Home > Honeywell > Security system > Honeywell K35891 Manual

Honeywell K35891 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell K35891 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							 
    – 41 – 
    Testing the System 
    About Testing the System 
    Using the Test mode allows each protection point to be checked for proper operation. 
    Testing should be conducted weekly to ensure proper operation. 
     •  The keypad sounds a single beep about every 30 seconds as a reminder that the 
    system is in the Test mode. 
     •  Alarm messages are not sent to your Central Station while Test mode is on.
     
    1.  Disarm the system and close all protected windows, 
    doors, etc. The READY indicator light should come on 
    if all zones are intact (i.e., all protected windows, 
    doors, etc. are closed. Alpha Displays: 
    ∗∗∗∗DISARMED∗∗∗∗ 
    READY TO ARM    
    2.              +  5  TEST  then  [0] (walk) 
     (Master Code)  
     
    The Dial test (option “1”) is intended for the installer 
    and should not be used unless directed to do so by your 
    Security System Representative. 
    1 = DIAL,  0 = WALK 
     
      
    3.  Listen. The external sounder should sound for about 1 
    second then turn off. If the sounder does not sound, 
    CALL FOR SERVICE.  The “Test in Progress” display 
    appears only on the keypad that started the test. TEST IN PROGRESS 
     
      
    4.  Fault zones. Open each protected door and window in turn and listen for three 
    beeps from the keypad. Identification (zone number or zone description) of each 
    faulted protection point should appear on the display. The display clears when the 
    door or window is closed. 
    5.  Walk in front of any interior motion detectors (if used) and listen for three beeps. 
    The identification of the detector should appear on the display when it is activated. 
    The display clears when no motion is detected. Note that if wireless motion detectors 
    are used, there is a 3-minute delay between activations. This conserves battery life. 
    6.  Test all smoke detectors, following the manufacturers instructions. The 
    identification of each detector should appear on the display when each is activated. 
      If a problem is experienced with any protection point (no confirming sounds, no 
    display), call for service immediately. 
      When all protection points have been checked and are intact (closed), there should 
    be no zone identification numbers displayed on the keypad. 
    7.  Exit test mode:    
                  +  1   OFF  
      (Security Code) 
    If the test mode is inadvertently left active, it automatically turns off after 4 hours. 
    During the final five minutes, the keypad will emit a double beep every 30 seconds.  
    						
    							 
    – 42 – 
    Trouble Conditions 
     
    Check and 
    Battery Displays 
      
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
     
    The word CHECK on the keypads display, accompanied by a 
    beeping at the keypad, indicates a trouble condition in the system. 
    To silence the beeping for these conditions, press any key. 
    1. A display of CHECK and one or more zone numbers 
    indicates that a problem exists with the displayed zone(s) and 
    requires your attention. Determine if the zone(s) displayed are 
    intact and make them so if they are not. If the problem has been 
    corrected, the display can be cleared if you enter the OFF 
    sequence (security code plus OFF key) twice. If the display 
    persists, CALL FOR SERVICE. 
     Note: A display of CHECK 70 on Alpha Display keypads 
    indicates that the wiring connection to the external sounder is 
    at fault (opened or shorted), and you should CALL FOR 
    SERVICE. See “BELL FAILURE” on next page. A display of 
    CHECK 90 indicates that RF interference may be impeding the 
    operation of wireless sensors* in the system. See “Rcvr Jam” 
    on next page. 
    2. If there are wireless sensors* in your system, the CHECK 
    condition may also be caused by some change in the 
    environment that prevents the wireless receiver from receiving 
    messages from a particular sensor.  CALL FOR SERVICE if this 
    occurs.  
     
    *  Not all systems use wireless sensors.  
    IF YOU CANNOT CORRECT A CHECK DISPLAY, 
    CALL FOR SERVICE. 
     
     
    TYPICAL CHECK DISPLAYS  
    06 
    CHECK 
            AC  
     
     
     
    FIXED-WORD DISPLAY KEYPAD 
    CHECK 06  
    BEDROOM WINDOW 
    ALPHA DISPLAY KEYPAD 
    						
    							 
    – 43 – 
    Trouble Conditions (cont’d) 
     
    Words or letters in parentheses (   ) are those that are displayed on Fixed-Word Display 
    keypads. 
     
