3 feet (91 cm)* CClearance to permanently closed window12 inches (30 cm)* 12 inches (30 cm)*J Clearance to a non mechanical air supply inlet into building or combustion air inlet to any other appliance6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30kW), 36 inches (91cm) for appliances above 100,000 Btu/ hr (30 kW) 4 feet (1.2 m) below or to side of opening; 1 foot (30 cm) above opening. D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal 12 inches (30 cm)* 12 inches (30 cm)* KClearance to a mechanical air supply inlet6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3 m) horizontally EClearance to unventilated soffit 12 inches (30 cm)* 12 inches (30 cm)*L Clearance above paved sidewalk or paved driveway located on public property7 feet (2.13 m)† 7 feet (2.13 m) FClearance to outside corner2 feet (60 cm)* 2 feet (60 cm)*MClearance under veranda, porch, deck, or balcony12 inches (30 cm) ‡ 12 inches (30 cm) ‡ GClearance to inside corner18 inches (45 cm)* 18 inches (45 cm)* 1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code. 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code. † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Where it may cause hazardous frost or ice accumulations on adjacent property surfaces. ‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor . * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer ’s installation instructions.

37 TERMINATION CLEARANCES SIDEWALL DIRECT VENT VXVENT TERMINAL AIR SUPPLY INLETA REA WHERE TERMINAL IS NOT PERMITTED v v A G V F IXE DCLOSED FIXE DCLOSED OPERABLE OPERABLEV C B B B B F BV V AJ V H M X XV VK B E DL DIRECT VENT(using outdoor air for combustion) EXTERIOR CLEARANCES FOR SIDEW ALL VENT TERMINA TION Figure 45b Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion. CANADIAN INSTALLATIONS 1US INSTALLATIONS 2CANADIAN INSTALLATIONS 1US INSTALLATIONS 2 AClearance above grade, veranda, porch, deck or balcony 12 inches (30 cm) 12 inches (30 cm)H Clearance to each side of center line extended above meter/regulator assembly3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/ regulator assembly 3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/regulator assembly* BClearance to window or door that may be opened6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30 kW), 36 inches (91 cm) for appliances above 100,000 Btu/hr (30 kW) 6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 9 inches (23 cm) for appliances between 10,000 Btu/hr (3 kW) and 50,000 Btu/hr (15 kW), 12 inches (30 cm) for appliances above 50,000 Btu/hr (15 kW)IClearance to service regulator vent outlet 3 feet (91 cm) 3 feet (91 cm)* CClearance to permanently closed window6 inches (15 cm)* 6 inches (15 cm)*J Clearance to a non mechanical air supply inlet into building or combustion air inlet to any other appliance6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30 kW), 36 inches (91 cm) for appliances above 100,000 Btu/ hr (30 kW) 6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 9 inches (23 cm) for appliances between 10,000 Btu/hr (3 kW) and 50,000 Btu/hr (15 kW), 12 inches (30 cm) for appliances above 50,000 Btu/hr (15 kW) D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal 12 inches (30 cm)* 12 inches (30 cm)* KClearance to a mechanical air supply inlet6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3 m) horizontally EClearance to unventilated soffit12 inches (30 cm)* 12 inches (30 cm)*L Clearance above paved sidewalk or paved driveway located on public property7 feet (2.13 m)† 7 feet (2.13 m)†* FClearance to outside corner2 feet (60 cm)* 2 feet (60 cm)*MClearance under veranda, porch, deck, or balcony12 inches (30 cm) ‡ 12 inches (30 cm) ‡* GClearance to inside corner18 inches (45 cm)* 18 inches (45 cm)* 1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code. 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code. † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Where it may cause hazardous frost or ice accumulations on adjacent property surfaces. ‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor . * Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer ’s installation instructions.

