Home > Honeywell > Alarm system > Honeywell Notifier Nfs28 Manual

Honeywell Notifier Nfs28 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Notifier Nfs28 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							997-492-000-6, Issue 6
    July 201124
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    No indication on panel - buzzer
    not sounding
    Panel in Fire state.No power to panel. Check mains suppl
    y;
    Check total battery voltage is
    >21V.
    Check mains supply to panel;
    Check battery connections
    Carry out visual check;
    if problems persist replace
    units/batteries until fault clears.
    Indication Action
    Possible Cause
    Common Fault Indication plus:
    AC mains failed - panel operating on
    batteries;
    Batteries - poor connection/
    disconnection;
    Batterycharger fuse blown;
    Batteries reversed;
    Batteries - deep discharge state
    (mains supply on).
    Auxiliary output - short circuit or
    overload Incorrect EOL device.
    Sounder circuit fault - open or short
    circuit.
    Zone circuit fault - open or short
    circuit.
    Zone circuit fault - partial open or
    short circuit; excess capacitance/
    cable length; dual or no EOL device;
    incorrect configuration of EOL. Check cables. Change EOL configuration t
    ype.
    Change EOL device(s)
    Carry out visual check.
    Carry out visual check.
    Reset system. If unable to
    reset or problem re-occurs -
    replace panel.
    Carry
    out visual check.
    Carry
    out visual check.
    Power Supply
    Fault indication
    plus intermittent buzzer.
    Auxiliary Fault indication plus
    intermittent buzzer.
    Sounder Fault/ Disabled flashing
    plus intermittent buzzer.
    Zone Fault/ Disabled/ Test
    flashing plus intermittent buzzer.
    Earth Fault indication plus
    intermittent buzzer.
    S ystem Fault indication plus
    continuous buzzer.
    S ystem Fault indication plus
    Common Fault indication plus
    intermittent buzzer.
    Zone Fault/ Disable/ Test plus
    Disablement stead yindications.
    Zone Fault/ Disable/ Test plus
    Test stead yindications.
    External sounders operating, no
    buzzer activation.
    Unable to reset. Go into Test/ Disable Options
    and re-enable zone.
    Go into Test/ Disable Options
    and take zone out of Test mode.
    Remove input.
    Turn key
    (cover on only );
    check cause of alarm - ensure
    broken glass replaced/ smoke
    cleared, etc.
    Processor failed.
    Expansion PCB(s) missing or
    disconnected..
    Relevant zone disabled.
    Relevant zone in Test mode.
    Class Change input operated.
    Key
    in Access Level 1 position
    (cover on onl y);
    Alarm condition stills exist. Unwanted connection of external
    cabling to earth.
    System Fault indication plus
    intermittent buzzer. Expansion PCB(s) missing or
    disconnected. Re-fit / re-connect Expansion
    PCB(s).
    Re-fit / re-connect Expansion
    PCB(s).
    6.10 Fault Finding Chart
    Use this chart to identify the cause of possible problems
    when commissioning your system. 
    						
