Home > Honeywell > Controller > Honeywell T775abm Manual

Honeywell T775abm Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell T775abm Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    1162-0254—13
    CHECKOUT
    Inspect all wiring connections at the controller terminals, 
    and verify compliance with the installation wiring 
    diagrams.
    WARNINGElectrical Shock Hazard.
    Can cause severe injury, death or property 
    damage.
    Disconnect power supply before beginning wiring 
    or making wiring connections, to prevent electrical 
    shock or equipment damage.
    If any wiring changes are required, first be sure to remove 
    power from the controller before starting work. Pay 
    particular attention to verifying the power connection (24, 
    120, or 240 Vac).
    After the controller is installed and wired, apply power.
    Power Loss
    The date and time settings are retained for 24 hours after 
    a power outage. After a power loss of more than 24 hours, 
    the date and time settings may need to be reentered. All 
    other settings are stored permanently.
    Temperature Sensor Calibration
    As wire length increases, resistance increases and thus 
    the temperature reading increases. If necessary, calibrate 
    the sensor input by reducing the value by the amount 
    shown in the Table 3. For example, a wire run with 18 
    gauge wire of 1,000 feet, requires a calibration offset of 
    -6.0° F (-21° C).
    IMPORTANT
    If the calibration value in the table exceeds the 
    controller’s calibration limits of +/-10° F (+/-6° C), 
    you must use a heavier gauge wire.
    For example, with a wire run of 1,000 feet you 
    must use 20 AWG wire or heavier in order to 
    calibrate for wire loss within the limits of the 
    controller.
    See “2.2.2.2. CALIBRATE (the sensor)” on page 18 for 
    the instructions to enter the calibration value.Fig. 23 shows how sensor resistance varies with 
    temperature for a sensor having a positive temperature 
    coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms 
    per degree C)
    .
    Fig. 23. Sensor Resistance vs. Temperature. Table 3. Temperature Sensor Calibration for Resis-
    tance Loss Due to Wire Length.
    AW G
    Rating mΩ/ftTemperature Offset in 
    °F (Foot)
    a
    a
    This is the distance from the controller to the sensor 
    (already accounts for round trip distance).200 ft 500 ft 1,000 ft
    14 2.5 0.46 1.14 2.28
    16 4.0 0.72 1.82 3.64
    18 6.4 1.16 2.90 5.82
    20 10.2 1.86 4.64 9.28
    22 16.1 2.92 7.32 14.64
    AW G
    Rating mΩ/mTemperature Offset in 
    °C (Meter)
    a
    100 m 200 m 300 m
    14 8.3 0.44 0.86 1.30
    16 13.2 0.68 1.38 2.06
    18 21.0 1.10 2.18 3.28
    20 33.5 1.74 3.48 5.22
    22 52.8 2.74 5.48 8.22
    M24304
    TEMPERATURE (DEGREES)
    RESISTANCE (OHMS)
    1403
    1317
    1231
    11 4 5
    1059
    973
    20 40 60 80 100 120 140 160 180 200 220
    0 10 20 30 40 50 60 70 80 90 100°F
    °C 0 -20 -40
    120
    11 0250-40 -20 -10-30
    1489
    887
    801
    1097 ± 0.08 OHMS
    AT 77°F (25°C)
    POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F1
    1 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—1312
    INTERFACE OVERVIEW
    The T775A/B/M controllers use an LCD panel and 
    6-button keypad to provide status information and permit 
    user input of the programming, setup, and scheduling 
    parameters.
    The following figure describes the display areas of the 
    LCD and the keypad
    .
    Fig. 24. LCD Display - Home Screen And Keypad.
    Menu Area – On the home screen, the LCD displays the 
    configured relays and whether they are active. In 
    Program, Setup or Schedule mode, the LCD displays the 
    current menu selection and its order within the menu 
    hierarchy.
    Data Area – On the home screen, the LCD displays the 
    sensors and outputs status. In Setup or Program mode, 
    the LCD displays menu choices, parameter selections, 
    and data values.
    Lock Icon – The icon indicates the MENU button is 
    locked and prevents access to the Setup and Program 
    menus.
    NOTE: Pressing and holding the HOME and MENU 
    buttons simultaneously for five seconds 
    locks/unlocks the MENU button.
