Home > Lucent Technologies > Communications System > Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual

Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 2397
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-71 Packet Bus Fault Isolation and Repair 
    5
    NOTE:
    The Tone/Clock circuit pack should be the next-to-last one checked. (The 
    TN771D must be reseated after the Tone/Clock is reinstalled.) Refer to 
    Procedure 3 for the TN768 or TN780 Tone/Clock circuit pack in a PPN with 
    duplicated SPEs.
    If the packet bus problem is present when the circuit pack is inserted, but is 
    resolved when the circuit pack is removed, either the circuit pack or the 
    backplane pins in that slot caused the problem. If the backplane pins are intact, 
    replace the circuit pack. Keep in mind that there may be more than one failure 
    cause.
    In Procedure 2, you may try one circuit pack at a time, or multiple circuit packs 
    simultaneously. The allowable level of service disruption should guide this 
    choice. If the entire port network can be disrupted, trying large groups of circuit 
    packs will save time. If traffic is heavy, trying 1 circuit pack at a time is slow but 
    will minimize outages.
    If the TN771D Standalone mode does 
    not indicate packet bus faults, perform 
    Procedure 2 for 
    only the port circuit packs (purple slots) listed in Table 5-3 in 
    Procedure 1. In this case, you need not check for problems with the backplane 
    pins. It is sufficient to determine whether the problem is resolved by removing 
    circuit packs.
    If you decide to remove multiple circuit packs, consider working with an entire 
    carrier at a time to more quickly and reliably determine which circuit packs are 
    not the source of trouble. Any circuit packs, (packet or non-packet), that have 
    been recently inserted should be checked first. Packet circuit packs should be 
    checked before non-packet circuit packs.
    1. Remove one or several circuit packs.
    2. Determine if the packet bus fault is still present. If not, go to step 4.
    3. If the packet bus fault is still present:
    a.Determine if the backplane pins in the removed circuit pack’s slot 
    are bent using the output from the Maintenance/Test standalone 
    mode and the backplane illustrations which appear earlier in this 
    discussion.
    b. If the backplane pins are bent:
    Power down the carrier (see ‘‘
    Replacing a BIU or Rectifier’’), 
    straighten or replace the pins, reinsert the circuit pack and restore 
    power. Repeat Step 2 for the same circuit pack.
    c. If the backplane pins are not bent:
    Reinsert the circuit pack(s), and repeat this procedure for the next 
    set of circuit packs. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-72 Packet Bus Fault Isolation and Repair 
    5
    4. If the packet bus fault is not present:
    a. Reinsert circuit packs one at a time and repeat the following 
    substeps until all circuit packs have been reinserted.
    b. Determine if the packet bus fault has returned.
    c. If the packet bus fault has returned, the reinserted circuit pack is 
    defective. Replace the circuit pack and then continue.
    d. If the packet bus fault does not return when all of the circuit packs 
    have been reinserted, you are finished.
    Continue with Procedure 3 if all the port circuit packs have been checked, but 
    the packet bus fault is still not resolved.
    Procedure 3
    Procedure 3 removes and reinserts SPE and EPN control circuit packs one at a 
    time. In the PPN, the following SPE circuit packs either use the packet bus or are 
    connected to it in the backplane wiring:
    nTN1655 Packet Interface
    nTN768/TN780 Tone/Clock 
    nUN332 MSSNET
    In the EPN, the following control circuit packs either use the packet bus for 
    communication or are connected to it in the backplane wiring:
    nTN775 EPN Maintenance Board 
    nTN768/TN780 Tone/Clock
    These are the only SPE and EPN control circuit packs that are likely to cause a 
    packet bus problem in a stable system. Perform this procedure on only these 
    circuit packs.
    If the TN771D Standalone mode does 
    not indicate packet bus faults, perform 
    Procedure 3 for 
    only the Packet Interface and Tone/Clock circuit packs and do 
    not check for problems with the backplane pins. Determining if the problem is 
    resolved by removing circuit packs is sufficient.
    For a system with simplex SPE:
    1. Power down the control carrier. Refer to ‘‘Replacing SPE Circuit Packs’’.
    2. Remove the suspect circuit pack.
    3. Determine if the backplane pins in the removed circuit pack’s slot are 
    bent.
    4. If the backplane pins are bent:
    a. Straighten or replace the pins. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-73 Packet Bus Fault Isolation and Repair 
    5
    b. Insert the same circuit pack.
    5. If the backplane pins are not bent:
    a. Replace the circuit pack (reinsert the old one if a replacement is not 
    available).
    6. Turn the power back and allow the system to reboot. This may take up to 
    12 minutes. Log in at the terminal.
    7. Determine if the packet bus fault is still present. If not, you are finished.
    If the problem is still present,
    a. If the old circuit pack was reinserted in Step 5, replace the circuit pack, 
    and repeat Procedure 3.
    b. If the circuit pack was replaced in Step 5, repeat Procedure 3 for the next 
    SPE circuit pack.