    							997-492-000-6, Issue 6July 2011
    25
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    7 Configuration
    Access Level 3 allows input, output and control functions
    to be configured.
    The following sections describe how to configure the
    panel. Each procedure requires the panel status to be
    at access Level 3. The state of the configurable options
    is indicated by the panel LEDs.
    The table at left shows the functions of each pushbutton
    at access Level 1/ 2 and Level 3.
    The Configuration menus are as follows:
    1 Miscellaneous: Panel Options; System
    2 Zones: either 1- 2, 1- 4 or 1- 8
    3 Output circuits: 1- 4*
    4 Digital Inputs: 1 and/ or 2
    5 Delays: first stage; second stage.
    *Each output can be configured as a monitored or volt-
    free relay output. Output circuits 3 and 4 can be provided
    using the optional 2-way Relay PCB (kit PN: 020-713).
    Manual Zones
    The odd-numbered zones are configured as manual,
    i.e. MCP-only, zones. Manual zones can be changed so
    they can form part of a day-time delay strategy.
    7.1 Entering Access Level 3
    To enter access Level 3: hold down the  pushbutton
    and press the following pushbuttons in the order given -
    ,  and .  Rapid flashing of the FIRE LED
    confirms that the panel is at  access Level 3. You can
    now access the  configuration options in any order.
    The Level 3 function of each pushbutton is indicated
    using an icon within brackets immediately above each
    pushbutton.
    Press the following pushbuttons to select menu options:
      - Panel/ System Options
      - Zone Input/ EOL Type
      - Output Type/ Delay
      - Digital Inputs
      - Delays.
    Press 
     to cycle through the sub-menu. Press  at
    anytime to return to the Top Level menu.
    See the configuration map on the back cover of this
    manual for a quick reference guide.
    ISO 7240-2 : 14.5.3e), f) Installers must make a
    record of the configuration
    details of the panel and store the information at access level 3.
    ISO 7240!ISO7240
    !
    A copy of the configuration map (see the
    back page) marked up and dated would
    make a suitable record.  Any change of
    configuration will require a new
    configuration record. 
    						
    							997-492-000-6, Issue 6
    July 201126
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    7.2 Panel Options - A
    Four user-configurable panel options are available:
    a. Enable/Disable Engineering Mute
    b. Enable/Disable Commissioning Mode
    c. ACCEPT pushbutton access level
    d. LAMP TEST pushbutton access level.
    e. Delay Lights DISABLEMENT LED
    7.2.1 Engineering Mute
    The operation of the panel’s buzzer can be changed so that it
    operates only occasionally with a Fire state, fault condition or
    during any active configured first stage delays. This can be
    selected independently of Commissioning Mode.
    The default is Engineering Mute disabled.
    7.2.2 Commissioning Mode
    The panel can be put in Commissioning Mode to assist
    the commissioning process.
    In this mode, most faults are indicated after 4 secs instead
    of the normal 20 secs delay to aid fault finding.
    Commissioning Mode times-out automatically 60 secs after
    the cover is replaced. Selection of commissioning Mode
    automatically selects the Engineering Mute function.
    7.2.3 ACCEPT Pushbutton Access Level
    The ACCEPT pushbutton can be configured to operate  at
    access Level 1 or 2. The default operation is access Level 2.
    7.2.4 LAMP TEST Access Level
    The LAMP TEST pushbutton can be configured to operate  at
    access Level 1 or 2. The default operation is access Level 2.
    7.2.5 Delay Lights DISABLEMENT LED
    EN 54-2 and ISO 7240 Annex E acknowledges that delays
    may be permanently configured in the normal mode of
    operation of the equipment, (e.g. day mode) and in such
    cases there is no need for a disablement indication. Use
    this option when the DISABLEMENT LED 
    is required to
    indicate any configured delays.
    7.3 Panel Options - B
    The following options are selectable:
    a. Non-latched faults
    b. Pulse Fire Routing outputs
    c. FBF Fire Routing disable - forces off
    d. Re-sound - new zone in alarm
    e. Mains fault delay.
    7.3.1 Non-latched Faults
    When enabled, this option allows faults and fault indications
    to clear automatically. The buzzer can still be silenced while
    a fault is shown on the panel (it will resound if the fault
    reoccurs). By default the option is disabled and fault
    indications require manual intervention to clear.
    EN 54-2 & ISO 7240-2: Annex E Does not require delay
    indicated as a disablement. 
    						