    Other Trouble 
    Displays 
     
      
    * Any “beeping” that 
    accompanies a 
    trouble display can 
    be stopped by 
    depressing any key 
    on the keypad or by 
    entering an OFF 
    sequence (code + 
    OFF)  
     
     
     
    **    Not all systems use 
     wireless sensors. 
     COMM. FAILURE  Indicates that a failure has occurred in 
    (or FC)  the telephone communication portion of 
    your system. CALL FOR SERVICE.  
     
    SYSTEM LO BAT  Indicates that a low system battery  
    (or BAT with no  condition exists.  Display is  
    zone No.)  accompanied by beeping* at the 
    keypad. If this condition persists for 
    more than one day (with AC present), 
    CALL FOR SERVICE. 
     
    LO BAT  Indicates that there is a low battery 
    + zone descriptor  condition in the wireless transmitter** 
    (or BAT with  number displayed (00 is RF keypad).  
    zone No.)  Accompanied by a single beep*
     (about 
    once every 30 seconds) at the keypad.  
        Either replace the battery yourself, or 
    CALL FOR SERVICE.  If the battery is 
    not replaced within 30 days, a CHECK 
    display may occur.  
     
    Rcvr Jam  Wireless part of the system is experiencing
    (or CHECK 90)  RF interference which may impede 
    reception from wireless sensors.** 
     
    ALARM 1xx 
    FAULT 1xx 
    CHECK 1xx 
    (or 91) Indicates a communication problem 
    between the control and a connected 
    device (e.g., RF receiver, zone expander) 
    where the “xx” indicates the device 
    address. CALL FOR SERVICE. 
     
    MODEM COMM  
    (or CC) Indicates that the control is on-line with 
    the Central Monitoring Stations remote 
    computer.  
    The control will not report system 
    activity while on-line. Wait a few minutes 
    — the display should disappear. 
     
    BELL FAILURE Indicates that the wiring connection to  
    (or CHECK 70)  the external sounder is at fault (open or 
    shorted). Accompanied by “beeping” at 
    the keypad. CALL FOR SERVICE.  
      
    						
    							 
    – 44 – 
    Trouble Conditions (cont’d)  
     
    Other Trouble 
    Displays 
    (Continued) AC LOSS  The system is operating on battery power 
    (or NO AC)
      only due to an AC power failure.  
      
    If only some lights are out on the 
    premises, check circuit breakers and 
    fuses and reset or replace as necessary.  
      If AC power cannot be restored and a 
    “low system battery” message appears 
    (see previous page), CALL FOR 
    SERVICE. 
     
    Busy-Standby 
    (or dI) If this message remains displayed for 
    more than 1 minute, system is disabled. 
    CALL FOR SERVICE. 
     
    OPEN CIRCUIT   The keypad is not receiving signals from  
    (or OC)  the control. CALL FOR SERVICE. 
     
     
    Long Rng Trbl If part of your system, back-up  
    (or bF)  communication device has failed.  
       CALL FOR SERVICE. 
     
     
    TELCO FAULT    The telephone line has a problem. 
    (or CHECK 94) CALL FOR SERVICE. 
     
     
    Total Power FailureIf there is no keypad display at all, and the READY indicator is not 
    lit, operating power (from AC and back-up battery) for the system 
    has been interrupted and the system is inoperative. CALL FOR 
    SERVICE.  
     
    In The Event Of Telephone Operational Problems 
    In the event of telephone operational problems, disconnect the control from the phone line by 
    removing the plug from the phone wall jack. We recommend that your installer demonstrate this 
    disconnection on installation of the system. Do not attempt to disconnect the phone connection 
    inside the control. Doing so will result in the loss of your phone lines. If the regular phones work 
    correctly after the control has been disconnected from the phone wall jack, the control has a 
    problem and you should immediately call for service. If upon disconnection of the control, there is 
    still a problem on the phone line, notify the Telephone Company that they have a problem and 
    request prompt phone repair service. The user may not under any circumstances attempt any 
    service or repairs to the security system. Repairs must be made only by authorized service (see 
    the LIMITED WARRANTY statement for information on how to obtain service).      
      
    						
    							 
    – 45 – 
    Maintaining Your System 
     
    Taking Care of 
    Your System The components of your security system are designed to be as 
    maintenance-free as possible. However, to make sure that your 
    system is in reliable working condition, do the following: 
    1.  Test your system weekly
    . 
    2.  Test your system after any alarm occurs.
      