    6-Button Keypad – The keypad is used to access the 
    menus and enter values (See “Using the LCD Panel 
    Interface”).
    Using the LCD Panel Interface
    The 6-button keypad is used to move through the menus 
    and enter or change parameter values.
    Home Button
    Pressing the HOME button at any time exits the current 
    Programming or Setup display screen and returns to the 
    home screen as shown in Fig. 24 and Fig. 25.
    Menu Button
    •Pressing the MENU button always displays the 
    Program menu. If you are in Setup mode, you exit 
    setup and return to the Program menu.
    • Pressing and holding the MENU button for five 
    seconds leaves the current screen and displays 
    the Setup menu.
    Left and Right Arrow Buttons ( and )
    Use these buttons to move backward () and forward 
    () through the Program and Setup menus.
    Up and Down Arrow Buttons ( and )
    Use these buttons to move your selection up and down 
    through a menu or list.
    • When the desired item is highlighted, you press the 
     arrow button to display that item’s content.
    • When a value is displayed (e.g. 70° F), the up and 
    down arrows increase and decrease the value.
    NOTE: Once you select an item from a list or enter a 
    value, pressing the
      or  or HOME but-
    ton accepts your selection or value and 
    stores it in the controller’s memory.
    Home Screen
    In the normal run state, the LCD home screen displays 
    the current sensed temperatures, the modulating outputs 
    status, the active status of the output relays, and error and 
    status codes. 
    Active relays are indicated by the small black square („) 
    just below the relay number. Fig. 25 shows the home 
    screen with relays 1, 2, and 4 energized. 
    Pressing the 
     and  buttons from the home screen 
    cycles through each modulating output that is paired with 
    the sensor it controls and the active output relays
    .
    Fig. 25. LCD Display - Home Screen Displaying 
    Sensors, Active Relays, and Mod Outputs.
    NOTE: The modulating output home screen and the 
    relay home screen do not dynamically update 
    the active relay status, sensor values, and 
    modulating output percentages. The 
    information is a snapshot taken when you 
    press the 
     or  button to display the 
    screen.
    MOD1             40%
    MOD2             60%
    DI ON
    HOME
    RELAYS  1  2  3  4
            ON
    SENSORSSENSOR A78SENSOR B84
    MENU AREA
    home menuF o
    F o
    DATA AREA
    LOCK ICON
    6 BUTTON KEYPAD
    M24488
    MOD1             40%
    MOD2             60%
    DI ON            HOME
    RELAYS  1  2  3  4
            ON
    SENSORS
    SENSOR A
    78SENSOR B84
    o
    oF
    F
    MOD1             40%
    MOD2             60%
    DI ON            HOME
    RELAYS  1  2  3  4
            ON
    oF
    oF REL 1          ON
    HEAT
    SETPOINT
    60SENSOR A62
    RT 12345 HRS
    DI ON            HOME
    RELAYS  1  2  3  4
            ON
    MOD 1          40%
    COOL
    SETPOINT
    74SENSOR A62
    o
    oF
    F
    M24489
    MOD1             40%
    MOD2             60% 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    1362-0254—13
    IMPORTANT
    After four minutes of inactivity (no buttons 
    pressed), the LCD display reverts to the home 
    screen display.
    Accessing the Menus
    Menus are used for programming, scheduling, viewing the 
    summary settings, and setup of advanced options.
    Programming, Scheduling, and 
    Summary Menus
    To access these menus from the home screen, press the 
    MENU button (See Fig. 26)
    .
    Fig. 26. Menus.
    Depending on whether scheduling is enabled or not, the 
    LCD displays one of two menus as shown in Fig. 26. 
    Scheduling is enabled from the Setup menu’s Output 
    settings (See “2.3.3.1. USE SCHED” on page 25).
    Setup Menu
    To access the Setup menu, press and hold the MENU 
    button for five seconds (Refer to Fig. 27).
    Fig. 27. Setup Menu.
    Using the Menus
    When you are working with the menus, use the:
    • Left arrow button (
    ) to scroll backward through 
    the menus •Right arrow button () to select the 
    highlighted menu item and display its content
    • Up and Down arrow buttons (
     and ) to scroll up 
    and down through a list of items or to increase or 
    decrease the value of a displayed parameter
    NOTE: If you press the HOME button or there is no 
    keypad activity for four minutes, you exit 
    Program mode and return to the home 
    screen.