    							997-492-000-6, Issue 6July 2011
    27
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    Non-latching only affects the following fault conditions:
    a. Zone Faults
    b. Earth Fault
    c. Power Supply Fault
    d. Sounder Fault
    e. Fire Output Fault
    f. Fault Output Fault
    g. Auxiliary Supply Fault.
    Note:System Fault remains latching at all times.
    7.3.2 Pulse Fire Routing Outputs
    When this option is selected the fire routing ouput is
    activated for a period of 5 secs only (pulsed). Continuous
    activation of the routing output is the default.
    7.3.3 FBF Fire Routing Disable - Forces Off
    VdS requirement only.
    7.3.4 Re-sound - New Zone in Alarm
    By default, after the panel has received a fire event and
    the sounders have been silenced using the SOUNDERS
    START/STOP pushbutton, a new fire event, but in
    another zone, will activate the sounder outputs again.
    This option allows the configuration of sounder outputs
    to ignore any new zones in fire after the sounders have
    been silenced.
    7.3.5 Mains Fault Delay
    By default, a mains fault is indicated within 10 seconds.
    This option allows the delay to be extended to 30, 60 or
    90 minutes. The 60 minute and 90 minute options do
    not comply with EN 54 (see information at left).
    Note:The Non-latched faults and Mains fault delay
    options can be used together. For example, if the
    delay is set to 30 minutes then the fault is indicated
    after this time. The indication is removed
    automatically 10  seconds after the fault is cleared.
    7.4 System Options
    The following options are selectable:
    a. Clear Checksum
    b. Select Default Configuration
    7.4.1 Clear Checksum
    Use this selection to clear user configuration checksum
    faults.
    7.4.2 Select Default Configuration
    This enables the panel to be returned to the factory-
    configured state. When System LED 2 is lit the panel is
    in the factory-configured state.
    EN 54-4: 5.4
    A mains fault MUST
    be indicated within 30 minutes.
    ISO 7240-4 : 5.4
    A mains fault MUST be indicated within 100 seconds.
    ISO 7240 !ISO7240
    ! 
    						
    							997-492-000-6, Issue 6
    July 201128
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    7.5 Fire Zone Input Type
    Fire input zones can be configured as follows:
    a. Latching/non-latching alarms
    b. Alarm or for short-circuit operation
    c. Auto or manual operation mode
    d. Coincident-alarm or separate-alarm detection
    e. Setting a Sprinkler Verification Time.
    f. EOL Device Type.
    7.5.1 Latching/Non-latching Alarms
    A detection zone can be configured as latching or non-
    latching. When selected as latching, if the panel enters
    the fire (or fault) state this condition will remain active
    until the panel is reset. When selected as non-latching,
    the panel state returns to normal once the input condition
    has been cleared. The default is latching.
    7.5.2 Alarm or Short-circuit Operation
    The panel can be configured to respond to a short-circuit
    input on a zone as a fire or fault condition. The default is
    fault indication.
    Caution: You 
    will contravene the requirements of EN 54-2
    if you configure short-circuit as a fire
    condition. For guidance, refer to appropriate
    local fire standards.
    7.5.3 Auto/ Manual Zones
    The panel has the following factory-configured default:
    a. Odd-numbered zones - manual zone, i.e. no delay to activation of outputs, used with MCPs. Manual zones
    will always cause immediate entry into the Fire state.
    b. Even-numbered zones - auto. detection, i.e. if configured for day-time delay strategy, outputs will
    be delayed as per the delay strategy.
    Note: If no delay strategy is being used (default panel
    setting) this operation has no effect.
    Any zone can be configured as manual or auto action.
    7.5.4 Coincidence Detection
    The panel will, by default, indicate a fire condition when
    a single device on a single zone goes into alarm.
    The panel can be configured so that to enter a full fire
    condition, two zones must be in the fire state. Coincidence
    detection is only supported for pairs of zones, i.e. zone 1
    concident with 2, zone 3 coincident with 4, etc. When
    configured, upon the first zone going into fire the respective
    zonal fire indicator illuminates, the panel enters the alert
    state but the general fire LED does not light.
    Note:  Zone pairs set for coincidence detection are forced
    to function as auto zones.
    On the second fire alarm zone the standard fire sequence
    will be followed for both input zones.
    EN 54-2 : 8.2.4a) &
    ISO 7240-2 : 9.2.4a)
    The panel must indicate a fault condition for a short circuit.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240
    EN 54-2: & ISO 7240-2: 7.6
    1. Configuring a local
    detection zone as non-
    latching contravenes the
    requirements of EN54 and ISO 7240.
    2. Reset from an alarm state must be a manual operation at access Level 2.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240 
    						