    Silencing Low 
    Battery Warning 
    Tones at the 
    Keypad You can silence the keypad’s warning tones by pressing the OFF key, 
    but the keypads low battery message display will remain on as a 
    reminder that you have a low battery condition in one or more of your 
    wireless sensors. When you replace the weak battery with a fresh one, 
    the sensor sends a good battery signal to the control as soon as the 
    sensor is activated (opening/closing of door, window, etc.), causing the 
    low battery display to turn off. If the sensor is not activated, the 
    display will automatically clear within approximately 1 hour. 
     
    Replacing 
    Batteries in 
    Wireless Sensors 
     
     
    Wireless sensors 
    may not have 
    been used in your  
    security system  
     
    IMPORTANT:  
    Use only batteries 
    recommended by 
    your installer as 
    replacement. 
    Each wireless sensor in your system has a 9-volt or 3-volt battery. 
    The system detects a low battery in wireless sensors, including smoke 
    detectors, the personal emergency transmitter, and the portable 
    wireless keypad and displays a low battery message*. (A low battery 
    in a portable wireless keypad is detected as soon as one of its keys is 
    pressed, and displayed as 00.). Battery-operated smoke detectors with 
    a low battery also emit a single chirp sound approximately once 
    every 20–30 seconds. 
    Alkaline batteries provide a minimum of 1 year of operation, and in 
    most units and applications, provide 2–4 years of service. 3-volt 
    lithium batteries provide up to 4 or more years of operation. Actual 
    battery life will depend on the environment in which the sensor is 
    used, the number of signals that the transmitter in the sensor has had 
    to send, and the specific type of sensor. Factors such as humidity, high 
    or low temperatures or large swings in temperature, may all lead to 
    the reduction of actual battery life in an installation. 
     
    * The low battery message comes on as a warning that battery replacement 
    in indicated sensor(s) is due within 30 days. In the meantime, a sensor 
    causing a low battery indication is still fully operational.
     
    Routine Care  Treat the components of your security system as you would any 
    other electrical equipment. Do not slam sensor-protected doors or 
    windows. 
     Keep dust from accumulating on the keypad and all protective 
    sensors, particularly on motion sensors and smoke detectors. 
     The keypad and sensors should be cleaned carefully with a dry soft 
    cloth. Do not spray water or any other fluid on the units.  
    						
    							 
    – 46 – 
    Fire Alarm System 
     
    THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS   
    General Your fire alarm system (if installed) is on 24 hours a day, for 
    continuous protection. In the event of an emergency, the strategically 
    located smoke and heat detectors will sound their alarms and 
    automatically send signals to your system, triggering a loud, 
    interrupted pulsed sound* from the Keypad(s) and any external 
    sounders. A FIRE message will appear at your Keypad and remain on 
    until you silence the alarm (see below for silencing fire alarms).  
    *
     Temporal pulse sounding is produced for Fire alarms, as follows: 
     3 pulses–pause–3 pulses–pause–3 pulses–pause. . . , repeated. 
     
     TYPICAL FIRE EMERGENCY  DISPLAYS 
     
    FIRE 01   MASTER 
    BEDROOM 
     01
    0101 01 
        
    ALARM 
     FIRE   
    AC 
     
     
     ALPHA DISPLAY KEYPADFIXED-WORD DISPLAY KEYPAD 
    Silencing  
    Fire Alarms and 
    Clearing Memory 
    of Alarm 1.  You can silence the alarm at any time by pressing the OFF key 
    (the security code is not needed to silence fire alarms). To clear the 
    display, enter your code and press the OFF key again (to clear 
    Memory of Alarm). 
    2.  If the Keypads FIRE display does not clear after the second OFF 
    sequence, smoke detectors may still be responding to smoke or 
    heat producing objects in their vicinity. Investigate, and should 
    this be the case, eliminate the source of heat or smoke. 
    3.  If this does not remedy the problem, there may still be smoke in 
    the detector. Clear it by fanning the detector for about 30 seconds.
    When the problem has been corrected, clear the display by 
    entering your code and pressing the OFFkey. 
     