38 3. Do not install an additional trap in the condensate drain piping. DO NOT remove, modify or alter the factory condensate trap. INSTALLATION INSTRUCTIONS 1. Ensure the water heater’s Enable/Disable switch is in the “Disable” position. 2. Install a 1/2 inch PVC condensate drain line between the condensate drain connection on the Exhaust/Condensate Elbow and a suitable building drain. The exhaust elbow has a "built in" condensate trap. Do not install an additional trap in the condensate drain piping, Figure 46. 3. Terminate the condensate drain piping with an elbow above the drain. Ensure that any discharge will exit the condensate drain line no more than 6 inches (15.2 cm) above a suitable building drain, or external to the building, see Figure 46. NOTE: In cold climates it is recommended the condensate drain be terminated at a suitable drain inside the building. 4. Ensure the condensate drain line is not elevated above the condensate drain connection on the exhaust/condensate elbow, see Figure 46. 5. Brace the condensate drain line with floor mounted standoffs every three feet. 6. Ensure the condensate drains freely during start up, see Start Up on page 52. 7. Condensate clean out cap must be on and tight when unit is in operation. WATER HEATER INSTALLATION CONDENSATE DRAIN INSTALLATION Installation must conform with these instructions and local building codes. Condensate neutralizer kits are available. Contact your distributor or Service Agency. Field supplied materials required for installation include: • Approved PVC cement and PVC primer. • 1/2 inch PVC pipe - minimum length to equal the distance between the water heater and a suitable building drain. • 1/2 inch PVC fittings (elbows, couplings and adapters) necessary to install a condensate drain line between the exhaust/condensate elbow assembly and a suitable building drain. • Floor mounted standoffs to brace the drain line. INSTALLATION NOTES 1. The condensate drains from the water heater’s covered by this instruction have PH levels between 4.3 and 5.0. Install a commercially available neutralizing kit if required by local codes. Lower PH levels are acidic. Do not connect a metal condensate drain line, such as copper pipe, to the water heater for this reason. 2. The field installed condensate drain line must not be less than 1/2 inch PVC in size. The condensate line must slope to an open drain. CONDENSA TE DRAIN LINE - FIELD INST ALLED DRAIN LINE TO TERMINA TE NO MORE THAN 6 INCHES (15.2 cm) ABOVE DRAIN BUILDING DRAIN 1/2” NPT CONDENSA TE DRAIN CONNECTION CONDENSATE CLEANOUT EXHAUST/CONDENSA TE (VENT) ELBOW PRESSURE POR T Figure 46

39 SUPPLY GAS LINE INSTALLATION Contact your local gas utility company to ensure that adequate gas service is available and to review applicable installation codes for your area. Be sure that the gas meter has sufficient capacity to supply the rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If the gas meter is undersized, the gas company will have to install a properly sized gas meter. Fire and Explosion Hazard Turn of f gas lines during installation. Contact a qualified installer or servic e agency for installation and service. Excessive gas pressure to gas valve ca n cause serious injury or death. Do not use water heater with any gas other than the gas shown on the rating label. Make sure gas supplied is same type listed on the water heater’s rating label. The water heaters covered in this manual are not intended for operation at higher than 14.0” W. C. (2.49 kPa) for natural and propane gas supply pressure, see Table 4 on page 10. The water heaters covered in this manual require supply gas regulators to maintain required supply gas pressure. Exposure to higher gas supply pressure may cause damage to the gas controls which could result in fire or explosion. If overpressure has occurred such as through improper testing of gas lines or malfunction of the supply system the water heater’s gas valve must be checked for safe operation by a Qualified Service Agency. Ensure supply regulator vent lines and the safety vent valves are protected against blockage. These are components of the gas supply system, not the water heater. Vent blockage may occur during ice storms. It is important to guard against gas valve fouling from contaminants in the gas ways. Such fouling may cause improper operation, fire or explosion. If copper supply lines are used they must be internally tinned and certified for gas service. REGULA TED GAS SUPPL Y LINE MAIN GAS SHUT OFF VA LVE TEE FITTING PIPE CAP SEDIMENT TRAP Figure 47 Ensure all gas pipe is clean on the inside before installation. To trap any dirt or foreign material in the gas supply line a sediment trap must be installed as shown in Figure 47. The sediment trap must be readily accessible and not subject to freezing conditions. Install in accordance with the recommendations of the local gas utility company. GAS LINE SIZING Minimum required supply gas line sizes are shown in Table 5 on page 10. Depending on the developed equivalent length and/or the number of appliances connected to a common main, the size of supply gas lines may have to be increased. Size the supply/main gas line(s) in accordance with Table 13 or Table 14. The values given in Table 13 and Table 14 are for straight lengths of iron pipe at 0.5" W. C. (125 Pa) pressure drop, which is considered normal for low pressure systems. Note that fittings such as elbows and tees will add to the pipe pressure drop. Schedule 40 Steel or Wrought Iron Pipe is the preferred material for the gas line of this water heater. It is imperative to follow the sizing recommendations in the latest version of the National Fuel Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as the gas line for this water heater. SUPPLY GAS LINE SIZING U. S. UNITS TABLE 13 LENGTH IN FEET NORMAL IRON PIPE SIZES (INCHES) INPUT IN THOUSANDS BTU/HR 1 1/4” 1 1/2” 2”2 1/2” 3”4” 10 140021003960630011000 23000 20 9501460 27504360770015800 30 7701180 2200 3520625012800 40 6609901900 3000530010900 50 5809001680 265047509700 60 5308101520 240043008800 70 4907501400 225039008100 80 4606901300 205037007500 90 4306501220 195034507200 100 4006201150 1850 32506700 125 3605501020 165029506000 150 3255009501500 26505500 175 3004608501370 24505000 200 N/A430 8001280 22804600 SUPPLY GAS LINE SIZING METRIC UNITS TABLE 14 LENGTH IN METERS NORMAL IRON PIPE SIZES (INCHES) INPUT IN kW 1 1/4” 1 1/2” 2”2 1/2” 3”4” 3.0 4106151160 1845 32216735 6.1 2784288051277 22554626 9.1 2253466441031 18303748 12.2 1932905568781552 3192 15.2 1702644927761391 2840 18.3 1552374457031259 2577 21.3 1432204106591142 2372 24.4 1352023816001083 2196 27.4 1261903575711010 2108 30.5 11 7182 3375429521962 38.1 1051612994838641757 45.7 95146 2784397761610 53.3 88135 2494017171464 61.0 N/A126 2343756881347