    							997-492-000-6, Issue 6July 2011
    29
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    7.5.5 Sprinkler Verification Time
    A 2 sec. verification time is applied to all inputs to reduce
    the occurrence of false indications of alarm due to transient
    phenomena. 
    When monitoring an input from a sprinkler
    system it may be necessary to configure a sprinkler
    verification delay. This is an exceptional situation and will
    require the approval of a fire officer.
    7.5.6 EOL Device Type
    Use this option to change the default EOL device type
    from a capacitor to a resistor when the panel is used for
    retrofit installations.
    Note: Failure to do this on retrofit installations may cause
    the panel to enter the Fire state, with consequent
    operation of the sounders.
    7.6 Sounder Output Type/ Delay
    The two sounder circuits and two optional relay circuits,
    if fitted, are each configurable as one of the following:
    a. Sounder output
    b. Fire routing output
    c. Fault output.
    d. Local Alarm  Output.
    Up to two optional, 8-way Relay PCB(s) can be fitted.
    Each PCB can be independently configured to provide
    one of the following functions:
    e. Repeat Zonal Output
    f. Coincident Zonal Output
    g. Repeat Zonal Output (zones 1-4) and Shop Interface
    Outputs
    h. Inputs and Shop Interface Outputs.
    Up to two optional, 4-way Sounder PCB(s) can be fitted.
    Each PCB can be independently configured to provide
    monitored sounder, fire or fault routing output.
    EN 54 and ISO 7240-2  and local installation guidelines
    impose requirements on the application of outputs.
    Please consider the following when configuring the
    different output types available on this CIE:
    i One output on the panel must be configured as a fire output, (EN 54-2 & ISO 7240-2: 7.7.1).
    This may be an unmonitored relay output.
    ii One output on the panel must be configured as a fault output. (EN 54-2: 8.8 and ISO 7240-2: 9.8).
    This may be an unmonitored relay output.
    iii If an EN 54-2 or ISO 7240-2, 7.8 monitored sounder output is required an unmonitored relay is not suitable,
    use a monitored sounder output (either PSU PCB or
    4-way sounder output PCB).
    iv If an EN 54-2 or ISO 7240-2, 7.9 monitored fire alarm routing output is required an unmonitored relay is not
    suitable, use a monitored sounder output (either PSU
    PCB or 4-way sounder output PCB).
    v) If an EN54-2 or ISO 7240-2, 7.10 monitored fire protection output is required use the optional 4-way
    EN 54-2: & ISO 7240-2: 7.1.3
    The panel must respond to an input within 10 secs.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240
    EN 54-2: 8.8 &
    ISO 7240-2: 9.8
    One output on the panel
    must be configured as a fault output.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240
    EN 54-2: &
    ISO 7240-2 7.7.1
    One output on the panel must be configured as a fire output.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240 
    						