    Smoke Detector 
    ResetDepending on the type of smoke detectors in your system, it may be 
    necessary to reset the smoke detectors after a fire alarm has been 
    turned off. Check with your installer. This reset is accomplished at 
    a keypad, as follows:   
    Enter Security Code ( except “arm only” user), then press the [1] key. 
    NOTE: During smoke detector reset, “FAULT xx” appears (about six 
    seconds) and should disappear if the detector is clear.  
    						
    							 
    – 47 – 
    Fire Alarm System (cont’d) 
    THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS   
    Manually 
    Initiating 
    a Fire Alarm 1.  Should you become aware of a fire emergency before your smoke or 
    heat detectors sense the problem, go to your nearest keypad and 
    manually initiate an alarm by pressing the panic key assigned for 
    FIRE emergency for 2 seconds (see below). If a key pair has been 
    assigned for fire, press both keys at the same time. See the Using 
    the Panic Keys section below for further details. 
    2.  Evacuate all occupants from the premises. 
    3.  If flames and/or smoke are present, leave the premises and notify 
    your local Fire Department immediately. 
    4.  If no flames or smoke are apparent, investigate the cause of the 
    alarm. The zone number(s) of the zone(s) in an alarm condition will 
    be displayed at the keypad. 
      
    Using the 
    Panic Key(s) 
    Assigned for 
    FIRE 
    Emergency A key or key pair may have been assigned for manually initiating a 
    FIRE alarm. See the Panic Keys section for key assignments. 
    For convenience, indicate the key or key pair assigned for fire below. 
    Individual Keys 
    A  B C 
       
                  Press the individual key assigned for fire for 2 seconds. 
    OR Key Pairs 
       
       1 OFF and   ∗ READY  (zone 95) 
       
       ∗ READY and  #       (zone 99) 
          3 STAY   and #       (zone 96) 
       DISPLAYS FOLLOWING MANUAL INITIATION OF A FIRE ALARM 
     FIRE 95 
     
    95
    9595 95 
        
    ALARM 
    FIRE
     AC 
     
     
     ALPHA DISPLAY KEYPAD 
     FIXED-WORD KEYPAD     
    Carbon 
    Monoxide 
    Alarms If installed, carbon monoxide detectors provide continuous protection. 
    If a high level of carbon monoxide is detected, an interrupted pulsed 
    alarm sound occurs at the keypads and the detector(s). Immediately 
    move to a spot where fresh air is available, preferably outdoors. From 
    a safe area, call your security service provider for further instructions. 
    To silence the keypad sounding, press the OFF key. To silence the 
    detector, see its instructions. 
    Press both keys of the 
    key pair assigned for 
    fire at the same time.  
    						
    							 
    – 48 – 
    Fire Alarm System (cont’d) 
    THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS  
     
    National Fire Protection Association 
    Recommendations on Smoke Detectors 
     
     
    With regard to the number and placement of smoke/heat detectors, we 
    subscribe to the recommendations contained in the National Fire Protection 
    Associations National Fire Alarm Code (NFPA 72) noted below. 
    Early warning fire detection is best achieved by the installation of fire 
    detection equipment in all rooms and areas of the household as follows: A 
    smoke detector installed outside of each separate sleeping area, in the 
    immediate vicinity of the bedrooms and on each additional story of the 
    family living unit, including basements and excluding crawl spaces and 
    unfinished attics.  
    In addition, the NFPA recommends that you install heat or smoke detectors 
    in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, 
    furnace room, utility and storage rooms, basements and attached garages. 
     
    DININGKITCHENBEDROOM
    BEDROOM
    BEDROOM
    BEDROOM
    LIVING ROOMBEDROOMBDRM DINING 
    LIVING ROOM TV ROOMKITCHEN
    BEDROOM
    BEDROOM TO
    BR
    LVNG RM
    BASEMENTKTCHN.CLOSED
    DOORGARAGE
    Smoke Detectors for Minimum Protection
    Smoke Detectors for Additional Protection
    Heat-Activated Detectors
    BDRM
    floor_plan-001-V1  
    						
    							 
    – 49 – 
    Fire Alarm System (cont’d) 
    THIS SECTION APPLIES ONLY TO RESIDENTIAL SYSTEMS  
     