    If you press the MENU button, you exit and 
    return to the menu.
    MENU
    PROGRAM
    EXIT
    homemenuORMENU DISPLAY WHEN
    SCHEDULING IS NOT SET MENU DISPLAY WHEN
    SCHEDULING IS SET
    MENU
    MOD1             40%
    MOD2             60%
    DI ON            HOME
    RELAYS  1  2  3  4
            ON
    F o 
    F o  SENSORS
    SENSOR A
          78SENSOR B      84
    PROGRAM
    SCHEDULE
    SUMMARY
    EXIT
    M24490
    homemenu
    SETUP
    MOD1             40%
    MOD2             60%
    DI ON            HOME
    RELAYS  1  2  3  4
            ON
    FIVE
    SECONDS F o 
    F o  SENSORS
    SENSOR A
          78SENSOR B      84
    SENSORS
    OUTPUTS
    EXIT
    M24491 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—1314
    1. PROGRAMMING
    The controller must be programmed before being placed 
    into service.
    IMPORTANT
    During programming, the controller is live at all 
    times. For example, the contacts may open and 
    close when adjusting the setpoint.
    The Programming process uses a hierarchical menu 
    structure that is easy to use. You press the 
     and  
    arrow buttons to move forward and backward through the 
    menus. 
    NOTES:
    1. The controller interface is intuitive. You may 
    find that you do not need the following 
    procedure instructions to program the 
    controller. You may want to use this 
    procedure simply as a reference to locate the 
    particular option or parameter of interest.
    2. The menus can display only those relays that 
    are defined in Setup (See “2.3.2. NBR OF 
    RELAYS” on page 24). For example, if you 
    configure only two relays, then only two relays 
    display on the appropriate menus.
    3. If you press the HOME button or there is no 
    keypad activity for four minutes, you exit 
    Program mode and return to the home 
    screen.
    4. If you press the MENU button, you exit 
    Program mode and return to the menu.
    Setpoint and Differential
    The following describes the relationship between setpoint 
    and differential for heating and cooling. These settings are 
    programmed for each output relay.
    Heating Mode Setpoint and Differential
    In heating mode, the differential is below the setpoint. The 
    relay de-energizes when the temperature rises to the 
    setpoint. As the temperature drops to the setpoint minus 
    the differential, the relay energizes.
    Cooling Mode Setpoint and Differential
    In cooling mode, the differential is above the setpoint. The 
    relay de-energizes when the temperature falls to the 
    setpoint. As the temperature rises to the setpoint plus the 
    differential, the relay energizes.
    Setpoint High Limit
    You can set a single irreversible setpoint high limit 
    maximum value, which is applied to all outputs.
    Adjust the setpoint (at any output) to the desired 
    maximum setpoint. Then, simultaneously press the 
    home, 
    , and  buttons and continue to press all three 
    buttons for five seconds to set the setpoint high limit 
    maximum to this value.
    NOTE: You must press all three buttons at exactly 
    the same time for this action to occur.
    IMPORTANT
    1. This action sets the maximum setpoint value of 
    all outputs to the setpoint high limit maximum.
    2. Setting the high limit setpoint maximum is 
    irreversible. If you perform the action 
    inadvertently gently and this setpoint adversely 
    affects the control of your system, you must 
    replace the controller.
    Programming the T775A/B/M 
    Controller
    To program the controller, perform the following 
    procedures in the order listed:
    1.Enter Program mode — see “1.1. Entering Program 
    Mode” 
    2.Program the Outputs — see “1.2. Program Menu for 
    Outputs”
    When programming is complete, you may continue with 
    “3. SCHEDULING” on page 30 or, for advanced options, 
    continue with “2. SETUP (ADVANCED OPTIONS)” on 
    page 17.
    Fig. 28. Program Menu.
    1.1. Entering Program Mode
    Press the MENU button, then select PROGRAM and 
    press the  button to view the Program menu.
    Fig. 28 shows the Program menus for controllers with and 
    without Modulating Outputs.
    NOTE: Modulating outputs are not available on the 
    T775A and T775B controller models.ORMENU
     PROGRAM
    MENU
    PROGRAM
    M24492
    RELAY 1
    RELAY 2
    RELAY 3
    RELAY 4
    EXIT
    MENU
    PROGRAM
    MOD 1
    MOD 2
    RELAY 1
    RELAY 2
    RELAY 3
    RELAY 4
    EXIT 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    1562-0254—13
    Fig. 29. Program Menu Outputs.