    							997-492-000-6, Issue 6
    July 201130
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    sounder output PCB, NFS-SST(English PN: 020-769-
    001) or NFS8V-SST (German PN: 020-769) Display
    Boxes and Routing Termination kit (020-773).
    vi If an EN 54-2 or ISO 7240-2, 8.9 monitored fault routing output is required both relay and PSU PCB sounder
    outputs are unmonitored in this mode. For this
    application use the optional 4-way sounder output PCB.
    vii Note: PSU PCB sounder circuits do not comply with EN 54-13 partial-open-, partial-short-circuit
    requirements. For this application use the optional 4-
    way sounder output PCB.
    7.6.1 Select Output
    Select Sounder 1, Sounder 2, or if the 2-way Relay PCB
    is fitted, Relay 1 or Relay 2. The default selection is
    Sounder 1. Press 
      to select another output.
    7.6.2 Select Type
    Having selected the appropriate output circuit now select
    one of the following: Sounder, Fire Routing Output, Fault
    output, Local Alarm Output or Pulsing Sounder Output.
    The default type for Sounder circuits 1 and 2 is Sounder.
    Press 
     to select an alternative type.
    Notes:
    1 The Local Alarm Output does not activate with non- latched zones (assumes non-latched zones are from
    external panels).
    2 The pulsing option will activate the selected sounder/relay outputs as follows: one second ON / one second OFF.
    7.6.3 Select Delay
    These outputs can be configured as part of a strategy to
    delay the operation of sounder and/ or fire routing outputs
    during daytime operation.
    Each sounder/ fire routing/ fault routing/ lo cal alarm output
    can be configured with a two-stage delay (see  Section 7.8
    Primary and Secondary Delays ). Once configured the
    DELAY ON/OFF pushbutton or a Digital Input  are used to
    enable the delay to outputs. This panel state is confirmed
    by the illumination of the DELAY ON  LED (default
    configuration). If required, the panel may also be
    configured to light the DISABLEMENT LED when the
    delay mode is active (refer to ‘Panel Options - A’ of the
    configuration menu located at the back of this manual).
    7.7 Digital Inputs
    Two digital input circuits are provided for connection to
    ancillary equipment, if required. Each circuit can be
    configured to provide one of the following input actions:
    a. Class change (default)
    b. Alert
    c. Evacuate
    d. Delay Mode (default)
    e. Reset
    f. Fire transmission confirmed return signal (latched or non-latched)
    Sounder output types
    ‘sounder’ and ‘pulsed’ must not be mixed on the same installation to avoidconfusion of the
    evacuation signal.
    EN 54-2 & ISO 7240-2 Level 2 Keyswitch
    access MUST be used with these inputs.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240
    EN 54-13:  5.3.4
    Installations designed to meet EN 54-13 require
    partial short and partial open fault warning. 
    						
    							997-492-000-6, Issue 6July 2011
    31
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    g. Fault transmission failed return signal.
    Class Change: When a class change digital input is
    activated, all outputs configured as sounders will be
    activated until the input condition is removed.
    Alert: When an alert digital input is activated, all outputs
    configured as sounders and the internal buzzer start pulsing.
    The sounders and internal buzzer remain pulsing until the
    digital input is deactivated. Alert operation will override class
    change and fault conditions, but not the alarm condition.
    Note:If the sounder output is configured as type ‘pulsed’
    then an alert input will cause the sounder outputs
    and internal buzzer to turn on with a steady tone.
    Evacuate: When an evacuate digital input is activated, a
    general evacuate is initiated, i.e. all the bells activate,
    until the input condition is removed.
    Note: If the sounder output is configured as type ‘pulsed’
    then an evacuate input will cause the sounder
    outputs and internal buzzer to pulse.
    Delay Mode: This allows external control of delays to
    outputs. It can be used to delay activation of outputs
    during the day and so this use is commonly known as
    Day Mode. When this input is active, delays can still be
    cancelled using the ‘Delays On/Off’ button.
    Reset: This digital input can be used to return the panel
    to normal operation after the occurrence of an event,
    such as an alarm or fault. Faults are latching and a reset
    cannot return the panel to normal until the condition
    causing the fault has been remedied.
    Fire Transmission confirmed return signal: This type of
    digital input provides the ability to confirm the activation
    of the Fire Routing Output. Selection of either a latched
    or non-latched activation signal is available.
    Fault Transmission failed return signal: This type of digital
    input provides the ability to route Fault Routing Output
    faults back to the panel. It is assumed that the external
    equipment will provide the necessary fault monitoring of
    the routing output and provide feedback to the panel.
    7.7.1 Select Input
    Select Digital Input circuit 1 or 2. The default selection is
    input 1. Press 
      push-button to select the other output.
    7.7.2 Set Type
    Digital input 1 is configured, by default, as a Delay Mode
    input. Digital input 2 is configured, by default, as a Class
    Change input. Press 
     push-button to select  another type. 
    						