    If Procedure 3 fails to identify the cause of the problem, go to Procedure 4.
    For a system with duplicated SPEs:
    1. For SPE circuit packs, follow the ‘‘Replacing Circuit Packs on a Duplicated 
    SPE: Lock-and-Power-Down’’ procedure within the ‘‘Replacing SPE Circuit 
    Packs’’ section to remove and replace the circuit pack.
    2. To remove an EPN Tone/Clock circuit pack, use set tone-clock if 
    necessary to make the suspect circuit pack the standby. (Always check 
    the status of the standby Tone/Clock with status port network before 
    executing an interchange.)
    3. Determine if the backplane pins in the removed circuit pack’s slot are 
    bent.
    4. If the pins are bent:
    a. Power down the carrier if it is not already.
    b. Straighten or replace the pins.
    c. Insert the same circuit pack.
    d. Restore power to the carrier.
    5. If the backplane pins are not bent:
    Insert or replace the circuit pack.
    6. Determine if the packet bus fault is still present. If not you are finished.
    7. If the packet bus fault is still present, do the following:
    a. If the old circuit pack was reinserted in Step 5, replace the circuit 
    pack and repeat Procedure 3 starting at Step 2.
    b. If the circuit pack was replaced with a new one, proceed with the 
    next step. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-74 Packet Bus Fault Isolation and Repair 
    5
    8. Repeat this procedure for the other SPE or Tone/Clock. If both have 
    already been checked, go to the next step.
    9. If all SPE and/or EPN control circuit packs have been checked and the 
    problem is not resolved, continue with Procedure 4.
    Procedure 4
    Procedure 4 is used when the preceding procedures fail or when open leads are 
    present. It is helpful in identifying multiple circuit pack faults and carrier hardware 
    faults. It attempts to isolate the failure to a particular set of carriers and checks 
    only the circuit packs in those carriers.
    In Procedure 4, the TDM/LAN Cable Assemblies and TDM/LAN termination 
    resistor packs are replaced. If this action does not resolve the packet bus fault, 
    the carriers are reconfigured by moving the termination resistor packs on the 
    carrier backplanes in such a manner that certain carriers are disconnected from 
    the bus. To terminate the packet bus at the end of a particular carrier, unplug the 
    cable that connects the carrier to the next carrier and replace the cable with a 
    TDM/LAN terminator resistor pack (see Figure 5-16
    ). When the length of the 
    packet bus is modified with this procedure, circuit packs that are essential to 
    system operation (and the TN771D Maintenance/Test in standalone mode) must 
    still be connected to the new ‘shortened’ packet and TDM busses.
    !DANGER:
    Power must be removed from the entire port network before any cables or 
    terminators are removed. Failure to do so can cause damage to circuit 
    packs and power supplies, and can be hazardous to the technician.
    !DANGER:
    Circuit packs in carriers that are not part of the shortened bus are not 
    inserted. As a result, these circuit packs are not alarmed Ignore alarm 
    status for these circuit packs for now All alarms should be resolved when 
    the cabinet is restored to its original configuration. 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-75 Packet Bus Fault Isolation and Repair 
    5
    Figure 5-16. Carrier Rewiring Example—Rear View of Multicarrier Cabinet
    Procedure 4 consists of two parts. Part 1 attempts to clear the packet bus fault by 
    replacing all the bus cabling and terminators within a port-network. Part 2 
    attempts to isolate the fault to a particular carrier by extending the packet bus 
    from the control carrier to additional carriers one at a time.
    Part 1: 
    1. Power down the port network.
    2. Replace all of the TDM/LAN Cable Assemblies and both TDM/LAN 
    Terminators.
    3. Restore power to the port network.
    4. Determine if the packet bus fault is still present.
    5. If the packet bus fault is resolved, the procedure is completed. Otherwise, 
    go to Part 2.
    TDM/LAN Bus Cable  TDM/LAN Bus Terminator
    Normally
    Con®gured
    Cabinet
    (All 5 Carriers
    Used)Bus Shortened
    to Carrier A Only
    (Control Carrier)Shortened Bus
    Extended to
    Include
    A and B
    Carriers
    Carrier D
    Carrier EFans Carrier A Carrier B Carrier C 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Responding to Alarms and Errors 
    Page 5-76 Packet Bus Fault Isolation and Repair 
    5
    Processor Port Network:
    1. Power down the cabinet and terminate the packet bus so that it extends 
    only from the carrier that contains the active SPE (A or B) to the carrier that 
    contains the Maintenance/Test circuit pack. 
    2. Power up the cabinet, allow the system to reboot, and determine if the 
    packet bus fault is still present. If not, proceed to the next step.
