Page 11

3
A12175
3.2. Set Dealer Information
From the main screen, touchMENU, on the bottom of the control. TheSERVICE
icon allows you to upload your contact information into the Infinity Touch Control.
A12176SFormat your contact information and logo (if applicable) using the PC/MAC
application, save it to a standard USB drive. See Section 6.7.
STouch theSERVICEicon for about 10 seconds, then touchDEALER LOGO
UPLOAD.
SPlace the USB drive into the USB port on the bottom of the Infinity Touch
Control and follow...

Page 12

4
4. Installation
4.1. Overview
This instruction covers installation of the InfinityrTouch Control and the Infinityr
Wireless Access Point only. Physical installation instructions for the indoor and
outdoor equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the InfinityrSystem are
covered only in this installation instruction. It is the guide to connecting the system
components and commissioning the system once all physical components are...

Page 13

5
4.3. Location
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect power before routing control wiring.
!WARNING
All wiring must comply with national, local, and state codes.
4.3.1. Wall Control
The Infinity Touch Control is the command center for the Infinity System. It should
be located where it is easily accessible and visible to the adult homeowner or end
user. For accurate temperature measurement, the following guidelines should be...

Page 14

6
SClose to or in direct airflow from supply registers.
SIn areas with poor air circulation, such as behind a door or in an alcove.
4.3.2. Remote Room Sensors
A Remote Room Sensor can be used with the Infinity Touch Control to take the
place of the control’s internal temperature sensor. This allows the Infinity Touch
Control to be mounted in areas with less than optimal airflow (such as near an
exterior door, window or in a closet). The remote sensor can be wired to the
terminal block connectors labeled...

Page 15

7
Sensor 1 Sensor 2
Sensor 3 Sensor 4 Damper Control
Module
ZS_Damper Control
Module
ZS_C
A03233
4.3.3. Smart Sensors (for zoning applications)
Any zone may use a Smart Sensor. It provides a temperature display and buttons to
adjust the desired temperature in that zone only. It also displays outdoor
temperature and indoor humidity sensed at the control. Only one Smart Sensor may
be used per zone. They cannot be averaged like Remote Room Sensors. If a Smart
Sensor is used in a zone, a Remote Room Sensor...

Page 16

8
NOTE: ABCD bus wiring only requires a four--wire connection; however, it is
good practice to run thermostat cable having more than four wires in the event of a
damaged or broken wire during installation.
Each communicating device in the InfinityrZone System has a four--pin connector
labeled ABCD. It is recommended that the following color code be used when
wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
ABCD
A03193
It is not mandatory that the...

Page 17

9
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, the main
electrical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label.
!WARNING
STurn off all power to equipment.
SIf an existing InfinityrControl or other control is being replaced:
dRemove existing control from wall.
dDisconnect wires from existing control....

Page 18

10
SAdjust length and routing of each wire to reach each wire entry on the
connector backplate. Strip 1/4 --in (6.4 mm) of insulation from each wire.
SMatch and connect thermostat wires to proper terminals on control backplate.
dSee wiring diagrams in Appendix A.
SPush any excess wire into the wall. Seal hole in wall to prevent any air leaks.
Leaks can affect operation.
SAttach Infinity Control to the mounting plastic by lining up the plastic guides
on the back of the control with the opening on the...

Page 19

11
4.4.2. Damper Control Module (zoning systems only)
All wiring is run back to the Damper Control Module. Select a location near the
furnace or fan coil where wiring from the control, each Remote Room Sensor or
Smart Sensor, each damper actuator, and the equipment itself can come together
easily. The Damper Control Module is approved for indoor use only and should
never be installed with any of its components exposed to the elements. The Damper
Control Module (and zone dampers) may be installed in any...

Page 20

12
A12214
A12215
NOTE: Once Infinity Control is secured to wall with the backplate assembly
(snapped together), care must be taken not to bend or break the interlocking tabs
when removing.
4.5.1. Decorative Backplate
Sold separately, a thin decorative backplate is available to hide any marks/screw
holes left from the previous thermostat. This decorative backplate (or beauty ring)
is used by snapping it onto the back of the mounting plate before securing the plate
to the wall. 