    8.  MAINTENANCE 
    8 - 5 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    0011 AOH Amplifier 
    OverheatPossible• Overheat was detected in Amplifier. 
    • Overheat was detected in regenerative 
    resistor of Amplifier. 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
     
    Operating state when alarm occurred 
    POSSIBLE CAUSES   OPERATING STATE 
    1  2 3 4 5 
    When control power supply is turned on △ 
     ○ △ 
     
    During operation △ ○ ○ ○ 
     
    After emergency stoppage         ○ 
     
    Corrective Measures 
     CAUSES   CORRECTIVE MEASURES 
    1  Faulty internal circuit of Servo Amplifier  Replace amplifier. 
    2  Regenerative power is too large • Review operational conditions 
    • Use external regenerative resistor 
    3  Although regenerative power is within 
    specification, ambient temperature of Servo 
    Amplifier is too high.   Review cooling method so that temperature in 
    control board not become over 131°F (55℃). 
    4  Although regenerative power is within 
    specification, cooling fun in Servo Amplifier 
    stops. • Check if cooling fan in amplifier is rotating. Replace 
    amplifier if fan is not operating. 
    5  Regenerative power when emergency 
    stoppage was too large. • Replace Amplifier 
    • Review load condition 
     
    After overheat was detected, thermal SW in regenerative resistor will not recover to normal 
    operation without cooling down period for a while.  
    						
    							 
    8.  MAINTENANCE 
    8 - 6 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    0101 OV Over 
    voltage Possible DC voltage of main circuit of amplifier 
    exceeded allowable voltage 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
     
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 4 5 6 
    When control power supply is turned on ○ 
         
    When main circuit power supply is turned on ○ ○ 
        
    When motor is started or stopped     △ ○ ○ ○ ○ 
     
    Corrective Measures 
     CAUSES  CORRECTIVE MEASURES 
    1  Faulty amplifier control board    Replace servo amplifier. 
    2  Power voltage of main circuit is exceeding 
    allowable voltage Reduce voltage to within allowable range. 
    3  Load inertia is too high  Reduce load inertia to within allowable range. 
    4  Subject to not connecting regenerative resistor:
    • Operational pattern requires regenerative 
    resistor. • Review operational pattern and load inertia, change 
    to operational pattern not requiring regenerative 
    resistor. 
    • Install external regenerative resistor 
    5  Subject to using built-in regenerative resistor: 
    • Faulty wiring of connector CND, or 
    • Regenerative circuit is faulty • Wiring built-in regenerative resistor correctly: 
    [15A/30A] Connect built-in regenerative resistor 
    wires to P and Y terminals of connector 
    CND. 
    [50A]          Short circuit between P- X terminals of 
    connector CND. 
    Replace Servo Amplifier if malfunction persists.   
    6  Subject to using external regenerative 
    resistor: 
    • Regenerative resistor is not connected 
    • Regenerative resistor is broken 
    • Regenerative circuit is faulty Turn power OFF, check wiring and resistance value 
    of regenerative resistor.   
    Replace amplifier if malfunction persists.   
     
     
      
    						
    							 
    8.  MAINTENANCE 
    8 - 7 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    0110 OS Over 
    speed Possible Rotating speed of servomotor exceeded 
    allowable speed (1.2 times maximum 
    rotating speed) during operation. 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
     
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1  2 3 4 5 
    When control power supply is turned on ○ △ 
       
    Upon command input after Servo ON   △ ○ 
      ○ 
    When motor is started     ○ ○ 
     
    During operation (except when motor is started)   ○ ○ 
      
     
    Corrective Measures 
     CAUSES  CORRECTIVE MEASURES 
    1  Faulty amplifier control board    Replace servo amplifier. 
    2  Faulty servomotor sensor Replace servomotor 
    3  Overshoot is too large during motor start.  Use the analog monitor of the remote controller to 
    check the velocity. 
    →  If over shoot is too large, adjust the servo 
    parameter 
    →  Change the acceleration/deceleration speed 
    pattern command 
    →  Reducing the load inertia. 
    4  Incorrect wiring of U, V, W phases between 
    amplifier and motor Check and correct wiring. 
     