    Emergency Evacuation 
     
      
    2nd FLOOR
    BACK
    FRONTfloor_plan-002-V0
    BATH CLOSET
    BEDROOM
    BEDROOM
    BEDROOM
    1st FLOOR
    BATH KITCHEN
    BEDROOMBEDROOM
    PORCH
    BACK DOOR
     Establish and regularly practice a plan of escape in the 
    event of fire. The following steps are recommended by 
    the National Fire Protection Association: 
    1.  Position your detector or your interior and/or 
    exterior sounders so that they can be heard by all 
    occupants. 
    2.  Determine two means of escape from each room. 
    One path of escape should lead to the door that 
    permits normal exit from the building. The other 
    may be a window, should your path be impassable. 
    Station an escape ladder at such windows if there 
    is a long drop to the ground. 
    3.  Sketch a floor plan of the building. Show windows, 
    doors, stairs and rooftops that can be used to 
    escape. Indicate escape routes for each room. Keep 
    these routes free from obstruction and post copies 
    of the escape routes in every room. 
    4.  Assure that all bedroom doors are shut while you 
    are asleep. This will prevent deadly smoke from 
    entering while you escape. 
    5.  Try the door. If the door is hot, check your 
    alternate escape route. If the door is cool, open it 
    cautiously. Be prepared to slam the door if smoke 
    or heat rushes in. 
    6.  When smoke is present, crawl on the ground. Do 
    not walk upright, since smoke rises and may 
    overcome you. Clearer air is near the floor. 
    7.  Escape quickly; dont panic. 
    8. Establish a common meeting place outdoors, away 
    from your house, where everyone can meet and 
    then take steps to contact the authorities and 
    account for those missing. Choose someone to 
    assure that nobody returns to the house — many 
    die going back.  
    						
    							 
    – 50 – 
    Quick Guide to Basic System Functions 
    FUNCTION PROCEDURE  COMMENTS 
    Check Zones Press READY key.  View faulted zones when system not 
    ready. 
    Arm System Enter code. Press arming key desired: 
    (AWAY, STAY, NIGHT-STAY, MAXIMUM, 
    INSTANT) Arms system in mode selected. 
    Quick Arm 
    (if programmed) Press #. Press arming key desired: 
    (AWAY, STAY, MAXIMUM, INSTANT) Arms system in mode selected, quickly 
    and without use of a code. 
    Bypass Zone(s) Enter code. Press BYPASS [6] key. 
    Enter zone number(s) to be bypassed  
    (use 2-digit entries). Bypassed zones are unprotected and 
    will not cause an alarm if violated. 
    Quick Bypass 
    (if programmed) Enter code. Press BYPASS [6] key + [#].  Bypasses all faulted zones 
    automatically. 
    Silence Sounders 
     Burglary: 
      Fire or CO: 
     Check:  
    Enter code. Press OFF [1] key. 
    Press OFF [1] key. 
     
    Press any key. 
     
    Also disarms system. Memory of alarm 
    remains until cleared. 
    Memory of Alarm remains until 
    cleared. 
    Determine cause.  
    Disarm System Enter code. Press OFF [1] key. (OFF need 
    not be pressed if entry delay or an alarm is 
    active) Also silences sounders. Memory of 
    alarm remains until cleared. 
    Clear Alarm 
    Memory After disarming, enter code again.  
    Press OFF [1] key again. Keypad beeps rapidly on entry if alarm 
    has occurred while absent. Alarm 
    display will remain upon disarming 
    until cleared. 
    Duress (if active 
    and connected to  
    Central Station) Arm or disarm normally, but use your 4-
    digit Duress code to do so.  Performs desired action and sends 
    silent alarm to Central Station. 
    Panic Alarms 
    (as programmed) Press key [A], [B], or [C] for at least 2 
    seconds, or key pairs 1 + 
    ✱; ✱ + #, or 3 + # 
    respectively. See the Panic Keys section for 
    emergency functions programmed for 
    your system. Note: Keys “A”, “B”, and 
    “C” may have been programmed for 
    other functions. 
    Chime Mode To turn ON or OFF: Enter code. Press 
    CHIME key. The keypad will sound if doors or 
    windows are violated while system is 
    disarmed and chime mode is ON. 
    Test Mode To turn ON: Enter code. Press TEST key, 
    then [0]. 
    To turn OFF: Enter code. Press OFF key. Tests alarm sounder and allows 
    sensors to be tested. 
    Phone Access 
    if applicable Consult Phone Access Users Guide that 
    accompanies the Phone Module. Permits system access remotely, via 
    Touch-tone phone.  
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell K35891 Manual