    1.2. Program Menu for Outputs
    Press the MENU button, select PROGRAM, then select 
    RELAY 1 (or MOD 1) to view the parameters. Fig. 29 
    shows RELAY 1.
    NOTE: For MOD 1 and 2, THROT RNG replaces 
    DIFFRNTL.
    NOTE: The Setback parameter displays only if 
    scheduling is enabled (See Fig. 57 on 
    page 24) or the DI Option is set to Setback. 
    (See Fig. 60 on page 26).
    Continue with “1.2.1. SETPOINT”.
    Fig. 30. Program - Setpoint.
    1.2.1. SETPOINT
    1.From the menu, use the  and  buttons to 
    highlight SETPOINT.
    2.Press the 
     button to display the setpoint value.
    3.Use the  and  buttons to increase/decrease 
    the desired setpoint temperature.
    Default: 70° F (21° C)
    Range: -40° to 248° F (-40° to 120° C)
    4.Press the 
     button to accept the setpoint 
    temperature and display the next option.
    Fig. 31. Program - Differential or Throttling Range.
    1.2.2. DIFFERENTIAL or THROTTLING 
    RANGE
    Differential is used for Relay outputs and Throttling Range 
    is used for Modulating outputs.
    1.From the menu, use the
      and  buttons to 
    highlight THROT RNG or DIFFERNTL.
    2.Press the 
     button to display the throttling range 
    value.
    3.Use the
      and  buttons to increase/decrease 
    the desired value. 
    Default: 20° F (-7° C)
    Range: 1° to 300° F (1° to 149° C).
    4.Press the 
     button to accept the value and display 
    the next option.
    In heating mode, the Differential is below the setpoint. The 
    relay de-energizes when the temperature rises to the 
    setpoint. As the temperature drops to the setpoint minus 
    the Differential, the relay energizes.
    In cooling mode, the Differential is above the setpoint. The 
    relay de-energizes when the temperature falls to the 
    setpoint. As the temperature rises to the setpoint plus the 
    Differential, the relay energizes.
    The Throttling Range brackets the setpoint setting, e.g., if 
    the setpoint is 72°F (22° C) and the throttling range is 
    10° F (-12° C), then the effective throttling temperature 
    range is 67° to 77° F (19° to 25° C). This applies to both 
    modulating outputs and floating outputs.
    PROGRAM
               RELAY 1MENU
    PROGRAM
    RELAY 1
    SETPOINT
    DIFFRNTL
    SENSOR
    HEAT/COOL
    SETBACK
    EXIT
    M24493
    ENTER
    SETPOINT
    FOR 
    RELAY 1
    PROGRAM
    RELAY 1
    SETPOINTMENU
    PROGRAM
    RELAY 1
    SETPOINT
    70F o 
    M24494
    ENTER
    DIFFERENTIAL
    FOR 
    RELAY 1
    PROGRAM
    RELAY 1
    DIFFRNTLMENU
    PROGRAM
    RELAY 1
    DIFFRNTL
    20F o 
    M24495 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—1316
    Fig. 32. Program - Sensor.
    1.2.3. SENSOR
    1.From the menu, use the  and  buttons to 
    highlight SENSOR.
    2.Press the 
     button to display the sensor selec-
    tions.
    3.Use the
      and  buttons to select Sensor A or 
    B.
    4.Press the 
     button to accept the highlighted sen-
    sor and display the next option.
    Fig. 33. Program - Heat/Cool.
    1.2.4. HEAT/COOL
    1.From the menu, use the  and  buttons to 
    highlight HEAT/COOL.
    Default: HEAT
    2.Press the 
     button to display the heat and cool 
    selections.
    3.Use the
      and  buttons to select Heat or Cool.
    4.Press the  button to accept the highlighted 
    selection and display the next option.
    Fig. 34. Program - Setback.
    1.2.5. SETBACK
    The Setback temperature option displays if scheduling is 
    enabled (See Fig. 57 on page 24) or the DI Option is set 
    to Setback. (See Fig. 60 on page 26).