      
    						
    							 
    8.  MAINTENANCE 
    8 - 8 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    0111 PE Control 
    power 
    supply 
    error  Possible Control power supply input voltage is 
    below specified range 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
     
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 
    When control power supply is turned on △ ○ 
     
    During operation △ 
     ○ 
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1  Faulty amplifier internal circuit    Replace servo amplifier. 
    2  Power supply input voltage is below specified 
    range Set voltage within specified range.   
    3  Fluctuation or momentary interruption of input 
    power voltage   Check power supply 
     
      
    						
    							 
    8.  MAINTENANCE 
    8 - 9 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 Abbreviation Alarm NameAlarm 
    Clear Contents 
    DE1 Encoder 
    disconnection
    (sensor error)Not 
    possibleDisconnection of sensor signal (A, B, C 
    or PS signal) line was detected 
    DE2 Serial 
    disconnection 
    (sensor error)Not 
    possibleDisconnection of sensor signal (PS 
    signal) line was detected 
    DE3 Encoder initial 
    error (sensor 
    error) Not 
    possibleInitial data of motor sensor can not be 
    read in.  1000 
    DE4 Serial 
    receiving stop 
    (sensor error)Not 
    possibleNo feedback of absolute position data 
    from absolute sensor 
      EXDE External 
    encoder 
    disconnectionPossible Disconnection of full close sensor 
    signal line was detected. 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
     
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 4 5 6 
    When control power supply is turned on ○ ○ ○ ○ ○ ○ 
    After servo ON       ○ ○ 
     
    During operation △ 
      ○ ○ 
     
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1 Encoder wiring: 
    • Incorrect wiring 
    • Loose connector 
    • Poor connector contact 
    • Encoder cable is too long 
    • Encoder cable is too thin • Check and correct wiring. 
    • Check if sensor power voltage of motor is over 
    4.75V.  Correct if necessary. 
    2  Wrong sensor classification setting of 
    amplifier Correct setting. 
    3  Sensor classification setting differs from actual 
    sensor. Replace with servomotor attached with correct 
    sensor.  
    4  Faulty amplifier control circuit  Replace servo amplifier. 
    5  Faulty servomotor sensor  Replace servomotor. 
    6  Parameter setting is for full close servo 
    system. Set parameters for semi-close system 
    (Mode2-page0 Func0-bit7). 
     
      
    						
    							 
    8.  MAINTENANCE 
    8 - 10 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    1001 MPE Main 
    power 
    supply 
    drop Possible Main circuit power supply voltage drop 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
      
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 4 5 
    When control power supply is turned on       ○ △ 
    After main circuit power supply is turned on ○ ○ 
       
    During motor operation (alarm can be reset)   △ ○ 
      
    During motor operation (alarm can not be reset)     ○ 
       
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1  Power supply voltage is below specified rangeSet power supply to within specified range. 
    2  Main circuit rectifier is broken  Replace servo amplifier. 
    3  Input voltage dropped.    Or momentary 
    interruption occurred. Check main power supply not to occur momentary 
    interruption or power drop.   
    4  Low voltage of out of specification is supplying 
    to main circuit (R.S.T) Check main circuit voltage not to supply around 
    power from other to R. S. T when main circuit OFF. 
    5  Faulty internal circuit of servo amplifier  Replace servo amplifier 
     
      
    						
    							 
    8.  MAINTENANCE 
    8 - 11 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    1010 FP Main 
    power 
    supply 
    phase 
    loss Possible Phase loss detected in 3-phase main 
    power supply input 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
      
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 
    When control power supply is turned on   ○ 
     
    When main power supply is turned on ○ 
     ○ 
    During motor operation △ 
      
    Alarm occurred although specified single phase 
    power input   ○ 
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1  Faulty input contact on one of the R, S, T 
    phases Check and correct wiring. 
    2  Faulty amplifier internal circuit    Replace servo amplifier 
    3  Servo amplifier is not specified for single 
    phase • Confirm model number and delivery specification of 
    servo amplifier.    Replace with amplifier for single 
    phase, if necessary. 
    • Change parameter for single phase Amplifier 
    (Mode4-page8 PSKD) 
     
      
    						
    							 
    8.  MAINTENANCE 
    8 - 12 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    1100 SE Velocity 
    control 
    error Possible Velocity control is not functioning normally 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
     
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 4 5 
    When control power supply is turned on         ○ 
    Upon servo ON input ○ 
     ○ 
      
    Upon command input ○ ○ ○ 
      
    When motor is started or stopped       ○ 
     
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1  Incorrect wiring of U, V, W phases between 
    amplifier and motor Check and correct wiring. 
    2  Incorrect wiring of A, B phases between 
    INC-E and ABS-E encoder connection Check and correct wiring. 
    3  Motor is vibrating (oscillating)  Adjust servo parameter to stop vibration (oscillation).
    4  Overshoot and/or undershoot is too large  Use the analog monitor of the remote controller to 
    check the velocity   
    • Adjust servo parameter to reduce overshoot and/or 
    undershoot. 
    • Increase acceleration/deceleration command time.   
    Or, mask the alarm by setting Func2 of remote 
    controller.  
    4  Faulty servo amplifier control circuit  Replace servo amplifier. 
     