    If there are shorts on the packet bus, perform Procedures 2 and/or 3 for 
    the circuit packs in the active SPE and carriers connected to it on the 
    shortened bus. (Procedure 2 is performed for port circuit packs, and 
    Procedure 3 is performed for SPE circuit packs.)
    3. If the packet bus fault is not present, extend the packet bus to another 
    carrier, and repeat the procedure in the previous step. When the addition 
    of a carrier causes the fault to recur, and if there are shorts, perform 
    Procedure 2 and/or Procedure 3 for only the circuit packs in that carrier.
    4. If the packet bus fault recurs when the packet bus is extended, and if 
    there are no shorts, or Procedures 2 and 3 do not resolve the problem, the 
    added carrier(s) that caused the problem to recur are defective and must 
    be replaced.
    Expansion Port Networks:
    1. Place the Maintenance/Test circuit pack into a carrier that contains the 
    active Expansion Interface circuit pack to permit isolation of the failure to 
    the smallest possible number of carriers.
    2. Power down the cabinet and terminate the packet bus on the carrier with 
    the M/T and active EI.
    3. Determine if the packet bus fault is still present If so, and if there are shorts 
    on the packet bus, perform Procedure 2 and/or Procedure 3 for only the 
    circuit packs in carriers connected to the ‘‘shortened’’ packet bus.
    4. If the packet bus fault is not present, extend the packet bus to another 
    carrier, and repeat the procedure in the previous step. When a carrier that 
    causes the fault to recur is added, and if there are shorts, perform 
    Procedure 2 and/or Procedure 3 for only the circuit packs in that carrier.
    5. If the packet bus fault recurs as the packet bus is extended, and if there 
    are no shorts, or Procedures 2 and 3) do not resolve the problem, the 
    added carrier(s) that caused the problem to recur are defective and must 
    be replaced. 
    						
    							Additional Maintenance Procedures
    Page 6-1 Software Updates 
    6
    DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    6
    6Additional Maintenance Procedures
    Software Updates
    A software update is the complete replacement of the software load running on a 
    switch with a new version of software. Updates are used to provide new features 
    and improved services, and to repair bugs discovered in the field. Note that the 
    process is called a software update; the command used is upgrade software. A 
    description of this command appears in Chapter 8, ‘‘
    Maintenance Commands’’. 
    Software 
    field updates are partial replacements of a software load normally used 
    for emergency bug fixes. Usually, a field update is transmitted electronically to 
    the system from a remote site, but a technician must be on site to apply the 
    update to backup tapes and insure that the system returns to normal operation. 
    This procedure should be guided by the remote facility applying the update.
    Refer to
     DEFINITY Enterprise Communications Server Release 5.4 Upgrades and 
    Additions for R5r
     for specific upgrade information.
    Software Version Number
    Each software load is identified by a version number. The following are typical 
    software version numbers displayed when list configuration software-version 
    is entered:
    SOFTWARE VERSION: DG3r01.06.1.00.0
    SOFTWARE VERSION: G3r5.01.2.0.078
    This identifier is also called the release number or the vintage number. Version 
    numbers are interpreted as follows: 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Additional Maintenance Procedures 
    Page 6-2 Software Updates 
    6
    Release 5r loads:
    The boot image field contains “m” (mips) for G3r systems.
    The system expects any software upgrade to be going from a lower, or older 
    version number, to a higher, or newer version number. To install an older version 
    (for example, when backing out a failed upgrade), follow normal escalation 
    procedures to avoid putting the system into a corrupted state.
    Each software version also has a compatibility index of the form:
    Differences between old and new version numbers and compatibility indexes 
    can be used to determine what service effects can be expected from the update. 
    See the ‘‘
    Service Effects of a Software Update’’ section that follows.
    Service Effects of a Software Update
    Simplex SPE
    The upgrade software command executes a system reboot similar to a reset 
    system 4. Emergency transfer is invoked and all calls drop. The MT login is 
    terminated and error logs are cleared. The service outage lasts for a period of up 
    to 15 minutes. Results of each step in the upgrade process and initialization 
    diagnostics are displayed on the terminal screen. Screen output is described in 
    Maintenance Commands, upgrade software. Failure of initialization will produce 
    an SPE-down mode, described in 
    Initialization and Recovery. Translations are 
    reloaded from the primary storage device and reformatted for the new software if 
    necessary.