    This is the desired setpoint temperature that you want to 
    use during setback mode for this output. For example, if 
    your setpoint is 70° F (21° C) and you want the 
    temperature to drop 10° F during setback mode, enter 
    60° F (16° C) as the setpoint for this output.
    1.From the menu, use the
      and  buttons to 
    highlight SETBACK.
    2.Use the
      and  buttons to increase/decrease 
    the desired setpoint temperature.
    Default: 60° F (16° C)
    Range: -40° to 248° F (-40° to 120° C)
    3.Press the 
     button to accept the value and display 
    the menu.
    1.2.6. Program Next Output (Mod or Relay)
    For the next output (Mod or Relay), select the desired 
    output from the Program menu (Refer to Fig. 28 on 
    page 14).
    Go to “1.2.1. SETPOINT” on page 15 to program the next 
    output.
    When you finish programming the outputs, continue with 
    “1.2.7. Exiting Program Mode” on page 17.
    MENU
    PROGRAM
    RELAY 1
    SENSOR
    SELECT
    SENSOR FOR
    RELAY 1
    SENSOR A
    SENSOR B
    PROGRAM
     RELAY 1
     SENSOR
    M24496
    PROGRAM
     RELAY 1
     HEAT/COOLMENU
    PROGRAM
    RELAY 1
    HEAT/COOL
    SELECT
    HEAT/COOL
    FOR 
    RELAY 1
    HEAT
    COOL
    M24497
    ENTER
    SETBACK
    SETPOINT 
    FOR RELAY 1
    PROGRAM
     RELAY 1
     SETBACKMENU
    PROGRAM
    RELAY 1
    SETBACK
    60F o 
    M24498 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    1762-0254—13
    Fig. 35. Program - Exit.
    1.2.7. Exiting Program Mode
    Press the HOME button to leave programming mode and 
    return to the home screen.
    This completes the programming procedure.
    2.SETUP (ADVANCED OPTIONS)
    Setup provides the ability to change the factory default 
    settings for the temperature sensors and outputs, to 
    enable/disable reset control, and to enable/disable 
    scheduling.
    NOTE: The controller interface is intuitive. You may 
    find that you do not need the following setup 
    instructions for the sensors and outputs. You 
    may want to use this procedure simply as a 
    reference to locate the particular option or 
    parameter of interest.
    NOTES:
    1. If you press the HOME button or there is no 
    keypad activity for four minutes, you exit 
    Setup mode and return to the home screen.
    2. If you press the MENU button, you exit Setup 
    mode and return to the menu.
    Setup Procedure
    The Setup process uses a hierarchical menu structure 
    that is easy to use. You press the  and  arrow buttons 
    to move forward and backward through the menus.
    NOTE: The menus can display only those relays that 
    are defined in Setup (see “2.3.2. NBR OF 
    RELAYS” on page 24). For example, if you 
    configure only two relays, then only two 
    relays display on the appropriate menus.Once in Setup mode, you use the — 
    • Left arrow button (
    ) to scroll backward through the 
    Setup menus
    • Right arrow button (
    ) to select the highlighted menu 
    item and display its content
    • Up and Down arrow buttons (
     and ) to scroll up 
    and down through a list of items or to increase or 
    decrease the value of a displayed setup parameter
    To change the controller’s sensors and output setup 
    parameters, perform the following procedures in the order 
    listed:
    1.Enter Setup mode — see “2.1. Entering Setup 
    Mode”
    2.Setup Sensors — see “2.2. Setting up the Sensors”
    3.Setup Outputs — see “2.3. Setting up the Outputs” 
    on page 21
    4.Exit Setup Mode — see “2.4. EXIT Setup Mode” on 
    page 30
    2.1. Entering Setup Mode
    To enter Setup mode, press and hold the MENU button for 
    five seconds to display the Setup menu. Refer to Fig. 27 
    on page 13.
    Fig. 36. Setup - Sensors Menu.
    2.2. Setting up the Sensors
    1.From the Setup menu, use the  and  buttons 
    to highlight SENSORS.
    2.Press the 
     button to display the Sensors menu.
    MENU
    PROGRAM
    MOD 1
    MOD 2
    RELAY 1
    RELAY 2
    RELAY 3
    RELAY 4
    EXIT
    M24499
     SETUP
     SENSORSSETUP
    SENSORS
    # SENSORS
    SENSOR A
    SENSOR B
    EXIT
    M24500 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—1318
    Fig. 37. Setup - Sensors - Number of Sensors.