     
     
    Velocity control error alarm is set to “not detecting” as standard, but can be change to 
    “detecting” by setting bit5 of Func2 to “0” when necessary. 
     
    This alarm may be detected during motor start or stop in cases where load inertia is high or 
    for applications with G-force axis.    In these cases, set bit5 of Func2 to “1” for “not detecting”. 
    						
    							 
    8.  MAINTENANCE 
    8 - 13 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    1101 OVF Excess 
    position 
    deviationPossible Position loop deviation counter exceeded 
    allowable value 
     
    Operating State when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    12345678 9 10 111213
    When control power supply is turned on           ○ 
       
    During stoppage at servo ON             ○
        ○
      
    When command input is started   ○△○○○
     ○△ ○ 
     △
      
    During high speed start or stoppage ○○
        ○○ ○ 
     △○
     
    During operation with a long command   ○
        ○△ 
      △
      
    After JOG/ Tune              ○
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1  Position command frequency is too high, or 
    acceleration/deceleration time is too short. Review controller position command. 
    2  Load inertia is too high or motor capacity is 
    too low Review load conditions, or change to larger capacity 
    motor. 
    3  Holding break is not released  Check and correct wiring. Replace servomotor if 
    wiring is correct (and voltage is applied as specified), 
    4  Motor is mechanically locked, or there is 
    mechanical interference Review mechanics 
    5  One or all of the U, V, W phases between 
    amplifier and motor is disconnected. Check and correct wiring. 
    6  Motor rotation caused by external force 
    (gravity, etc.) during stoppage (completion of 
    positioning). Review load or change to larger capacity motor. 
    7 • Current limiter is activated by command from 
    controller, with limit value set too low. 
    • Set encoder pulse number does not match 
    motors. • Increase limit value or switch off current limiter. 
    • Change to the encoder pulse number of motor 
    8  Improper servo parameter setting (position 
    loop gain, etc.) Revise parameter setting (increase position loop gain, 
    etc.). 
    9  Excess deviation setting is too low    Increase excess deviation value from controller. 
    10  Faulty amplifier control board  Replace servo amplifier. 
    11  Faulty servomotor sensor  Replace servomotor. 
    12  Power supply voltage drops  Check power supply voltage again. 
    13  Normal and no problem This is in considering to deviation left at controller after 
    JOG operation or tuning from remote controller.    Clear 
    alarm to recover, or stop alarm by setting MODE2/ 
    page7/ bit4 to “1” with remote controller to stop alarm.
      
    						
    							 
    8.  MAINTENANCE 
    8 - 14 
    Alarm Status 
    Segment LED 
    Display Alarm Code 
    ALM8,4,2,1 AbbreviationAlarm 
    NameAlarm 
    Clear Contents 
     
    0011 EXOH External 
    overheat
     Possible External overheat was detected. 
    Alarm code 0,1 indicates: when Func2/ bit7,6 =”0,0”, “0”= output open and “1”= output short. 
      
    Operating state when alarm occurred 
    POSSIBLE CAUSES OPERATING STATE 
    1 2 3 4 
    When control power supply is turned on ○ ○ 
     △ 
    After operating for a short period     ○ △ 
     
    Corrective Measures 
     CAUSE  CORRECTIVE MEASURES 
    1  Although the system is of not connecting 
    external thermal, Amplifier sets to external 
    overheat detection valid. Change parameter setting to external overheat 
    detection invalid (Mode2-Page4 Func3-bit4,5) 
    2  In case of system connecting external 
    thermal, wiring is disconnected. Check and correct wiring. 
    3  External thermal terminal (external 
    regenerative resistor) operated.   • Review operational conditions. 
    • Increase capacity of external regenerative resistor 
    4  Faulty servo amplifier control board  Replace servo amplifier 
      
    						