    							®OPERATIONAL INFORMATION
    Five-minute Compressor Timeguard
    This timer prevents the compressor from starting unless it has been off for at least 5 minutes. It can be defeated for 1 cycle by simultaneously
    pressing the FAN mode button and the INCREASE TEMPERATURE button.
    Fifteen-minute Cycle Timer
    This timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle. Its function is to assure
    that equipment is not cycled more than 4 times per hr. This timer is defeated for 1 cycle when the desired temperature is manually changed.
    It can also be defeated for 1 cycle by simultaneously pressing the FAN mode button and the INCREASE TEMPERATURE button.
    Fifteen-minute Staging Timer
    In multistage heating or cooling, this timer prevents any higher stage from turning on until the preceding stage has been on for 15 minutes.
    This timer is defeated if the temperature error is greater than 5ÉF (usually due to a large change in desired temperature).
    Three-minute Minimum On Time
    In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes.
    Heat/Cool Set Points (Desired Temperatures)
    A minimum difference of 2ÉF is enforced between heating and cooling set points. This is done by allowing one setting to push the other, to
    maintain this difference.
    Auto Changeover
    When the auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed
    for 20 minutes. If the set point is changed, the 20 minute requirement is deleted. Auto mode may be disabled.
    Emergency Heat Mode
    When thermostat is configured as a heat pump and emergency heat mode is selected, all Y signals are locked out and W becomes energized
    upon a call for heat.
    Heat On and Cool On Icons
    When a heating or cooling demand exists, the HEAT ON or COOL ON icon will either remain on or flash. If flashing, the equipment is
    temporarily prevented from turning on by one of the timers (see above). While the icon remains on without flashing, the equipment is on.
    Power On Check
    When AC power is first applied, all segments of the display are turned on for a few sec. Following this, the temperature display indicates the
    model/configuration via the following 2 digit code:
    ACÐ1-speed air conditioner, HPÐ1-speed heat pump, A2Ð2-speed air conditioner, H2Ð2-speed heat pump.
    Error Codes
    -- Ð If the thermostat cannot properly read room temperature, the display will indicate -- (2 dashes) and all outputs (except the fan if on) will
    turn off. This is to prevent operation of the equipment if the thermostat has failed.
    E2 Ð If the AC line voltage drops below a minimum (brownout) level, all outputs are turned off and the display indicates E2. This condition
    will remain for 15 sec after proper line voltage is restored. If the AC line voltage disappears completely, the display will immediately go blank.
    E3 Ð If the thermostat cannot properly read outdoor temperature, and it is needed for proper operation (Heat pump system and Option 8 is
    not set to OF), E3 will flash alternately with room temperature.
    ®Thermostat Troubleshooting
    SYMPTOM WHAT TO CHECK
    Blank LCDCheck for 24vac between R and C at terminal connections. Both R and C must be con-
    nected for proper operation.
    -- (2 dashes) on temperature displayTemperatrue sensor reading out of range. Check sensor for damage. If recycling power
    does not clear display, thermostat should be replaced.
    E2 on temperature displayBrownout condition or too low of voltage to thermostat. Double check wiring and check for
    24vac between R and C. E2 will clear 15 sec after proper voltage is restored.
    E3 on temperature displayThe outdoor temperature sensor is open, not connected, or shorted.
    FILTER on temperature displayAfter the selected number of hour of blower operation FILTER will display on LCD. This
    is to remind the homeowner to check the filter. Press RESET FILTER button to clear
    display and reset timer to 0.
    Cooling will not come onSelect COOL mode. Set desired temperature to 10ÉF below room temperature. Simulta-
    neously press FAN and INCREASE TEMPERATURE buttons to defeat timers. Check for
    COOL ON icon and 24vac at Y (first-stage) terminal. If present, thermostat is OK and
    problem is with equipment or wiring. If not present, replace thermostat.
    Heating will not come onSelect HEAT mode. Set desired temperature to 10ÉF above room temperature. Simulta-
    neously press FAN and INCREASE TEMPERATURE buttons to defeat timers. Check for
    HEAT ON and 24vac at Y (first-stage) terminal (with heat pump) or W/W1 (with air condi-
    tioner) terminal. If present, thermostat is OK and problem is with equipment or wiring. If
    not present, replace thermostat.
    11 
    						
    							A98468
    NON-PROGRAMMABLE THERMOSTAT CONFIGURATION RECORD
    Date
    Owner/Operator
    A)  Hardware Configuration
    				  R19 Resistor located on Model HP and 2S only.  (Uncut = Enable Heat Pump Operation,
    				  Cut = Air Conditioner Operation)
    				  No R19 Resistor present.  (Model AC thermostat only)Thermostat Model No.
    B)  Mode Settings
    
    C)  Configuration Options
    Mode (Off, Heat, Cool, Auto, Eheat)
    Heating Set Point Value
    Cooling Set Point Value
    Fan (Auto or On)
    1  			 Anticipator (1-9: factory default = 3)
    2  			 Clean Filter Timer (Off or 1-9: factory default = 2)
    3  			 Fahrenheit or Celsius (F or C: factory default = F)
    4 			 Fan On with W (Off or On: factory default = Off)
    5-6			 N/A
    7			 Zoning Selection (Off or On: factory default = Off)
    8			 Auxiliary Heat Lockout (Off or 5-55 F: factory default = Off)
    9-12		 N/A
    13			 Room Temperature Offset (-5 to +5: factory default = 0)
    14			 N/A
    15			 Enable Auto Mode (Off or On: factory default = On)		  
    Copyright 1998 CARRIER Corp. · 7310 W. Morris St. · Indianapolis, IN 46231tstat16si
    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
    Book 1 4
    Tab misc. misc.
    PC 101 Catalog No. 03TS-TA5 Printed in U.S.A. Form TSTAT-16SI Pg 12 10-98 Replaces: TSTAT-14SI 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Tstatccnhp01 B Manual