Home > Carrier > Thermostat > Carrier Systxccitn01a Manual

Carrier Systxccitn01a Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Systxccitn01a Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							13
    A12213
    NOTE: Once the Infinity Touch Control is secured to wall with the backplate
    assembly (snapped together), care must be taken not to bend or break the
    interlocking tabs when removing.
    4.6. Humidifier Connections
    A 24VAC bypass or fan powered humidifier may be installed.
    NOTE: Do NOT use a traditional humidistat to control humidifier operation. If a
    humidifier is installed, let the Infinity Touch Control operate humidifier.
    4.6.1. Bypass Humidifier
    A bypass humidifier should be wired directly to the furnace or fan coil HUM and
    24VAC COM terminals. The Infinity Control Touch will automatically energize the
    HUM output during a call for humidification.
    4.6.2. Fan Powered Humidifiers
    Most fan powered humidifiers produce internal 24VAC in order to energize upon a
    switch or contact closure. For this application, a 24VAC N.O. Isolation Relay
    (DPST) MUST be used to prevent mixing the internal humidifier power with the
    indoor equipment transformer. Applying 24VAC isolation relay coil to furnace or
    fan coil HUM and COM terminals will allow the Infinity Touch Control to 
    						
    							14
    automatically energize the HUM output during a call for humidification. The N.O.
    relay contacts will be used to energize the humidifier. See fan powered humidifier
    installation instructions for more details.
    5. Commissioning
    This section addresses initial power up (or commissioning) of a new Infinityr
    Touch Control. The control will communicate and identify all components in the
    InfinityrSystem. The following is a typical example for a communicating
    variable --speed furnace / fan coil with a 2 --stage air--conditioner / heat pump
    (including HYBRIDHEATrdual fuel system).
    5.1. Searching for Indoor Unit
    The Infinity Touch Control will light up and begin the commissioning process by
    displaying “Searching for indoor unit”.
    A12177
    NOTE: If the variable --speed indoor equipment (furnace or fan coil) cannot be
    found, the control will display “Indoor unit not found”. ThisMUSTbe corrected
    before the initial power up sequence can continue. Proceed to the next section,
    Searching for outdoor unit. If it is not corrected, the Infinity Touch Control will go
    into itsDEMOoperating mode. 
    						
    							15
    A12178
    5.2. Searching for Outdoor Unit
    The Infinity Touch Control will then proceed to communicate with the outdoor unit
    by displaying “Searching for outdoor unit”.
    NOTE: If the outdoor unit cannot be found, the control will display “Outdoor unit
    not found”.
    SSelect the appropriate unit installed; then, touchNEXT.
    dAC1Stage– 1 --stage air conditioner
    dAC2Stage– 2 --stage air conditioner
    dHP1Stage– 1 --stage heat pump
    dHP2Stage– 2 --stage heat pump
    dNone– No outdoor unit installed
    SThe installer will first be instructed to select the appropriate size of the outdoor
    unit; then, touchNEXT. 
    						
    							16
    A12183
    5.3. Indoor Evaporator Selection
    If a furnace is installed with a variable capacity heat pump, a screen will appear to
    select the installed indoor evaporator coil. This selection is used to adequately
    calculate the refrigerant charge required while in the heat pump charging screens
    under the Heat Pump Checkout menu (See page 44). Select “other” for non --Carrier
    evaporators.
    5.4. Electric Heater Selection
    If the indoor equipment is a fan coil, the control will display “Searching for heater”
    until one is found. If the electric heater is not self--identifying, the select heater
    screen will appear. Touch the appropriate heater size; then, touchNEXT. 
    						
    							17
    A12184
    5.4.1. Hydronic Heat Application
    The Infinity Touch Control supports 2 types of Hydronic Heat applications:
    1. Hot water coil in combination with an FE fan coil and heat pump, or hot
    water coil as sole heat source with an FE fan coil.
    2. Non --zoned FE fan coil combined with radiant hot water heat.
    In either application, a Hydronic Heat kit should be installed in place of an electric
    heater. See FE fan coil Product Data for accessory part number. The system will
    self--identify that hydronic heat has been installed during electric heater selection.
    The system will treat the hot water coil as either auxiliary heat in a heat pump
    application, or the sole heat source. Setup options for Hydronic Heat applications
    are described in the setup section of this instruction.
    5.5. Searching for Zones (if applicable)
    “Zoning -- Searching” will appear on the screen to determine if any zones are
    present. The screen will show Zone 1, Zone 2, etc. and indicate all zones having
    either a Remote Room Sensor, or smart sensors associated with them. If the system
    contains smart sensors, they must be assigned a zone number before continuing.
    See the Smart Sensor Installation Instructions on how to assign Smart Sensors to
    their respective zones. After each zone has been identified, touchNEXT. 
    						