    2.2.1. Number of SENSORS
    The value entered here determines the number of 
    sensors displayed on the home screen.
    1.From the Sensors menu, highlight # SENSORS 
    then press the 
     button to display the number of 
    sensors.
    2.Use the
      and  buttons to enter the number of 
    sensors (1 or 2).
    Default: 2
    3.Press the 
     button to accept the value and display 
    the SENSOR A selection.
    Fig. 38. Setup - Sensors - Sensor A Menu.
    2.2.2. SENSOR A
    1.From the Sensors menu, highlight SENSOR A.
    2.Press the  button to display the Sensor A 
    selections.
    Fig. 39. Setup - Sensors - Sensor A - Units.
    2.2.2.1. UNITS (° F or ° C)
    IMPORTANT
    This is a global change and affects the unit 
    values for all temperature parameters on all 
    displays.
    The UNITS screen displays only for Sensor A.
    1.From the Sensor A selections, use the
      and  buttons to highlight UNITS.
    2.Press the  button to display the temperature 
    units.
    3.Use the
      and  buttons to highlight F or C.
    Default: F (Fahrenheit)
    4.Press the 
     button to accept the units and return 
    to the Sensor A selections.
    Fig. 40. Setup - Sensors - Sensor A - Calibrate.
    2.2.2.2. CALIBRATE (the sensor)
    Ensure that the wire size calibration value is within the 
    limits. See “Temperature Sensor Calibration” on page 11.
    1.From the Sensor A selections, use the
      and  buttons to highlight CALIBRATE.
    2.Press the  button to display the calibration 
    degree value.
    3.Use the
      and  buttons to increase/decrease 
    the desired calibration degrees.
    Default: 0.0
    Range: +/-10° F (+/-6° C)
    4.Press the 
     button to accept the value and return 
    to the Sensor A selections.
    ENTER
    NUMBER OF 
    SENSORS
    SETUP
     SENSORS
     # SENSORSSETUP
    SENSORS
    # SENSORS
    2
    M24501
    SETUP
    SENSORS
    SENSOR ASETUP
    SENSORS
    SENSOR A
    UNITS
    CALIBRATE
    LABEL
    EXIT
    M24502
    SETUP
    SENSORS
     SENSOR A
       UNITSSETUP
    SENSORS
    SENSOR A
    UNITS
    SELECT
    UNITS FOR
    SENSOR A
    DEG F
    DEG C
    M24503
    SETUP
    SENSORS
     SENSOR A
       CALIBRATE
    ENTER
    VALUE TO
    CALIBRATE
    SENSOR A
    SETUP
    SENSORS
    SENSOR A
    CALIBRATE
    M24504
    0.0F o  
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    1962-0254—13
    Fig. 41. Setup - Sensors - Sensor A - Label.
    2.2.2.3. LABEL (the sensor input)
    For a sensor already labeled, the display positions to and 
    highlights that label.
    1.From the Sensor A selections, use the
      and  buttons to highlight LABEL.
    2.Press the  button to display the label list.
    3.Use the  and  buttons to scroll through list 
    and highlight the desired label.
    You may need to scroll up or down to view all 
    possible labels.
    4.Use the 
     button to accept the highlighted label 
    and exit the list.
    NOTE: The label names in list order are: Sensor, 
    Boiler, Outdoor, Duct, Dischrg, Chiller, Room, 
    Supply, Return, and Animals.
    Fig. 42. Setup - Sensors - Sensor A - Exit.
    2.2.2.4. Exit Sensor A Setup
    Press thebutton to exit Sensor A selections and return 
    to the Sensors menu.
    or
    Use the
      and  buttons to highlight EXIT and press 
    the  button.
    Fig. 43. Setup - Sensors - Sensor B Menu.
    2.2.3. SENSOR B
    For the T775M2030 and T775M2048 models only, which 
    have a High/Low modulating temperature limit, the LIMIT 
    item displays on the Sensor B menu.
    1.From the Sensors menu, use the
      button to 
    highlight SENSOR B.
    2.Press the  
     button to display the Sensor B menu.
    2.2.3.1. CALIBRATE
    Setting the calibration value is accomplished the same 
    way as the Sensor A. See “2.2.2.2. CALIBRATE (the 
    sensor)” on page 18.