40 GAS LINE CONNECTION 1. The water heaters covered by this manual are shipped from the factory with a 1 1/2” supply gas connection, see Table 1 on page 10. Connect the supply gas line to the water heater's 24 VAC Gas Valve in accordance with all applicable local and national code requirements, see Figure 48. 2. (A)HCG3 119T500 natural gas models require a 1 1/2” minimum supply gas line. All other water heaters covered by this manual require a 1 1/4” minimum supply gas line. See Table 5 on page 10. 3. Apply thread sealing compounds (pipe dope/ Teflon tape) sparingly and only to the male threads of the pipe joints. Do not apply sealing compound to the first two threads. Use pipe dope or Teflon tape marked as being resistant to the action of liquid petroleum (LP/propane) gases. 4. Use only a smooth jaw adjustable wrench (such as a monkey wrench) as a back up on the body of the 24 VAC Gas Valve when tightening the first pipe nipple into the body of the valve. DO NOT use a standard pipe wrench (Stillson wrench) with metal tooth jaws as this may permanently damage the valve. 5. Use a standard pipe wrench (Stillson wrench) as a back up on the first pipe nipple installed above when connecting other fittings and pipe in the supply gas line to prevent the 24 VAC Gas Valve on the water heater from twisting during installation. 6. To prevent damage, care must be taken not to apply too much torque when connecting the supply gas line to the water heater. 7. Install a sediment trap as shown in Figure 47 on page 39. 8. Install a Main Gas Shutoff valve in the supply gas line as shown in Figure 47 on page 39. NOTE: Should overheating occur or the gas supply fail to shut off, turn off the Main Gas Shutoff valve to the water heater. Gas Line Connection Figure 48 GAS LINE LEAK TESTING Fire and Explosion Hazar d Leak test gas connections before placing the water heater in operation. Disconnect gas piping at main gas shutoff valve before lea k testing heate r. Install sediment trap in accordanc e with NFPA 54 or CAN/CSA 149.1. Use joint compound or Teflon tape compatible with propane gas . Any time work is done on the gas supply system perform a leak test to avoid the possibility of fire or explosion. 1. For test pressures exceeding 1/2 psi (3.45 kPa) disconnect the water heater and its Main Gas Shutoff Valve from the gas supply piping system during testing, see Figure 47 on page 39. The gas supply line must be capped when disconnected from the water heater. 2. For test pressures of 1/2 psi (3.45 kpa) or less, the water heater need not be disconnected, but must be isolated from the supply gas line by closing the Main Gas Shutoff Valve during testing. 3. Paint all supply gas line joints and connections upstream of the water heater with a rich soap and water solution to test for leaks. Bubbles indicate a gas leak. Do not use matches, candles, flame or other sources of ignition for this purpose. 4. Repair any leaks before placing the water heater in operation. PURGING Gas line purging is required with new piping or systems in which air has entered. Purging should be performed per the current edition of NFPA 54 the National Fuel Gas Code. ELECTRICAL WIRING All electrical work must be installed in accordance with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1 and local requirements. When installed, the water heater must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1. If any of the original wire as supplied with the water heater must be replaced, it must be replaced with 105°C rated wiring or its equivalent, except in the burner housing. In this case 200°C rated wire must be used. DEDICATED POWER WIRING AND BREAKERS Dedicated power supply wires, ground wiring and dedicated circuit breakers often prevent electrical line noise and are required when installing the water heater. POWER SUPPLY CONNECTIONS Read the requirements for the Power Supply on page 13 before connecting power. The 120 VAC hot wire from the power supply must connect to the black jumper wire or the "L1" terminal block location in the junction box and the 120 VAC neutral wire must connect to the white jumper wire or the "Neutral" terminal block location in the junction box for correct polarity. See Figure 49. Power supply connections must be made as follows: 1. Turn off power at the water heater's enable/disable switch and the breaker that supplies power to the water heater. 2. Remove the junction box cover. See Figure 3 on page 8 for junction box location. 3. Connect the 120VAC hot wire from the power supply to the black jumper wire or the terminal block location marked "L1" inside of the junction box located on top of the water heater. If the black jumper wire is used, make the connection inside of the junction box with a properly sized wire nut and wrap electrical tape around the wire nut and wire end. See junction box Figure 41 and wiring diagram Figure 58 on page 66. 4. Connect the 120VAC neutral wire from the power supply to the white jumper wire or the terminal block location marked "Neutral" inside of the junction box located on top of the water heater. If the white jumper wire is used, make the connection inside of the junction box with a properly sized wire nut and wrap electrical tape around the wire nut and wire end. See junction box Figure on page 41 and wiring diagram Figure 58 on page 66.