    							18
    A12185
    5.6. Filter Type Selection
    The installer will next be prompted to select the air filter type installed with the
    Infinity System. After the selection is made, touchNEXT.
    SAir Filter: 1 --in. to 4 --in. media filter
    SEAC: high voltage electronic air cleaner
    SAir Purifier: Infinityror PerformancetAir Purifier
    5.7. Humidifier Installation
    Next, the installer will be prompted to select whether a humidifier is installed in the
    system. SelectYESorNO, then touchNEXT.
    5.8. Ultraviolet Lights Installation
    Next, the installer will be prompted to select whether ultraviolet lights are installed
    in the system. SelectYESorNO, then touchNEXT.
    5.9. Equipment Summary
    The equipment summary screen will appear after accessories have been selected.
    This screen will give a summary of all equipment automatically found or manually
    selected. If an incorrect selection was made, touchRE-- INSTALLto go back to 
    						
    							19
    that particular screen and make changes. When everything is OK, touchNEXTto
    continue.
    A12144
    5.10. Static Pressure Check
    The static pressure check screen will appear next. The system will perform a static
    pressure check. This process will take about 1 --1/2 minutes to complete. When
    completed, a screen will appear displaying the static pressure (in inches) across the
    equipment at the expected highest delivered airflow. If the blower RPM is greater
    than 1200, then a warning will appear, but equipment operation and the
    TrueSensetdirty filter detection operation will not be affected. When the static
    pressure check is complete, touchNEXT.
    NOTE: The static pressure check occurs only at initial installation, or when
    INSTALLisrunintheINSTALL/SERVICEmenu.
    5.11. Duct Assessment (zoning applications only)
    The duct assessment screen will be displayed next for zoning applications. Touch
    NEXTto start Duct Assessment. Duct Assessment will measure the relative size of
    the ductwork, up to and through the dampers. These measurements are used to
    control the correct amount of airflow in the zoned system. Status messages will
    appear on the screen to indicate what the system is doing. The process will take 
    						
    							20
    approximately one minute per zone. The duct assessment will override a call for
    heat or cool.
    A duct assessment will automatically occur each day at a user selectable time. The
    factory default time is 1:00 p.m. but, may be changed by entering the Zoning Setup
    menu (see pages 36 -- 37). If there is an active call for heating or cooling, the
    system will wait until the call is satisfied before it performs the duct assessment.
    The system will first open all zones and drive the blower to 175 CFM/ton of cooling
    (or the minimum indoor unit’s airflow, whichever is greater). It will then take a
    static pressure measurement. The system will then close all zones and open one
    zone at a time, taking a static pressure measurement for each zone.
    The system will then close all zones and take a pressure measurement, getting a
    value for the duct leakage up to and through the dampers. With these static pressure
    measurements, the system will calculate the relative size of each zone as well as the
    percent leakage through the dampers At the end of the process, the display will
    show the relative size of each zone duct.
    If the Infinity Touch Control detects an error (damper not moving or damper wired
    backwards), it will perform the duct assessment again. If it still detects a damper
    problem, it will default the measurements into equal sizes, with 10% leakage, and
    display the zone number for the suspected zone damper.
    After the duct assessment is complete, touchNEXT.
    A12186 
    						
    							21
    6. Service Menu
    The Service menus contain a set of vital information. This information enables the
    installer or service person to view a summary of what has been installed, etc. This
    information is not covered in the Owner’s Manual.
    To enter service menus, touch menu, then touch and hold theSERVICEicon for at
    least ten seconds. The following screens are available in installation and service. To
    return to the previous screen, touchBACK. To exit the Service menus, touch
    DONE.
    A12145
    6.1. Equipment Summary
    TouchEQUIPMENT SUMMARYto show indoor unit type and model number,
    outdoor unit type (and model number if a 2 --stage unit), filter type, anyaccessories
    that are installed, and the number of zones in the system. To return to the previous
    screen, touchBACK. To exit the Service menus, touchDONE. 
    						
    							22
    A12144
    6.2. Installation
    TouchINSTALLATIONto perform the start --up process in order to learn all
    equipment in system. Press right side button to initiate the process. TouchNEXTto
    begin the process.
    A12146
    6.3. Set up
    6.3.1. Thermostat
    First touchSETUP, then touchTHERMOSTATto set up the parameters for the
    InfinityrTouch Control. 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Systxccitn01a Manual