    Duplicated SPE
    On a system with a duplicated SPE, a software update may be either 
    call-preserving or call-dropping. The compatibility of the old and new versions 
    determines which type of update is performed. If the major fields of the 
    compatibility indexes of the two versions are equal, then a call-preserving update 
    is possible. The documentation accompanying the update tapes (Engineering 
    Design Information, or EDI, and the Release Letter) should confirm this. With rare 
    exceptions, this is the case when the Feature Version and Product ID numbers 
    match.G3r5 m 01 2 0 078
    Product Boot Major Minor Unscheduled Load
    ID Image Release Release Release Number
    81
    Major Field Minor Field 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Additional Maintenance Procedures 
    Page 6-3 Software Updates 
    6
    If these conditions are not met, The upgrade software call-override option must 
    be used, and the update will result in a system reset level 2 (cold-2 restart). An 
    additional option, preserve-calls, can be added to force the system to attempt to 
    preserve calls, but this must be used with care. If the incompatibility is great 
    enough, this option may cause the system to escalate to a reboot (reset system 
    4). It is recommended that you escalate any such software update.
    Call-Preserving Update
    During a call-preserving update, calls in which two or more parties are 
    connected and talking are preserved. The following types of calls are dropped: 
    wideband calls, held calls, dialing calls, and calls that are connected to 
    announcements, speech synthesizers, or tones. Administered connections are 
    dropped and automatically restored. Feature activation attempts are ignored. No 
    new calls are processed for a brief period. This period usually lasts less than 5 
    seconds but can last up to 1 minute depending on traffic load during the SPE 
    interchange. Conference calls that attempt a new connection are either ignored 
    or dropped.
    Call-Dropping Update
    During a call-dropping update, the effect will be similar to a cold-2 restart (reset 
    system 2). All calls and system links drop, and the MT login is terminated. The 
    service outage lasts up to 4 minutes.
    Preparing for a Software Update
    1. Notify users of anticipated service effects described in the preceding 
    section and arrange to do the update at a suitable time. Also advise 
    appropriate users of the following feature interactions:
    nAdministered connections are temporarily dropped.
    nLeave Word Calling messages stored in the SPE are lost. Those 
    stored in a Message Server Adjunct or AUDIX system are saved.
    nSome feature settings will be lost and must be restored afterward. 
    The effect is the same as a cold-2 restart. Features affected include 
    night service, trunk/hunt group control, and manual/clock-manual 
    override status on time of day routing. For example, hunt groups 
    and attendant are put into night service after the update.
    nACD queues will be lost. There is no mechanism to drain the 
    queues. CMS or BCMS can be used to monitor the queue lengths. 
    If it is important to empty all queues before the update, you must 
    coordinate with the customer to redirect traffic away from ACD 
    splits before the update. Changing vectors to temporarily route 
    calls to a disconnect announcement is one way to accomplish this. 
    ACD agents will need to log in again after the update and their 
    status lamps may be incorrect for about an hour (until periodic 
    background maintenance completes one cycle). 
    						
    							DEFINITY Enterprise Communications Server Release 6
    Maintenance for R6r Volumes 1 & 2  555-230-126  Issue 2
    January 1998
    Additional Maintenance Procedures 
    Page 6-4 Software Updates 
    6
    nCMS links are dropped and restored, resulting in a loss of incoming 
    data during the upgrade. Data loss can be minimized by 
    performing the update soon after the end of a CMS measurement 
    interval.
    nWideband calls are dropped.
    2. Some information which is stored in system memory will be lost and must 
    be manually recorded and then re-entered after the update:
    nRecord all busied out maintenance objects. Enter display errors 
    print, and select error type 18 on the menu. All busyouts will be lost 
    during the update and must be reentered afterward. Disabled 
    maintenance objects will likewise be re-enabled by the update.
    nAll measurement data stored in memory, including BCMS, is lost. 
    Print any desired reports before the update.
    nEnter list report-scheduler. Reports that are currently printing or 
    queued will be lost. Wait until reports are finished printing or notify 
    the customer. Reports are printing if the Link State field displays up 
    on the status sp-link screen.
    nEnter list wakeup print and list do-not-disturb stations print. 
    These feature settings will be lost and must be re-entered 
    afterwards.
    3.Make sure that the system’s health and activity can support a successful 
    update:
    nEnter status spe and verify that the state of health of the SPE is 
    functional. This must hold true for active and standby SPEs when 
    duplicated.
    nEnter display alarms and display errors. Resolve any active 
    alarms or errors against SPE components or the PPN Tone-Clock.
    nEnter status logins and make sure that no other logins except 
    yours are active.
    nEnter status health and look at the amount of load on the system. If 
    call processing is greater than 50 percent, an update is not 
    recommended due to increased customer impact.
    nDisable TTI changes by the change system-parameters features.
    nEnter change system-parameters maintenance and make sure 
    that scheduled daily maintenance will not be running during the 
    update. The Start Time field should be set to a time well after the 
    session will end. If scheduled daily maintenance is running and 
    needs to be shut off, set the Stop Time field to one minute after the 
    current time. Be sure to restore the original settings when finished. 
    						
    All Lucent Technologies manuals Comments (0)

    Related Manuals for Lucent Technologies DEFINITY Enterprise Communications Server Release 6 Instructions Manual