    							997-492-000-6, Issue 6
    July 201132
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    7.8 Primary and Secondary Delays
    A day-time delay strategy can be implemented, if required,
    which comprises two user-configurable delay periods to
    allow a fire search to take place. These delay periods are
    referred to as primary and secondary. On an auto detection
    zone, every fire state places the panel in a full alarm, hold-
    off state until the indicated fire event has either:
    a. Been verified as true after the search and then
    manually-terminated (at the panel or by operating an
    MCP), or
    b. The primary delay period expires, thereby automatically operating the configured outputs (e.g. sounders).
    If the ACCEPT pushbutton is pressed during the primary
    delay period the delay to outputs is extended by the length
    of the configured secondary delay. The maximum total
    duration of a configured delay to outputs is 10 minutes,
    even if the sum of the configured primary and secondary
    delays exceeds this limit. Once the ten-minute delay period
    has expired the outputs will be activated automatically.
    7.8.1 Select Primary Delay Time
    Specify the first stage of the delay to outputs. The default
    is 30 secs. Press the 
      push-button to specify another
    primary delay period up to 120 secs in 30 sec increments.
    7.8.2 Delay toTransmission Device
    Activation of the transmission device output may be subject
    to  a delay. Press the 
      push-button to toggle the
    delayed/immediate action. The default condition is ‘delayed’.
    7.8.3 Select Secondary Delay Time
    Specify the second stage of the delay to outputs. The
    default is 1 minute. Press the  
      push-button to specify
    another secondary delay period up to 10 minutes in 1
    min increments.
    7.8.4 Two-zone Override Delay
    Delays to outputs are overridden when a second zone goes
    into fire. This default can be changed so that a second
    zone going into fire does not override an active delay. 
    						
    							997-492-000-6, Issue 6July 2011
    33
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    7.9 Configuration Examples
    The following examples are provided to offer guidance
    when navigating through some of the menu options.
    Note:
    If you lose your way at any time, simply press the ‘main
    menu’ pushbutton 
     to return to the menu select
    position.
    Example 1
    How do I configure the panel back to the factory default
    state?
    Ensuring that the panel is at access Level 3 (refer to
    earlier in this section). Use the icons in brackets (located
    above each pushbutton) when proceeding:
    Press the following pushbuttons in the order shown:
      - Selects Miscellaneous option
      - Press twice to s elect ‘System’  sub-item menu
     (hold for 5 seconds) -  System LED 2 lights to
    indicate the factory default condition has been restored.
    Press the 
     pushbutton to return to the top level and
    select another configuration menu option. To take the
    panel out of access level 3, press the 
     pushbutton.
    Note:  The panel remains at access Level 2 until the cover
    is relaced when access level is dependent on key
    position.
    Example 2
    How do I set  a delay of 1 min for sounder output circuit 2?
    With the panel at access level 3, press the following
    pushbuttons in the order shown:
     Selects Sounder Outputs option
      Use to select sounder circuit 2
     Use to select delay to output - LED 12 illuminates
    to confirm selection of sounder circuit delay.
    To enable the configured output delay for sounder circuit
    2, and with the panel at access Level 2, the 
    pushbutton  must be pressed and the DELAY ON and
    DISABLEMENT LEDs illuminate to confirm the panel has
    a delay to outputs configured.
    Press the 
     pushbutton to return to the top level and
    select another configuration menu option. To take the
    panel out of access level 3, press the 
     pushbutton. 
    						
    All Honeywell manuals Comments (3)

    Related Manuals for Honeywell Notifier Nfs28 Manual