    2.2.3.2. LABEL
    Setting the label is accomplished the same way as the 
    Sensor A. See “2.2.2.3. LABEL (the sensor input)” on 
    page 19.
    SETUP
    SENSORS
     SENSOR  A
       LABELSETUP
    SENSORS
    SENSOR  A
    LABEL
    SELECT
    LABEL FOR
    SENSOR  A SENSOR  A
    BOILER A
    OUTDOOR A
    DUCT A
    DISCHRG A
    CHILLER A
    ROOM A
    M24505
    SETUP
    SENSORS
    SENSOR A
    UNITS
    CALIBRATE
    LABEL
    EXIT
    M24506
    SETUP
    SENSORSSETUP
    SENSORS
    # SENSORS
    SENSOR A
    SENSOR B
    EXITSETUP
    SENSORS
    SENSOR B
    CALIBRATE
    LABEL
    LIMIT
    EXIT
    M24507 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—1320
    Fig. 44. Setup - Sensors - Sensor B - Limit.
    2.2.4. LIMIT (Sensor B only)
    For the T775M2030 and T775M2048 models only, the 
    LIMIT item displays on the Sensor B menu.
    NOTE: The LIMIT option acts only on Modulating 
    Output 1.
    1.From the Sensors menu, use the
      button to 
    highlight SENSOR B.
    2.Press the  
     button to display the Sensor B menu.
    3.Use the  and  buttons to select the LIMIT 
    item.
    4.Use the 
     button to display the Limit selections.
    5.Use the  and  buttons to select the desired 
    limit, (Disable, Hi Limit, or Low Limit).
    Default: Disable
    6.Press the 
     button to accept the value and return 
    to the Sensor B menu.
    When you select Hi Limit or Low Limit, the Sensor B menu 
    changes and adds the Hi/Low Limit and Throttling Range 
    items. 
    If you are setting a Hi or Low Limit, continue with “2.2.4.1. 
    HI LIMIT or LOW LIMIT (Sensor B only)”. 
    If you selected Disable for the Limit value, continue with 
    “2.3. Setting up the Outputs” on page 21.
    Fig. 45. Setup - Sensors - Sensor B - Hi/Low Limit 
    (showing Hi Limit).
    2.2.4.1. HI LIMIT or LOW LIMIT (Sensor B 
    only)
    Fig. 45 shows the High Limit, but the process is the same 
    for setting the Low Limit. 
    Sensor B can be assigned a high/low limit, so that as you 
    are controlling temperature at Sensor A, the control 
    adjusts its modulating output to prevent exceeding the 
    user-entered limit for Sensor B. 
    1.From the Sensor B menu, use the
      button to 
    highlight HI LIMIT or LOW LIMIT.
    2.Press the  
     button display the LIMIT value.
    3.Use the  and  buttons to increase/decrease 
    the desired Limit value.
    4.Press the 
     button to accept the value and return 
    to the Limit menu.
    The high and low limit action will work in either the heat or 
    the cool mode as follows:
    • When the low limit is used in the heat mode, the MOD1 
    output increases to prevent reaching the low limit at 
    sensor B.
    • When the high limit is used in the heat mode, the 
    MOD1 output decreases to prevent reaching the hi 
    limit at sensor B.
    • When the low limit is used in the cool mode, the MOD1 
    output decreases to prevent reaching the low limit at 
    sensor B.
    • When the high limit is used in the cool mode, the 
    MOD1 output increases to prevent reaching hi limit at 
    sensor B.
    SETUP
    SENSORS
      SENSOR  B
       LIMITSETUP
    SENSORS
    SENSOR  B
    LIMIT
    SELECT
    HI/LOW
    LIMIT FOR
    SENSOR B
    DISABLE
    HI LIMIT
    LOW LIMIT
    M24508
    SETUP
    SENSORS
    SENSOR B
    UNITS
    CALIBRATE
    LABEL
    LIMIT
    HI LIMIT
    THROT RNG
    EXIT
    SETUP
    SENSORS
     SENSOR  B
    ENTER
    VALUE FOR
    SENSOR B
    HI LIMITSETUP
    SENSORS
    SENSOR B
    HI LIM
    90F o 
    M24509 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell T775abm Manual