    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    8 Specification
    General
    The Fire Control Panel meets the requirements of EN 54-2/
    4 and ISO 7240-2/4. See Section 1.4 CE Marking for further
    details.
    Mechanical:
    Construction:
    Fire-resistant, ABS plastic moulded front
    cover and back box. Cover contains all
    user interface controls and visual
    indicators.
    Dimensions (mm): 318(h) x 356(w) x 96(d)
    Approx. Weight: 2kg (no batteries)
    Environmental:
    Climatic classification: 3K5, (IEC 721-2-3)
    Operating temperature: - 5
    oC to +45oC, (recommended +5oC to
    35oC)
    Humidity: 5%  to 95% R.H.
    Height above sea level: Maximum, 2000m
    Panel sealing: IP 30, (EN 60529)
    Vibration: EN  60068-2-6, 10-150Hz at 0.981ms
    -2,
    0.1g
    n (Meets the requirements of
    EN 54-2/4)
    EMC: Emissions: EN 61000-6-3
    Immunity: EN 50130-4
    Safety: EN 60950
    Indicators and Controls:
    LED Status indicators: Alarm,  Zonal  Fire, Zonal Fault, Power,
    General Fault, General Disablement, Test,
    Delay On (active), System Fault, Earth
    Fault, Power Supply Fault, Sounder Fault/
    Disabled, Fire Routing Active, Fire
    Routing OutputFault/Disabled, Fault
    Output Fault/Disabled, Auxiliary Fault.
    Controls:
    Two-position keyswitch:
    Level 1 (key removed or in ‘remove’ position)
    Level 2 access (key turned 90° clockwise).
    Dedicated push-buttons are provided for the following functions: ACCEPT, SOUNDERS STOP/START,
    RESET, BUZZER MUTE, DELAY ON/
    OFF, ITEM SELECT, DISABLE/TEST/
    NORMAL, LAMP TEST.
    External Connections:
    Cable entry: 18 x 20mm knock-outs on top face ofback box. One 25mm x 50mm knock-
    out on rear wall of back box. 
    						
    							997-492-000-6, Issue 6July 2011
    35
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    Electrical:
    Classification: A combination of 
    Installation Class 1
    and Class 2 (panel must be earthed).
    Conductor size: Compatible with cable conductor
    sizes: 0.5mm
    2 to 2.5mm2 .
    Supply Rating:
    Mains supply to the panel is to be provided via an external,
    double-pole, mains-isolation unit. The supply rating is:
    230V~ (ac) ±15%, 50/ 60Hz, 1.6A.
    Power Supply Specification:
    Input Fuse rating: T 1.6A H 250V
    Output ratings:
    Output voltage: 18.5 - 28.5Vdc
    Output current: 1.8A (includes charger current - charger
    disabled during alarm)
    Ripple voltage: 200mV  (peak-to-peak)
    Output Ratings - Charger: Charger voltage: 27.3Vdc at 20°C (temperature-
    compensated at -3mV/°C/cell)
    Charger current: 0.4A
    EN54 Battery Wiring Test Impedance: 0.8 Ohm
    EN54-4 PSU Loadings: I
    max(a)= 350mA @ 27Vdc
    I
    max(b)= 1.8A @ 27Vdc
    Range of battery size charged to 80% in 24hrs: 2.8Ah - 7Ah
    Recommended Standby Battery Sizes: 24 hour standby period - 2.8, 3.3 or 7Ah
    72 hour standby period - 2.8, 3.3 or 7Ah.
    Note 1: Internal batteries - sealed lead-acid types are
    recommended. The following manufacturers/ type are
    recommended: Yuasa-NP, Fiamm FG and Jackyl.
    Note 2:  To ensure compatibility with the battery wiring test
    batteries are to be 2.8Ah or greater. However,
    smaller Ah sizes will be compatible if the
    manufacturer’s stated initial charged internal
    resistance per battery is less than 80mOhms.
    Note 3: The batteries should be replaced at intervals not
    exceeding four years. Their lifetime is dependent upon
    the ambient temperature; refer to manufacturer’s
    technical specification for guidance. 
    						
    							997-492-000-6, Issue 6
    July 201136
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    Outputs:
    Sounder Circuits:
    Two outputs configurable as sounder, fire routing output or
    fault output and each rated at 0.5A. The sounder and fire
    routing outputs are monitored.
    18.0 - 28.5Vdc, (24Vdc nominal) rated at 0.5A.
    Note: If the total alarm current (sounders + fire + Auxiliary output)
    exceeds a total load of 1A, you must check the total
    alarm load using the Battery Calculation in Section 9.
    Zone Circuits:
    Factory-supplied two, four or eight detector zones.
    The quantity of detectors per zone equals 2.0mA divided by
    the individual detector’s quiescent current rating - see
    manufacturer’s data sheets - e.g. for a detector quiescent
    rating of 75 μA; the quantity of detectors:
    = 2.0mA ÷ 75 μA  =  26 detectors.
    Auxiliary DC Output: 18.0V - 28.5Vdc (24Vdc nominal) rated at 0.5A
    Note: The length of any cables connected to the auxiliary
    output 
    must not exceed 30m.
    Optional 2-Way Relay PCB providing: A Fire Relay Output
    A Fault Relay
     Output
    Each relay is rated at 30Vdc, 1A.
    Note:  To comply with the requirements of EN 54-2: 8.8, if
    the 2-way Relay PCB is not fitted one of the sounder
    circuits must be configured as a fault output.
    Optional 8-Way Relay PCB providing up to 8 outputs per
    PCB (two PCBs may be fitted). Relay contact functions are
    configurable using jumper links to provide the following: Repeat Zonal Output or
    Coincident Zonal Output or
    Repeat Zonal Output (zones 1-4) and Shop Interface
    Outputs or
    Inputs and Shop Interface Outputs
    Max current (per PCB): Quiescent - 0.1mA
    Alarm/ all active - 80.1mA
    Each relay is rated at 30Vdc, 1A
    Fire resistor:  Nominal 470R ±5%
    Optional 4-way sounder PCB supporting four configurable
    monitored outputs and two configurable input circuits.
    Various preset combinations of input and output functions
    are selected via a DIP switch. By using the supplied end-of-
    line termination the 4-way sounder PCB is able to provide
    sounder, fire routing and fault routing outputs as required
    by EN 54-2 and ISO 7240-2. These outputs are all monitored
    for partial-short and partial-open circuit faults as required
    EN 54-2: &
    ISO 7240-2 7.7.1
    One output on the panel
    must be configured as a fire output.
    !
    EN54
    ISO 7240!
    EN54
    ISO
    7240
    EN 54-13 : 5.3.4.1, 5.3.4.2
    PSU PCB circuits do not comply with the
    requirement for  partial- open and -short circuit
    fault monitoring on fire
    alarm device, fire routing
    and fault routing outputs. 
    						
    							997-492-000-6, Issue 6July 2011
    37
    EN 54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    by EN 54-13. A fault of the 4-way sounder PCB is indicated
    by the Auxiliary fault indicator. The following output options
    are configurable:- Sounder output
    - ÜE transmission circuit
    - Fire protection output (SST)
    - Fire routing output
    - Fault routing output
    The following input options are configurable: - Fire transmission confirmed
    - Fault transmission confirmed
    - Class change
    - Day Mode
    Maximum ouput current (per PCB): For two or more ouputs (if DIP switch 6 set to >250mA): 1.5A
    For each output (if DIP switch 6 set to 
    						
    							997-492-000-6, Issue 6
    July 201138
    EN54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
    9 Battery Calculation
    The table in Section 6.4.1 Standby Batteries can be used
    to select the correct battery size. If full calculations are
    required use the procedure below.
    General Data
    PSU size Maximum Maximum Internal
    No. of sounder External Battery Size
    CircuitsAlarm LoadRange
      1.8A 2 1A 2.8 - 7Ah
    Standby Load (Amps)
    Standby Load in Amps No. Current Total
    Basic panel1 0.034 0.034
    Device quiescent current
    (max 2mA per zone)
    EOL Current (per zone) - 0.0056
    fitted with Resistor EOL
    Optional 4-way Sounder PCB(s) 0/ 1/ 20.047
    Auxiliary equipment *
    Total Standby Load (L1)
    Peak/ Alarm Load (Amps)
    Alarm Load in Amps Qty Current Total
    Basic panel1 0.034 0.034
    Zones alarm current 2/ 4/ 80.03
    Optional 2-way Relay PCB 0/ 1 0.04
    Optional 8-way Relay PCB(s) 0/ 1/ 2 0.08
    Sounder output 1
    Sounder output 2
    4-way Sounder PCB outputs **
    Auxiliary equipment *
    Total Alarm Current (L2)
    Total 
    						
    							New South Wales
    (Head Office)
    9 Columbia Way
    Baulkham Hills NSW
    2153
    ph +61 (0)2 9899-4155
    fax +61 (0)2 9899-4156New Zealand
    264 Mt Eden Rd
    Mt Eden
    1064
    ph +64 (0)9 623-5050
    fax +64 (0)9 623 5060 
    						
    All Honeywell manuals Comments (3)

    Related Manuals for Honeywell Notifier Nfs28 Manual